62
Stop Valve
Full Bore Isolating Valve
Pressure Reducing Valve
Shower
Thermometer
Cold Water
Hot Water
Mixed Water
Check Valve
Recirculation Pump
Key
Strainer / Filter
Needle Valve
Flow indicator
Safety Valve
Water
Heater
Temp High 53˚C
Setpoint 49˚C
Temp Low 38˚C
Setpoint 49˚C
Temp High
Error Temp
49˚C
Problem:
“LCD Display shows any of the following...”
Blend circuit /
'DRV Programming
Software'
Blend circuit does not fully return to normal
temperature within the
'Disinfection
Timeout'
period. Check the following:
•
Disinfection Timeout value.
•
Cool Down start and finish times.
•
Early abort of disinfection cycle.
•
Use of a dump valve to speed up cool
down time.
dump valve
position
Содержание DRV40
Страница 43: ...43 Step 5 Step 6 ...
Страница 46: ...46 2 5mm HEX 3mm HEX 13mm HEX Step 1 Step 3 Step 4 Step 2 Seals shown 1 1 when printed at Full Scale ...
Страница 47: ...47 3mm HEX Step 5 3mm HEX Step 6 ...
Страница 48: ...48 3mm HEX Step 7 Step 7a Step 7b Seals shown 1 1 when printed at Full Scale ...
Страница 50: ...50 Only use silicone based lubricants on rubber seals A D E E E D B C 1793 215 Seal Pack Step 10 ...
Страница 51: ...51 A D B E C x 2 x 3 Seals shown 1 1 when printed at Full Scale ...
Страница 54: ...54 Calibrate HotEnd Valve Reset Temp 48 C Setpoint 49 C drv40 Rada 6 Wait for the DRV40 to reset ...