Step 11
Controls Wiring

Electrical Wiring should be done in accordance with all National Electrical
Code (NEC) and local state/city building codes

ALL CONTROLS WIRING BETWEEN INDOOR AND OUTDOOR UNIT IS HIGH VOLTAGE
MINIMUM 14 AWG WIRE MUST BE USED

Remove terminal covers from Indoor unit and wire to the terminals, small electrical screwdriver required
Control wiring from the Outdoor Unit must be a point to point i.e. the terminal that the wire is attached to on  
the Outdoor unit must be the same terminal it is wired to in on the Indoor unit

This is extremely important : Switching the L3 - L4 or N1 - L1 wires over will allow the Indoor unit to operate but 
it will not provide controls signals for the Outdoor unit so that the compressor will not operate
Ground connection should be made to ground screw marked in Indoor unit

If unit is a Heat Pump, the Defrost Sensor must be connected from the Indoor unit to the Defrost Sensor 
in the Outdoor unit.  Standard lead length is 25ft, if a longer length is required then cut the lead and 
extend it using 18 AWG thermostat wire.  Sensor is resistance based using 3.5V DC

Defrost Sensor wire/connection in Outdoor unit is accessed
by removing top panel from unit, wire is coiled on base of
unit

Control Wiring at Outdoor unit (Heat Pump unit shown)
Note use of colored wire (supplied with Line Set) and defrost 
sensor connected (Heat Pump only)

Ground wires connected to the terminal plate
Indoor and Outdoor units must be grounded

Step 12
Condensate Hose 

Unit is provided with approximately 18" of Condensate Hose

Hose connection is sized to accept a 3/4" OD or 5/8" ID Clear Plastic Hose to then extend to building drain
All condensate hose extensions should be in accordance with local building codes
Remember water only flows downhill to ensure positive draining from the unit

Check using water for a positive flow of Condensate

The basic system installation is now complete
The unit is now ready for start up - 
Use this time to ensure that worksite is tidy.  Quietside recommend the use of Slimduct products to hide 
the refrigerant line set interconnects - available from your Quietside distributor

Installation and Maintenance Manual

Unit Installation (Cont)

Содержание QSHE-092

Страница 1: ......

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ...manual 1 Check Rating Plate for correct system voltage before installing the unit Installing and operating a unit with the incorrect voltage may result in malfunction or other issues and will void th...

Страница 16: ...t s below 65 DegF so a Low Ambient Head Pressure Controller See accessories is required as is a Crankcase Heater field supplied Residential Bedrooms Family Rooms etc These require ballpark sizing of a...

Страница 17: ...ide recommend the Aspen brand of Condensate Pump follow their wiring diagram recommendations This pump is installed externally to the unit Follow Instructions failure to follow instructions may cause...

Страница 18: ...ng the weight of the unit Use a level to ensure mounting bracket is leveled so condensate can drain properly Step 5 Prepare Unit Line Set Connections Rotate refrigerant line stubs set gently through 9...

Страница 19: ...set between the Outdoor unit and the Indoor unit MUST have both refrigerant lines insulated as condensing device is located in the Outdoor unit Gently bend the line set stubs from the Indoor unit to...

Страница 20: ...system installed must have a separate branch circuit with an individual breaker fuse QCIC 09 QCIC 12 QCIC 18 QCIC 24 Breaker Size 15A 15A 15A 20A RLA 6 7A 8 8A 5 3A 8 6A MCA 8 2A 10 8A 6 5A 10 6A QCIH...

Страница 21: ...is required then cut the lead and extend it using 18 AWG thermostat wire Sensor is resistance based using 3 5V DC Defrost Sensor wire connection in Outdoor unit is accessed by removing top panel from...

Страница 22: ...ture is above 65 DegF to prevent damage to the compressor Unit has a 3 minute time delay for the compressor start up operation Unit is charged with enough R410A refrigerant for a line set of 25ft leng...

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Отзывы: