54
R1BK_50-RAD-ING-Manuale-1812.1_SK.3
2 Co
dici d
i seg
nal
azi
on
e anom
ali
e_
sol
o ris
c_
M
IAH
4_
firm
.L2
24A
_E
N
2. MAINTENANCE
SUPPOR
T CENTRE
CODE
FAULT
POSSIBLE CAUSE
SOLUTION
RESET
E03
FUMES SAFETY
THERMOFUSE (102°C)
THERMOFUSE BROKEN;
REPLACE IT;
MANUAL RESET
(PRESS THE RESET
‘
’ KEY).
THERMOFUSE CABLE
DISCONNECTED.
CHECK THE WIRING.
E04
WATER MISSING IN THE
SYSTEM
INSUFFICIENT WATER
PRESSURE INSIDE THE SYSTEM
(LOWER THAN 0.3 BAR);
LOAD THE SYSTEM;
AUTOMATIC.
WATER PRESSURE SWITCH
CABLE DISCONNECTED;
CHECK THE WIRING;
WATER PRESSURE SWITCH
BROKEN.
REPLACE IT.
E05
HEATING PROBE
BROKEN OR INCORRECTLY
CALIBRATED PROBE
(RESISTANCE VALUE 10
KOHM AT 25 °C NTC);
REPLACE IT;
AUTOMATIC.
DISCONNECTED OR WET
PROBE CONNECTOR.
CHECK THE WIRING.
E15
RETURN PROBE
BROKEN OR INCORRECTLY
CALIBRATED PROBE
(RESISTANCE VALUE 10
KOHM AT 25 °C NTC);
REPLACE IT;
AUTOMATIC.
DISCONNECTED OR WET
PROBE CONNECTOR.
CHECK THE WIRING.
E16
ELECTRIC FAN
ELECTRIC FAN BOARD
BROKEN;
REPLACE IT;
AUTOMATIC.
ELECTRIC FAN BROKEN;
REPLACE IT;
FAULTY POWER SUPPLY
CABLE.
REPLACE IT.
E18
I N S U F F I C I E N T
CIRCULATION
EXCHANGER OBSTRUCTED;
CLEAN OR REPLACE THE EXCHANGER;
AUTOMATIC.
CIRCULATOR BROKEN OR
DIRTY IMPELLER.
CLEAN THE IMPELLER OR REPLACE
THE CIRCULATOR.