4. Features

 One line text display for simplified operation

 Back light

 Real time clock (setting of year, month, day, time)

 Automatic Summer- Winter time change over

 Max 9 events per day (each day independently)

 Pre-set and adjustable programs

 Optimum-Start

 Arm chair programming (with display unit removed)

 OFF-Function, Key 

 to be pressed for 10 sec

 Holiday-Mode (date from – until can be set)

 Timer (Party) specific temperature for configurable duration

 Energy consumption display (heating on time * cost) 

  for last 2 days, -week, -month, -year

 Energy cost per hour configurable

 Frost protection

 Range limits for adjusting max and min temperature

 Access protection

 Operating language can be selected

 Control mode PWM or ON/OFF

 Minimum output on/off time and hysteresis configurable for 

  ON/OFF control

 Min- and max limits for floor temperature adjustable

 Valve protection

 Adaptation to valves normally open or normally closed

 Adjustable heating interrupt according standard EN 50559

3. Use

 

The electronic Room Temperature Controller QuickTherm HF Room Thermostat Smart can be used to control the room temperature in 
conjunction with::

 Electrical floor heating systems where the floor temperature has to be limited to a certain value

 

 Hot-water floor heating systems in conjunction with thermal actuators

In order to measure the floor temperature the remote sensor has to be used

5. Mounting

The controller should be mounted at a location in the room which:

 can be easily accessed

 allows free air circulation

 is not exposed to direct sunlight

 is not draughty (when doors or windows are opened)

 is not directly influenced by the source of heat

 is not located on an outer wall

 is approx. 1.5 m above the floor. 

 

Содержание QuickTherm HF

Страница 1: ...QuickTherm HF Room Thermostat QuickTherm HF Room Thermostat Smart Operating and installation instructions GB...

Страница 2: ...Controller 2 Select application Press OK Press OK Select Application ROOM LIMITER FLOOR FLOOR is factory pre set Press OK Note In case of changing the application the user and Installer settings will...

Страница 3: ...he internal or remote sensor The Heater will be switched on when the temperature drops below the current set point Actual Day Actual Room Temperature Calling for Heat Blinks if detached from power mod...

Страница 4: ...steresis configurable for ON OFF control Valve protection Heating or Cooling can be selected Adaptation to valves normally open or normally closed Measures the room temperature with the internal senso...

Страница 5: ...ing in plastic wall boxes only To insert or remove a flexible wire press pin The plastic tab must be in place to pro vide insulation between the terminals wires and the mounting screw Connecting accor...

Страница 6: ...es for example inside a conduit Connecting the remote sensor Caution The sensor is at mains voltage 6 Technical Data Order Type QuickTherm HF Room Thermostat Smart Supply voltage 230 V AC 50 HZ 195 25...

Страница 7: ...orage 20 C 70 C without condensation Rated impulse voltage 4 kV Ball pressure test 75 2 C Voltage and Current for the purposes of Interference measurements 230 V 0 1 A Degree of protection IP 30 Prote...

Страница 8: ...08 Caution Maximum length of removed cable insulation 8 mm Remote sensor 7 Wiring Diagram Dimensions 7 8...

Страница 9: ...ion there will be no need to change the time temperature settings on the device To select another program see 9 G1 Programm 1 Events 1 2 3 4 5 6 Time 6 00 8 30 12 00 14 00 17 00 22 00 Temperature C 21...

Страница 10: ...1 2 3 4 5 6 Time 6 00 8 30 12 00 14 00 17 00 22 00 Temperature C 21 0 18 0 21 0 18 0 21 0 15 0 Events 1 2 Time 7 00 23 00 22 00 Temperature C 21 0 15 0 Monday to Friday Saturday and Sunday 23 00 22 0...

Страница 11: ...for Saturday Programm 3 Events 1 2 3 4 Time 6 00 8 30 17 00 22 00 Temperature C 21 0 18 0 21 0 15 0 Events 1 2 3 4 Time 7 00 10 00 12 00 23 00 22 00 Temperature C 21 0 18 0 21 0 15 0 Monday to Friday...

Страница 12: ...rectly b Is the Optimum Start feature switched on see H7 Did the controller have enough time several days to adapt to the room s characteristics c Is an automatic change between Summer and Winter time...

Страница 13: ...ller to application needs see main menu INSTALLER SETTINGS Set a constant temperature manual operation see main menu MAN Use a separate program for special days see main menu AT HOME Keys to confirm a...

Страница 14: ...0h of the first day it ends at 24h of the last day In the period of time before HOL starts AUTO will be active While waiting for holiday start date other mode can be selected AUTO MAN TIMER HOME INFO...

Страница 15: ...s on power Display reading OFF Frost protection may happen if selected See H6 Switching ON again by activating e g NO 5 Summer Winter time change over Select if automatic Summer Winter Time changeover...

Страница 16: ...d on right column It can be selected if a remote sensor has to be used ROOM NO see 1 10 Set temperature to read Show set temperature instead of room temperature NO 11 Adjust Temperature Adjust tempera...

Страница 17: ...eizungsart H1 RAUM Frostschutz H6 NO kann nicht aktiviert werden Optimum Start H7 NO kann nicht aktiviert werden Heating Heating Cooling im Falle eines Fehlers Relais Aus Temperaturen SchaltzeitenvonH...

Страница 18: ...plug display unit switch off and on power supply Temperature Resistance Temperature Resistance 10 C 66 8 k 30 C 26 3 k 20 C 41 3 k 40 C 17 0 k 25 C 33 0 k 50 C 11 3 k In case of errors Err is blinkin...

Страница 19: ...The heater will be switched on when the temperature drops below the current set point Actual Day Actual Floor Temperature Calling for Heat Blinks if detached from power module or there is no mains po...

Страница 20: ...s week month year Energy cost per hour configurable Frost protection Range limits for adjusting max and min temperature Access protection Operating language can be selected Control mode PWM or ON OFF...

Страница 21: ...ing in plastic wall boxes only To insert or remove a flexible wire press pin The plastic tab must be in place to pro vide insulation between the terminals wires and the mounting screw Connecting accor...

Страница 22: ...power cables for example inside a conduit Connecting the remote sensor Caution The sensor is at mains voltage 6 Technical Data Order Type QuickTherm HF Room Thermostat Smart Supply voltage 230 V AC 50...

Страница 23: ...impulse voltage 4 kV Ball pressure test 75 2 C Voltage and Current for the purposes of Interference measurements 230 V 0 1 A Degree of protection IP 30 Protection class of housing II see Caution Pollu...

Страница 24: ...programs There are 3 pre set time temperature programs in the controller Pre set program 1 as shown below is the default Therefore if pre set program 1 is the best program to suit the application ther...

Страница 25: ...Programm 1 Events 1 2 3 4 Time 6 00 8 00 19 00 22 00 Temperature C 28 0 18 0 21 0 15 0 Events 1 2 3 4 Time 8 00 10 00 17 00 22 00 Temperature C 28 0 18 0 21 0 15 0 Monday to Friday Saturday and Sunda...

Страница 26: ...5 6 Time 6 00 8 00 12 00 14 00 19 00 22 00 Temperature C 28 0 18 0 28 0 18 0 28 0 15 0 Events 1 2 3 4 5 6 Time 8 00 10 00 12 00 14 00 19 00 22 00 Temperature C 28 0 18 0 28 0 18 0 28 0 15 0 Monday to...

Страница 27: ...27 Programm 3 Events 1 2 4 Time 11 00 13 00 22 00 Temperature C 21 0 18 0 15 0 Events 1 2 3 4 Time 8 00 10 00 19 00 22 00 Temperature C 21 0 18 0 28 0 15 0 Monday to Friday Saturday and Sunday...

Страница 28: ...rectly b Is the Optimum Start feature switched on see H7 Did the controller have enough time several days to adapt to the room s characteristics c Is an automatic change between Summer and Winter time...

Страница 29: ...ller to application needs see main menu INSTALLER SETTINGS Set a constant temperature manual operation see main menu MAN Use a separate program for special days see main menu AT HOME Keys to confirm a...

Страница 30: ...starts at 0h of the first day it ends at 24h of the last day In the period of time before HOL starts AUTO will be active While waiting for holiday start date other mode can be selected AUTO MAN TIMER...

Страница 31: ...on power Display reading OFF Frost protection may happen if selected See H6 Switching ON again by activating e g NO 5 Summer Winter time change over Select if automatic Summer Winter Time changeover Y...

Страница 32: ...tem mentioned on right column FLOOR see 1 10 Set temperature to read Show set temperature instead of room temperature NO 12 Number for floor tempe rature Read the floor temperature as number Instead o...

Страница 33: ...the relay to be On or Off PWM 10 10 30 OFF OFF 0 1 5 0 10 Min 1 30 6 Frost protection Set frost protection temperature Only if controller is switched OFF the temperature will be controlled to that va...

Страница 34: ...power unit fails unplug and re plug display unit switch off and on power supply Temperature Resistance Temperature Resistance 10 C 66 8 k 30 C 26 3 k 20 C 41 3 k 40 C 17 0 k 25 C 33 0 k 50 C 11 3 k In...

Страница 35: ...ated if the floor temp drops below the set min value This is even when the room temp is too high In case of function Max FloorTemp H3 heating will be stopped if the floor temp exceeds the set max valu...

Страница 36: ...teresis configurable for ON OFF control Min and max limits for floor temperature adjustable Valve protection Adaptation to valves normally open or normally closed Adjustable heating interrupt accordin...

Страница 37: ...ing in plastic wall boxes only To insert or remove a flexible wire press pin The plastic tab must be in place to pro vide insulation between the terminals wires and the mounting screw Connecting accor...

Страница 38: ...e power cables for example inside a conduit Connecting the remote sensor Caution The sensor is at mains voltage 6 Technical Data Order Type QuickTherm HF Room Thermostat Smart Supply voltage 230 V AC...

Страница 39: ...rage 20 C 70 C without condensation Rated impulse voltage 4 kV Ball pressure test 75 2 C Voltage and Current for the purposes of Interference measurements 230 V 0 1 A Degree of protection IP 30 Protec...

Страница 40: ...40 Caution Maximum length of removed cable insulation 8 mm Remote sensor 7 Wiring Diagram Dimensions 7 8...

Страница 41: ...ion there will be no need to change the time temperature settings on the device To select another program see 9 G1 Programm 1 Events 1 2 3 4 5 6 Time 6 00 8 30 12 00 14 00 17 00 22 00 Temperature C 28...

Страница 42: ...1 2 3 4 5 6 Time 6 00 8 30 12 00 14 00 17 00 22 00 Temperature C 21 0 18 0 21 0 18 0 21 0 15 0 Events 1 2 Time 7 00 23 00 22 00 Temperature C 28 0 15 0 Monday to Friday Saturday and Sunday 23 00 22 0...

Страница 43: ...1 2 3 4 Time 06 00 08 30 17 00 22 00 Temperature C 21 0 18 0 21 0 15 0 Events 1 2 3 4 Time 7 00 10 00 12 00 23 00 22 00 Temperature C 21 0 18 0 21 0 15 0 Monday to Friday Saturday and Sunday 23 00 22...

Страница 44: ...o adapt to the room s characteristics c Is an automatic change between Summer and Winter time activated see G5 2 The controller does not accept any changes Is access protection switched on see G6 3 Th...

Страница 45: ...ller to application needs see main menu INSTALLER SETTINGS Set a constant temperature manual operation see main menu MAN Use a separate program for special days see main menu AT HOME Keys to confirm a...

Страница 46: ...starts at 0h of the first day it ends at 24h of the last day In the period of time before HOL starts AUTO will be active While waiting for holiday start date other mode can be selected AUTO MAN TIMER...

Страница 47: ...on power Display reading OFF Frost protection may happen if selected See H6 Switching ON again by activating e g NO 5 Summer Winter time change over Select if automatic Summer Winter Time changeover Y...

Страница 48: ...ng systems For ON OFF you can select Hysteresis OFF no temperature hysteresis even at very low changes of temp the relay will switch over according to the Min On OffTime setting Min On OffTime the min...

Страница 49: ...ctivated for the specified time each day at 10 00 h in the morning 6 Frost protection Set frost protection temperature Only if controller is switched OFF the temperature will be controlled to that val...

Страница 50: ...power unit fails unplug and re plug display unit switch off and on power supply Temperature Resistance Temperature Resistance 10 C 66 8 k 30 C 26 3 k 20 C 41 3 k 40 C 17 0 k 25 C 33 0 k 50 C 11 3 k In...

Страница 51: ...51...

Страница 52: ...Quick Tec GmbH Bardelebenweg 25 14089 Berlin Germany Fon 49 0 30 577 01 8840 Fax 49 0 30 577 01 8849 mail quick tec com https quick tec com...

Отзывы: