Selecting a Location

Locate the LightAlert LOS1000 where 

it has an unobstructed view of the 

room, particularly the areas normally 

occupied by people.Ideal mounting 

height is 3.5 to 4.5 feet above the 

floor.

 

If people can not see the sensor lens 

from their normal positions in the 

room, the sensor will not detect their 

presence.

High cabinets, walls, doors and other 

obstructions may limit the sensor’s 

view of the entire room. If obstructions 

can be moved the sensor will have 

a better view. If the areas obstructed 

are not areas normally occupied, the 

sensor will still be able to see normal 

occupancy.

If the room is L shaped or the sensor’s 

view is badly obstructed from the door 

switch location, use the LightAlert 

LOS2400 ceiling mounted sensor 

instead of the LOS1000.

Ceiling mounted LOS2400  

sensor with 360° detection

Do not locate sensor over or looking 

at heating vents, baseboard heaters, 

hanging plants or air conditioners. 
Do not locate sensor where it will view 

direct sunlight.
If the sensor’s location gives it a view 

of other rooms or hallways, lights 

will be turned on when movement 

is detected in these adjacent areas. 

If this is undesirable, the sensor’s 

detection zone may be restricted by 

covering a portion of the lens with a 

white paper label or tape

.

Cabinet obstructs sensor’s

view of active area

Sensor

Obstruction moved,

sensor has full view

Sensor

Sensor has view of

adjacent area

Sensor

1

Caution:

 

TURN OFF ALL POWER BY 

REMOVING THE POWER FUSE 

OR TURNING OFF THE CIRCUIT 

BREAKER FOR YOUR SAFETY 

AND TO PREVENT DAMAGE TO 

THE UNIT.  

 

Please read this entire Owner’s 

Manual before proceeding. 

 

All wiring should comply with local 

electrical codes and may require a 

qualified electrician. 

 

Make sure the total lighting 

load connected to the LightAlert 

LOS1000 does not exceed the 

following:

120 VAC

Max 1000W ballast

 

   Max 800W incandescent

277 VAC: Max1800W ballast

Exceeding the wattage limits may 

damage the unit. To switch more 

wattage, an electrician can install a 

relay to handle the load. 

 

Do not use LightAlert LOS1000 

to control high intensity discharge 

lights, fans, heaters 

or motors. Small bathroom exhaust 

fans may be used with LOS 1000. 

 

The LOS 1000 may be used with 

both standard and program rapid 

start electronic fluorescent ballasts. 

 

When the LOS1000 is initially 

installed and the main power circuit 

is restored, it will take 3 min before 

the LOS1000 will automatically 

switch the light off when no one 

is present. It takes 3 min for all 

circuits, including timer and memory 

to stabilize.

Installation

Installation Step by Step:

1. 

Remove the existing switch, if 

necessary. 

2. 

Connect green ground lead from 

LOS1000 to system ground. 

3. 

Connect hot incoming power line to 

black sensor wire. Connect lighting 

load to the red sensor wire. 

4. 

Twist on wire nuts. Secure with 

electrical tape. Mount LOS1000 in 

wall box with two screws provided. 

5. 

Place switch in OFF position before 

turning on power. 

6. 

Press the Auto/Off switch IN to 

“Auto”. After a short delay, the lights 

will turn ON. When the room is 

vacted, the lights will turn OFF after 

the time delay you set. 

7. 

See “Adjustments” section for 

control options. Only make 

adjustments after a 3 minute 

warmup period. 

8. 

Attach the wall plate.

 

WALL MOUNTING BOX

ADJUSTMENT 

ACCESS COVER

(Removable only

when switch plate

is off)

Black

Red

White

Black

2

4

5