Parameters
Th18
,
Th19
,
Th21
,
Th58
,
Th78
,
Th79
,
Th80
,
Th81
,
Th59
are found in the System menu
Thermostats menu and should be adjusted to the needs of the user and the instruction above.
7.6.3
Configuration
10.1
Picture 21. Configuration 10.1
Work principle:
Recommended values of parameters:
Th18
=5°C;
Th19
=40°C;
Th21
=70°C
Heating plant
The pump is active if the boiler water temperature is above the previously defined value Th19. In order to
avoid freezing, the pump is on even when the water temperature is below Th18. If the water temperature
exceeds value Th21, the pump is activated for safety reasons.
Wiring:
Connect the output for DHW Temperature sensor to the connector.
Connect the output for Buffer temperature sensor to the connector.
Parameters:
They are factory-set.
The following parameters are found in the System menu, submenu Enables:
P26 [selection of configuration] =10;
P75 [DHW Temperature sensor] =8;
P76 [Buffer temperature sensor] =9;
P36 [pump configuration] =14
Parameters
Th18
,
Th19
,
Th21
are found in the
system menu
Thermostats menu
and should be
adjusted to the needs of the user and the instruction above.
7.6.4 Configuration 10.2
Picture 22. Configuration 10.1