Filename:  Catalyst Ethernet Addendum 1 1 V1_5 released 

RACO Manufacturing and 

Engineering 

  

Page 4 (21) 

 

Introduction 

Are you familiar with the operation of the Catalyst Data Logger/Autodialer yet? 

Changes to a few, very specific features of the Catalyst are described in this addendum.  

It 

is assumed that 

the reader of this addendum is already familiar with the basic operation and programming method of the 
Catalyst product and also is familiar with Alarmware software. If

 

this is not the case, please take the time 

necessary to familiarize yourself with the Catalyst  autodialer by reading the Owner's Manual. 

 

Important Note:

  It is important to note that a user cannot use the front keys of the Catalyst to program or 

change any Ethernet settings.  For this reason, it is crucial to use this addendum and Alarmware to 
configure the IP address of the Catalyst to identify and configure the device for Network traffics.  

1.

 

More info about the network and products 

For further information about the Catalyst Ethernet Option products, please consult the RACO Mfg and 
Eng web pages at 

www.racoman.com

 .  The latest manuals, Alarmware 2.0 software, and EDS-files (also 

included in the CD that is shipped with a new Catalyst Ethernet) etcetera can be downloaded from the 
online support sections of the web site.

 

For more information concerning the EtherNet/IP network the Open EtherNet/IP Vendor Organization has a 
webpage.  Please visit 

www.odva.org 

 for more information about EtherNet/IP.

 

For more information concerning the ModbusTCP network the Open Modbus Organization has a  webpage.  
Please visit 

www.modbus.org

  for more information about ModbusTCP.

 

For information concerning the Allen Bradley PLC’s refer to the Rockwell Automation homepage

 

www.rockwellautomation.com

 

 

2.

 

When should you use this addendum? 

The information provided in this document helps the user setup the Ethernet communication 
between the Catalyst and the Ethernet network.  It is assumed that the user has already connected 
the Catalyst to the Ethernet network and is ready to setup the remote channels (section 1.1.2 in the 
main Catalyst manual). 

Please note that this addendum is in effect a new section to the Industrial Networks section of the 
manual (Section 1.9.1 in the main Catalyst user Manual).  Therefore, the content of this addendum 
covers all the requirements of connecting to the Ethernet network, which also includes all testing 
and diagnostics. 

 The main purpose of connecting to the Ethernet network is to get the PLC data natively instead of 
connecting on other external network bridges. 

Содержание Catalyst

Страница 1: ...06 18 Filename Catalyst Ethernet Addendum 1 1 V1_5 released RACO Manufacturing and Engineering Page 1 21 Addendum to Catalyst Owner s Manual How to configure a Catalyst EtherNet IP with RSLogix 5000 A...

Страница 2: ...Document history Revision Date Description Author 1 00 2014 3 17 Document created Michael Jammal 1 1 2014 4 14 Modifications and verification J Garnett S Pottier 1 2 2014 4 15 Updated M Jammal 1 4 201...

Страница 3: ...EtherNet IP protocols Addendum Table of Contents Document history 2 Introduction 4 1 More info about the network and products 4 2 When should you use this addendum 4 3 Requirements 5 4 Determining Ne...

Страница 4: ...D that is shipped with a new Catalyst Ethernet etcetera can be downloaded from the online support sections of the web site For more information concerning the EtherNet IP network the Open EtherNet IP...

Страница 5: ...Name Type Version Rockwell PLC ControlLogix5000 n a PLC software RSLogix 5000 13 04 00 RACO IPConfig tool RACO IPConfig 2 1 1 1 Catalyst EtherNet IP Network Interface Addendum Catalyst EtherNet IP Eth...

Страница 6: ...will go from 0 to 1 indicating that the communication with the network is impaired and if the Catalyst is programmed to look for this change A bit flipping from 0 to 1 can report the loss of communic...

Страница 7: ...Address Description Size Limitation Catalyst SNA 0xxxx Coil number xxxx 1 bit 1 node 0xxxx 1xxxx Input number xxxx 1 bit 1 node 1xxxx 2xxxx Input register number xxxx 16 bit 1 node 3xxxx 3xxxx Output...

Страница 8: ...nk Similarly when addressing the input register 3xxxx allow for two consecutive 16 bit words keeping in mind the word is reserved but not used Hence consecutive addressing of both Input and Output Reg...

Страница 9: ...r can identify the RACO Ethernet autodialers in the Ethernet modules and tags To configure the PLC and the EtherNet IP network the tool RSLogix 5000 is used Firstly the PLC needs to be configured and...

Страница 10: ...Saved 2014 06 18 Filename Catalyst Ethernet Addendum 1 1 V1_5 released RACO Manufacturing and Engineering Page 10 21 Figure 2 Adding the PLC to the configuration...

Страница 11: ...e Ethernet I O module Right click on the I O configuration directory in the navigation list to the left as seen below Figure 3 Adding the Ethernet module Click on new module and select the desired Eth...

Страница 12: ...the settings for the Ethernet module 8 2 EtherNet IP network configuration The second step is to configure the EtherNet IP network and adding the RACO Catalyst EtherNet IP module to the configuration...

Страница 13: ...module First enter a name for the Catalyst module In the example below we call it RACO Ethernet This name will create a tag in RSLogix 5000 which can be used to access the memory location in the PLCs...

Страница 14: ...e enter 32 in this case stands for 32 instances of 8 bits If we had been using Data INT or Data DINT we would have to recalculate the size to match the data type so Data INT would have been 16 16 bit...

Страница 15: ...Inhibit Module isn t checked After this press finish Now the Catalyst has been added to the I O configuration in RSLogix 5000 The main screen will look as follows Figure 10 The main screen when the c...

Страница 16: ...t Ethernet Addendum 1 1 V1_5 released RACO Manufacturing and Engineering Page 16 21 Select Go Online from the Communications menu Figure 12 Opening the online window A new window appears select Downlo...

Страница 17: ...for the same I O size and IP settings as in the PLC configuration The configuration of the IP settings and the I O sizes is described in the two following chapters In the subsequent two chapters the...

Страница 18: ...see image below Figure 15 The RACO IPConfig tool The program scans the network for RACO Gateway Ethernet modules The settings can be configured manually or the DHCP function can be used For the RACO G...

Страница 19: ...the Modbus RTU side of the network 10 1 Monitoring the tags First go online and switch to Remote Run on the PLC To monitor the tags open the Controller Tags window and go to monitor tags Three tags n...

Страница 20: ...thernet cable into Ethernet outlet Select protocol Ethernet then click Ethernet Configuration This will bring up RACO IPConfig which must be in the same directory as Alarmware Use Raco IPConfig tool t...

Страница 21: ...et up a heartbeat channel to monitor communications recommended Select a channel for example channel 56 SNA 1 2 01992 Alarm on 1 Raw Value 0 reported as 0 Note To reset Catalyst to Factory Defaults Tu...

Отзывы: