1. INSTALLATION
INST
ALLER
INSTALLATION ON SELF-SUPPORTING FRAME
WARNING
During the installation of the heat generator, pay maximum attention to the installation of the
self-supporting frame. The frame must rest on a perfectly flat surface and, when supported against
the wall, the latter must be perfectly angled. The incorrect slopes of the device can cause the incorrect
discharge of condensate by means of the discharge duct with consequent condensate stagnation inside
the condensate module. The correct installation of the frame allows obtaining, acting on the lower
bracket, a counterslope of the device against the perpendicular.
In order to mount the frame and therefore the
generator, proceed as follows:
1. check the angle of the wall with the floor;
2. assemble the side profiles 3 and 4 on the pillars 1 and 2 (fig. 1);
3. assemble the side pillars 1 and 2 on the horizontal crossbeam 5;
4. assemble the central crossbeam 8 and the lower one 7;
5. complete the assembly, position the frame binding it to the wall 9 (if provided) and on the floor 10;
6. mount the upper bracket 6 and hook the eyelets of the boiler into the adequate hooks 11;
7. make sure that the frame is angled, adjust the inclination of the boiler by means of the lower bracket
(see "Wall mounting by means of fixing bracket") ensuring an inclination of the boiler, against the
vertical, of about 1–1.5°;
8. complete the installation by assembling the hydraulic components.
4
6
3
7
5
1
2
8
10
10
10
10
9
9
11
11
fig.1