mechanical  limit  of  the  actuator  or  the 
attached equipment. Failure hereof can cause 
mechanical  damage  of  the  actuator  or  the 
equipment. Please be advised that by moving 
the  external  reference  switch  the  extended 
position  will be  moved as  well by the same 
distance in the same direction. The stroke is 
stored as a fixed length with the zero position 
defined by the external limit switch. 
 
 

Connection 
 

The  EPS  02  is  equipped  with  a  four  pole 
pluggable X2 connector for the limit  switch 
output  relay  contacts  and  a  five  pole 
pluggable  X1  connector  for  the  24V  DC 
power  supply,  external  limit  switch  and  the 
motor  thermal  switch.  For  the  physical 
layout  please  refer  to  the  connection 
diagram. 
 
 

Power Supply Connector X1 

 
The  five  pole  female  connector  is  equipped 
with  screw  terminals  for  easy  interface  to 
customers  control  wires.  Each  terminal  will 
accept one # 16 AWG wire. 
 
Pin 1  GND 
Pin 2  +24V DC 
Pin 3  External reference switch 
Pin 4  Aux 24V DC supply 
Pin 5  Motor Over temperature switch 
 
 

Relay Contact Plug 

 
There  are  two  potential  free  relay  output 
contacts available to shut down the actuator. 
The  contacts  should  be  hard  wired  into  the 
reversing  motor  starter  or  VFD  control 
circuit  to  provide  reliable  end  of  stroke 
protection.  Within  the  permissible  stroke 
range of the actuator the contacts are closed. 
Relay output contact landed on terminal X2 
pin 1+2 will be opened if the selected retract 
position  is  reached  or  if  24V  DC  on  the 
external  reference  switch  input  X1  pin  3  is 
present. Relay output contact landed on  
 

 
 
 
terminal  X2  pin  3+4  will  be  opened  if 
the selected extend position is reached. 
 
X2 pin 1+2: Limit retract 
X2 pin 3+4: Limit extend  
 
Note:  If  the  24V  DC  supply  power  is 
turned  off  both  relay  output  contacts 
will open up. 
 
 

Technical Data 

 
EPS 02 Power Supply requirement: 
Voltage:  24V DC  
Range:  +20% / -30 % 
Current: 50 mA 
 
Output relay Contact: 
Max Voltage: 250V AC @ 5A 
                           30V DC @ 5A 
 
Digital Input: 
Voltage level: 24V DC  
Range: +20% / -30% 
 
Motor Over Temperature Protection: 
Input Type: Thermal Switch 
  
Position Accuracy: Stroke Length / 
   10 Bit * RPM on Sensor Shaft 
 
Data Storage 
Duration: 10 Years 
Battery: Lithium 1.2Ah 
 
Operating Temperature: -40

o

 F to 185

o

 F 

Protective  Rating:  IP  00,  circuit  board 
sealed 
Enclosure: Without 
Connector: 

Pluggable 

terminal 

connection 
 
 

LED Display 
 

The operating status of the EPS 02 will 
be indicated via three on board LED’s. 
 
LED yellow: 
LED is on steady if the actuator is in its 
selected stroke range. The LED is off if 

Содержание EPS 02

Страница 1: ...an be used Three on board LED s will guide the user through the initial setup procedure and will function thereafter as operation control signals Function The EPS 02 consists of two potential free rel...

Страница 2: ...e hard wired into the reversing motor starter or VFD control circuit to provide reliable end of stroke protection Within the permissible stroke range of the actuator the contacts are closed Relay outp...

Страница 3: ...om one function to the next Push button S2 is used to select the value in each of the selected function There are two settings which can be made independent from each other 1 Setting of the end of str...

Страница 4: ...LED pattern will change to its normal operational condition See above LED Display section Manual Position Setting Diagram TTL Level Communication Interface The EPS02 is equipped with a TTL level comm...

Страница 5: ...n to the stroke direction A counting direction will be selected with the radio buttons External Reference Function If an external reference switch is used this selector box will be enabled The positiv...

Страница 6: ...the screen into the EPS02 the Send Parameter Block button needs to be pushed This refers to all configuration screens Reed switch sector The reed switch sector display block is for diagnostic and func...

Страница 7: ...a negative and positive band around the selected switching point This number should be selected large enough to avoid shattering of the output signal and small enough to provide the desired position...

Страница 8: ...ollowing selections can be made 0 10V 10 0V 0 20mA 20 0mA 4 20mA and 20 4mA Based on the selection Cylinder max Stroke from the main screen the Limits for Analog Output Signal slide bar is initialized...

Страница 9: ...of the EPS06 As soon as the forward or reverse auxiliary contacts of the reversing motor contactor or VFD circuit are pulled in the on delay timer with the predefined Motor Rush in Time Delay Retract...

Страница 10: ...he main cylinder setting screen changes from red to green Connection Problem Trouble Shooting The most common problem is the incorrect selection of the COM Port With the EPS02 EPS06 connected and powe...

Страница 11: ...m Examples The EPS 02 limit switch contacts are hard wired into the reversing motor starter circuit The EPS 02 output signals are wired as permissive signals into the control circuit of a variable fre...

Отзывы: