2. FIRST START-UP
SUPPOR
T
C
ENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P08
POST-CIRCULATION HEATING TIMING
THROUGH THIS PARAMETER, IT IS POSSIBLE TO SET THE OPERATION
TIME OF THE PUMP AFTER THE MAIN BURNER TURNS OFF DUE TO THE
ENVIRONMENT THERMOSTAT.
0 - 90
VALUE EXPRESSED
IN MULTIPLES OF 5
SECONDS
(PRE-SET AT 36 X 5 = 180
SECONDS)
P09
POST-CIRCULATION DOMESTIC / STORAGE TIMING
THROUGH THIS PARAMETER, IT IS POSSIBLE TO SET THE OPERATION
TIME OF THE PUMP
AFTER CLOSING THE TAP OR REACHING THE
TEMPERATURE SET IN THE BOILER.
0 - 90
VALUE EXPRESSED
IN MULTIPLES OF 5
SECONDS
(PRE-SET AT 24 X 5 = 120
SECONDS)
P10
DOMESTIC FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM SPEED
IN DOMESTIC PHASE, THAT CORRESPONDS TO THE MINIMUM BURNER
POWER DURING A REQUEST TO OPERATE IN DOMESTIC MODE.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE PARAMETER
P00) AND ON THE GAS TYPE (SEE PARAMETER P02)
45 - VALUE
SET FOR
PARAMETER
P11
THE VALUE IS
EXPRESSED IN HERTZ
(1HZ = 30 RPM)
P11
DOMESTIC FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM SPEED
IN DOMESTIC PHASE, THAT CORRESPONDS TO THE MAXIMUM BURNER
POWER DURING A REQUEST TO OPERATE IN DOMESTIC MODE.
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE PARAMETER
P00) AND ON THE GAS TYPE (SEE PARAMETER P02)
VALUE
SET FOR
PARAMETER
P10 - 203
THE VALUE IS
EXPRESSED IN HERTZ
(1HZ = 30 RPM)
P12
HEATING FAN MINIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MINIMUM SPEED
IN HEATING PHASE, THAT CORRESPONDS TO THE MINIMUM BURNER
POWER DURING A REQUEST TO OPERATE IN HEATING MODE. [SEE
CHAPTER ‘HEAT CAPACITY DIAGRAM (KW) – ELECTRIC FAN FREQUENCY
(HZ)’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE PARAMETER
P00) AND ON THE GAS TYPE (SEE PARAMETER P02)
45 - VALUE
SET FOR
PARAMETER
P13
THE VALUE IS
EXPRESSED IN HERTZ
(1HZ = 30 RPM)