25 |
P a g e
Thermostat is satisfied
Condenser turns off
Fan speed ramps down to zero, extracting any remaining cooling from the DX coil
Dehumidification
When in cooling mode, a dehumidification function can be set using system switch 3 as follows:
OFF - Normal cooling fan runs at rate set by COOL CFM switch
ON - fan runs at 75% of COOL CFM rate for 15 min. and then reverts back to rate set by
COOL CFM
Fan Mode
R is connected to G
If fan is set to “ON” on thermostat, fan runs as follows:
If SYSTEM switch 4 is OFF, fan runs at selected HEAT CFM rate
If SYSTEM switch 4 is ON, fan runs at 50% of selected HEAT CFM rate
If fan is set to “OFF” on thermostat, fan runs at HEAT or COOL CFM settings
Constant Low Fan Circulation
Fan may be run at a low rate using system switch 4 as follows:
OFF – fan runs at rate set by HEAT CFM switch
ON – fan runs at 50% of rate set by HEAT CFM switch
Pump Exerciser
The circulating pump is exercised for 1 min every 24 hr when the ecosmart is OFF,
COOLING (Y), COOLING2 (Y2) or FAN (G) to prevent the possibility of ‘sticking’ due to
sediment and to meet local codes.
During the 1 min pump on-time, the fan is turned off and resumes once the pump
exercising is completed
Pump runs continuously if the outlet air temperature drops below 40F to prevent the
chance of freezing