RAB Lighting is committed to creating high-quality, affordable, well-designed and energy-efficient LED lighting and controls that make it easy for electricians to install 

and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]

ADJUSTABLE CONTROL PARAMETERS 

(Continued)

SETTING MOTION DETECTION SENSITIVITY  

(factory default setting is ideal for most applications)

Trimpot

1.

Hold push button for approx. 3 seconds to enter test mode

2.

Adjust the Time Delay trimpot to the hard stop setting for the
desired sensitivity (options: 5 or 10 min = Low; 15 or 20 min =
Med; 30 min = Max; default Max)

3.

Hold push button for approx. 3 seconds to exit test mode

4.

Return Time Delay to desired setting

WSREM Remote

1. Aim the remote at the IR receiver on the sensor
2. Select “New Settings” and “Sensitivity”
3. 3. Choose from the options of Low, Med or Max
4. 4. Select “Send”; remote displays “Settings Received”

SETTING LIGHT LEVEL HOLD-OFF

Adjust during daylight hours when ambient light is at the 
desired level.

Trimpot

Adjust the trimpot on the sensor housing to desired photocell 
setting (analog wheel with hashmarks: 1-300fc; default 300fc).

WSREM Remote

1. Aim the remote at the IR receiver on the sensor
2. Select “Adjust Photocell Setting”
3. Choose from the range of 1fc - 300fc with 1 footcandle
increments
4. Select “Send”; remote displays “Settings Received”
The light level values referenced are approximate and reference 
4000K CCT. Variations in color temperature may affect the actual 
levels the sensor sees. It is recommended that light level hold off 
be set up in the morning for best results.

Notes: 

Any adjustments made will override any previous settings 

whether manually made on the sensor or through the WSREM 
commission tool. Adjusting Time Delay does not affect Sensitivity 
and vice versa.

PUSH BUTTON FUNCTIONS

The following functions are available via the Push Button.

Manual Mode:

 To toggle the unit in or out of Manual Mode, 

quickly press the Push Button to toggle the load ON or OFF. 
When the load is turned ON manually, it will remain ON as long 
as motion is detected and the time delay has not expired. If the 
load is turned
OFF manually, the sensor holds the load OFF for as long as 
motion is detected and then for an additional 5 minutes of no 
motion detection. The next time the sensor detects occupancy, 
and the ambient light is lower than the established light level, 
the sensor automatically turns ON the load.

Test Mode: 

To place the unit in a 10 minute Test Mode, press the 

Push Button for about 3 seconds, or enable the Test Mode with 
the WSREM. The LED will flash once confirming you are in Test 
Mode. To exit Test Mode, press and hold the Push Button for 3 
seconds. Walk-test the unit to ensure proper detection.

Service Mode:

 To toggle the unit in or out of Service Mode, 

press and hold the Push Button for about 6 seconds. The LED 
will flash twice confirming you are in or out of Service Mode. In 
Service Mode, the LED and load will always be ON.

Power Up On Mode:

 Press and hold the Push Button for about 

9 seconds to enable Power Up ON Mode. The LED will flash 
three times confirming Power Up ON is enabled. In this mode, 
the sensor will turn the connected loads ON upon restoration of 
power.

Power Up Off Mode: 

Press and hold the Push Button for about 

12 seconds to enable Power Up OFF Mode. The LED will flash 
four times confirming Power Up OFF is enabled. In this mode, 
the sensor will keep the connected loads OFF upon restoration 
of power. The sensor is set to this mode by default.

Factory Default: 

To manually return the unit to factory default 

settings, press and hold the Push Button for about 15 seconds. 
This will return all settings to factory default with the exception 
of time delay and light level, which will be set to the current 
trimpot settings. When using the WSREM remote to return 
to factory default, all settings will be returned to the original 
factory settings regardless of current trimpot positions.
The LED will remain solid ON confirming it has been reset to the 
factory default.

Cancel: 

To prevent any changes from being made, hold the 

push button for about 18 seconds. For example, if resetting to 
factory default (or any other setting) is not desired then keep 
holding until you reach 18 or more seconds. The LED will turn 
off after 18 seconds to indicate there were no changes made.

INSTRUCTIONS

 

HIGH/LOW BAY PASSIVE INFRARED OCCUPANCY AND DAYLIGHT SENSOR

Содержание LOS800

Страница 1: ...n power is OFF before installing or maintaining fixture No user serviceable parts inside PIR Sensor with IR remote capability SPECIFICATIONS AND FEATURES OPTICAL Indoor use only Operating Temperature 32 F to 158 F 0 C to 70 C Operating Humidity 5 to 95 noncondensing Line voltage for direct connection to load 120 277 347V 60Hz or 230V single phase 50Hz operation Power consumption 0 2W Adjustable ti...

Страница 2: ...eting rablighting com INSTRUCTIONS HIGH LOW BAY PASSIVE INFRARED OCCUPANCY AND DAYLIGHT SENSOR LENS MASKING AND COVERAGE Lens Dimensions Top coverage pattern Side coverage pattern Top coverage pattern with mask Side coverage pattern with mask Shown with snap on rotatable mask for aisleway coverage included with sensor 50 25 0 25 50 0 50 25 25 50 100 50 25 0 25 50 0 50 25 25 50 100 0 10 10 20 20 30...

Страница 3: ... any necessary mounting accessories and attach them to the sensor making sure that the flying leads from the power module are accessible 6 Connect the line voltage and load wires to the sensor leads as shown in the Wiring Diagram see Figure 4 Do not allow bare wire to show Make sure all connections are secure 7 Restore power from the circuit breaker SETTING TIME DELAY Trimpot 1 Adjust the trimpot ...

Страница 4: ...n is detected and the time delay has not expired If the load is turned OFF manually the sensor holds the load OFF for as long as motion is detected and then for an additional 5 minutes of no motion detection The next time the sensor detects occupancy and the ambient light is lower than the established light level the sensor automatically turns ON the load Test Mode To place the unit in a 10 minute...

Страница 5: ...here is no motion detected after the first 30 seconds If occupancy continues beyond the first 30 seconds the established time delay applies Default setting is Disabled Visual Alert When enabled Visual Alert turns the load OFF for 1 second to warn any occupants of impending shutoff 1 minute before the time delay countdown expires Default setting is Disabled Occupancy mode When Occupancy mode is dis...

Отзывы: