49
3
Min/max Floor
Temperature
Set frost protection temperature. Only if controller is switched OFF, the temperature will be
controlled to that value.
•
Minimum floor temperature, the floor gets no colder as this temp. (OFF = no limit);
e.g. Min-Temp. = 21°, the floor will get no colder than 21° even if the room is too warm
•
Maximum floor temperature, the floor gets no warmer as this temp. (OFF = no limit);
e.g. Max-temp. = 35°, the floor will get no warmer than 35°, even if the room is too cold
If one of these limits is not needed it should be set to OFF
5
Valve
protection
The output will be activated for the specified time each day at 10:00 h in the morning
6 Frost protection
Set frost protection temperature. Only if controller is switched OFF, the temperature will be
controlled to that value.
5 °C
(OFF, 5…30)
7 Optimum start
The set temperature will be reached at the time specified in the program. During pre-heating time,
AUTO_ will be displayed
YES
8 Valves NO
If valves normally open have to be used
9
Energy Counter
Reset
The energy counter will be set to 0
NO
10
Display of floor
temperature
The temperature measured from remote sensor will be displayed (for service purpose)
11 Reset all
All INSTALLER and USER settings will be set to its Factory setting
NO
12
EN 50559 Inter-
rupt
Interrupts heating after continous heating of 1hr for this adjusted tim
NO