Step 9
Evacuation

Gauges can now be attached to the service ports - 

SERVICE PORTS HAVE A 5/16" CONNECTION TO THE GAUGE SET SO AN ADAPTOR IS REQUIRED

Once the gauges are attached the line set can be leak checked using Nitrogen at 300 Psig
Evacuate the unit down to a minimum of 200 Microns, break vacuum with Nitrogen to further leak check
Re-evacuate the system down to 200 Microns or lower
This is an R410A System it is essential that a deep vacuum be pulled on the system to remove all traces of
moisture

Step 10
Main Power Wiring

Electrical Wiring should be done in accordance with all National Electrical
Code (NEC) and local state/city building codes

Tip : Small Electrical Screwdriver is required for unit terminals

Breaker size and wiring must be sized for the rating plate amperage, MCA and MOP
If a smaller than required breaker is used possibility of unit damage etc could occur
Use only HACR type breakers, each system installed must have a separate branch circuit with an individual 
breaker/fuse

QCIC-09

QCIC-12

QCIC-18

QCIC-24

Breaker Size

15A

15A

15A

20A

RLA

6.7A

8.8A

5.3A

8.6A

MCA

8.2A

10.8A

6.5A

10.6A

QCIH-09

QCIH-12

QCIH-18

QCIH-24

Breaker Size

15A

15A

15A

20A

RLA

6.9A

9.0A

5.5A

8.6A

MCA

8.4A

11.0A

6.8A

10.6A

A local disconnect should be installed adjacent to the Outdoor unit in accordance with National and Local Codes 

The Outdoor unit provides power for the Indoor unit, no disconnect is required between the Outdoor and 
Indoor units
Line voltage from the disconnect should be wired to 

N - L (115V Unit)
L1 - L2 (208/230V Unit)

Remove RHS Knockout on the terminal access panel for whip/wiring connection
Ground connection must be made to the terminal plate

Tip : For easier access to the Terminals in the Outdoor unit remove the lower access panel to install whip and
sealtite connectors for conduit

Local Disconnect
and Whip Connected

Heat Pump unit terminals

L1 - L2 : Power from Breaker
L3 - L4 : Power to Indoor unit

1 Compressor Signal
2 Reversing Valve
3 Outdoor Fan

Installation and Maintenance Manual

Unit Installation (Cont)

Содержание QSHE-092

Страница 1: ......

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ...manual 1 Check Rating Plate for correct system voltage before installing the unit Installing and operating a unit with the incorrect voltage may result in malfunction or other issues and will void th...

Страница 16: ...t s below 65 DegF so a Low Ambient Head Pressure Controller See accessories is required as is a Crankcase Heater field supplied Residential Bedrooms Family Rooms etc These require ballpark sizing of a...

Страница 17: ...ide recommend the Aspen brand of Condensate Pump follow their wiring diagram recommendations This pump is installed externally to the unit Follow Instructions failure to follow instructions may cause...

Страница 18: ...ng the weight of the unit Use a level to ensure mounting bracket is leveled so condensate can drain properly Step 5 Prepare Unit Line Set Connections Rotate refrigerant line stubs set gently through 9...

Страница 19: ...set between the Outdoor unit and the Indoor unit MUST have both refrigerant lines insulated as condensing device is located in the Outdoor unit Gently bend the line set stubs from the Indoor unit to...

Страница 20: ...system installed must have a separate branch circuit with an individual breaker fuse QCIC 09 QCIC 12 QCIC 18 QCIC 24 Breaker Size 15A 15A 15A 20A RLA 6 7A 8 8A 5 3A 8 6A MCA 8 2A 10 8A 6 5A 10 6A QCIH...

Страница 21: ...is required then cut the lead and extend it using 18 AWG thermostat wire Sensor is resistance based using 3 5V DC Defrost Sensor wire connection in Outdoor unit is accessed by removing top panel from...

Страница 22: ...ture is above 65 DegF to prevent damage to the compressor Unit has a 3 minute time delay for the compressor start up operation Unit is charged with enough R410A refrigerant for a line set of 25ft leng...

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Отзывы: