2. FIRST START-UP
SUPPOR
T CENTRE
PARAMETER
DESCRIPTION
RANGE
FUNCTION
P13
HEATING FAN MAXIMUM SPEED ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN MAXIMUM SPEED
IN HEATING PHASE, THAT CORRESPONDS TO THE MAXIMUM BURNER
POWER DURING A REQUEST TO OPERATE IN HEATING MODE [SEE
CHAPTER ‘HEAT CAPACITY DIAGRAM (KW) –ELECTRIC FAN FREQUENCY
(HZ)’].
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE PARAMETER
P00) AND ON THE GAS TYPE (SEE PARAMETER P02)
VALUE
SET FOR
PARAMETER
P12 - 203
THE VALUE IS
EXPRESSED IN HERTZ
(1HZ = 30 RPM)
P14
STARTING STEP ADJUSTMENT
THROUGH THIS PARAMETER YOU CAN SET THE FAN SPEED DURING
START-UP
THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE PARAMETER
P00) AND ON THE GAS TYPE (SEE PARAMETER P02)
VALUE
SET FOR
PARAMETER
P10 - 203
THE VALUE IS
EXPRESSED IN HERTZ
(1HZ = 30 RPM)
P15
ANTI-LEGIONELLA FUNCTION
(FOR STORAGE BOILERS ONLY)
THROUGH THIS PARAMETER YOU CAN ACTIVATE/DEACTIVATE THE
“ANTILEGIONELLA” HEAT TREATMENT OF THE STORAGE TANK. EVERY
7 DAYS THE WATER TEMPERATURE INSIDE THE STORAGE IS HEATED
BEYOND 60 °C THUS GENERATING A BURNING HAZARD. KEEP UNDER
CONTROL SUCH DOMESTICH HOT WATER TREATMENT (AND INFORM THE
USERS) TO AVOID UNFORSEEABLE DAMAGES TO PERSONS, ANIMALS
AND PROPERTY. A THERMOSTATIC VALVE SHOULD BE INSTALLED AT
THE DOMESTIC HOT WATER OUTLET TO AVOID ANY BURNS.
0 - 1
0 = DISABLED
1 = ENABLED (PRE-
SET BY DEFAULT ON
STORAGE BOILERS ONLY)