INSTALLATION INSTRUCTIONS
19
cod.: 50-00105
NEOPRENE SEALING GASKET
FIXING SCREW
90° FLUE BEND Ø100/60
FLUE TERMINAL Ø 60 - POLYPROPYLENE
WALL PLATE Ø 100 - RUBBER
FLUE PIPE Ø 100
3.8 Flue connections
In order to ensure that the appliance functions correctly and efficiently, the flue connection between
the boiler and the flue terminal must be made using original components specifically designed for
condensing boilers.
Traditional flue components cannot be used for conveying exhaust fumes from condensing boilers,
nor vice versa.
●
In order to make the choice of which flue to install easier, in addition to being drawn differently, the above-
mentioned system is also differentiated in the flue catalogue and general price list by the insertion of the words
“…in polypropylene…” .
●
It is recommended that:
o
for the exhaust discharge duct, the entire length of the flue slopes upwards towards the exterior in order to
facilitate the flow of condensate back to the combustion chamber, which has been specifically designed to
collect and drain the acidic condensate;
o
for the air intake, the entire length of the duct slopes upwards towards the boiler to prevent the entry of
rainwater, dust or foreign bodies into the pipe;
ONLY for use with Horizontal concentric flue kit Ø60/100 mm polypropylene as per manufacturer’s kit No
50-00105.
Discharges exhaust gases and draws combustion air by means of two concentric ducts. The external Ø100 duct
draws the combustion air while the Ø60 duct discharges the exhaust fumes. The discharge duct must be connected
directly to the outside.
MAXIMUM FLUE LENGTH: 1000 mm.