With the refrigerant system completely evacuated the system can now be opened to allow the refrigerant 
charge in the Outdoor unit to be released into the line set

The Service Valves require a 6mm and a 5mm Allen wrench respectively to undo the valve stems 
Remove the BRASS caps from the Service Valves

Open the SUCTION line Valve first to prevent any possible oil logging of the Capillary tube

This can occur if the liquid line valve is opened first with the rest of the system in a deep vacuum
Then open the "LIQUID or EXPANDED GAS" line 

Unscrew both valve stems until they come to a stop against the valve body, replace the Brass Caps and 
then tighten the caps to prevent leaks

Energize the breaker to allow system to be powered

Start Indoor unit, Cooling mode is only allowed when the Outside Ambient Temperature is above 65 DegF to 
prevent damage to the compressor
Unit has a 3 minute time delay for the compressor start up operation

Unit is charged with enough R410A refrigerant for a line set of 25ft length

For longer line set lengths additional charge must be WEIGHED in per the following table

30ft

35ft 

40ft

45ft

1.5oz

3.0oz

4.5oz

6.0oz

2.5oz

5.0oz

7.5oz

10.0oz

1.5oz

3.0oz

4.5oz

6.0oz

2.5oz

5.0oz

7.5oz

10.0oz

Standard Operation of the unit - Cooling
Indoor Temperature Split 

30 DegF

Suction Pressure 

115 Psig, approx 37 DegF

Suction Line Temperature

45 DegF

Schraeder connection on the "Liquid" line DOES NOT READ
HEAD PRESSURE - it is an expanded gas pressure

Standard Operation of the unit - Heat Pump
Indoor Temperature Split 

30 DegF

High Side Pressure

400 Psig, approx 117 DegF

(Measured at Liquid Line Schraeder)
Discharge (Liquid) Line Temperature

130 DegF

Installation and Maintenance Manual

Unit Start Up

QCIC-09 & 12
QCIC-18 & 24

QCIH-09 & 12
QCIH-18 & 24

Added Charge required for a line set of 

Unit 

Open Suction Line 

Содержание QSHE-092

Страница 1: ......

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ......

Страница 6: ......

Страница 7: ......

Страница 8: ......

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ...manual 1 Check Rating Plate for correct system voltage before installing the unit Installing and operating a unit with the incorrect voltage may result in malfunction or other issues and will void th...

Страница 16: ...t s below 65 DegF so a Low Ambient Head Pressure Controller See accessories is required as is a Crankcase Heater field supplied Residential Bedrooms Family Rooms etc These require ballpark sizing of a...

Страница 17: ...ide recommend the Aspen brand of Condensate Pump follow their wiring diagram recommendations This pump is installed externally to the unit Follow Instructions failure to follow instructions may cause...

Страница 18: ...ng the weight of the unit Use a level to ensure mounting bracket is leveled so condensate can drain properly Step 5 Prepare Unit Line Set Connections Rotate refrigerant line stubs set gently through 9...

Страница 19: ...set between the Outdoor unit and the Indoor unit MUST have both refrigerant lines insulated as condensing device is located in the Outdoor unit Gently bend the line set stubs from the Indoor unit to...

Страница 20: ...system installed must have a separate branch circuit with an individual breaker fuse QCIC 09 QCIC 12 QCIC 18 QCIC 24 Breaker Size 15A 15A 15A 20A RLA 6 7A 8 8A 5 3A 8 6A MCA 8 2A 10 8A 6 5A 10 6A QCIH...

Страница 21: ...is required then cut the lead and extend it using 18 AWG thermostat wire Sensor is resistance based using 3 5V DC Defrost Sensor wire connection in Outdoor unit is accessed by removing top panel from...

Страница 22: ...ture is above 65 DegF to prevent damage to the compressor Unit has a 3 minute time delay for the compressor start up operation Unit is charged with enough R410A refrigerant for a line set of 25ft leng...

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Отзывы: