background image

quest

Asset Protection and IAQ Solutions

quest

1-800-533-7533 

10

www.QuestProtect.com

[email protected]

HI-E DRY 100 

Installation, Operation and Maintenance Instructions

  

quest

quest

5.6 Compressor/Capacitor Replacement

This compressor is equipped with a two terminal external overload, run capacitor, but no start capacitor or 
relay (see Fig. 4).

CAUTION-ELECTRICAL SHOCK HAZARD: Electrical power must be present to perform some tests; these 
tests should be performed by a qualified service person.

5.6A Checking Compressor Motor Circuits
Perform the following tests if the blower runs but the compressor does not with the humidity control ON.

1.  Turn the humidity control OFF and unplug the unit, remove the cabinet front (6 screws).
2.  Plug in the unit and turn the humidity control ON. Use a voltmeter to check for 110 to 120 volts between 

(a) the relay terminal that the black wire from the compressor connects to and (b) the capacitor terminal 
with the (2) white wires, (1) red wire & (1) brown wire connected. If voltage is present, go to step 3. If 
no voltage, the defrost thermostat, the relay or the condensate pump safety switch are open or there is 
a loose connection in the compressor circuit. Test each component for continuity; see the appropriate 
section if a defect is suspected.

3.  Turn the humidity control OFF and unplug the unit, then disconnect the red and yellow wires from 

compressor terminals R & S. Using an ohmmeter check continuity between the points listed below.

4.  Compressor terminals C and S: No continuity indicates an open start winding; the compressor must be 

replaced.

5.  Compressor terminals C and R: No continuity indicates an open run winding; the compressor must be 

replaced.

6.  Compressor terminal C and overload terminal 1: No continuity indicates a defective overload lead.
7.  Overload terminals 1 and 3: If there is no continuity, the overload may be tripped; wait 10 minutes and 

try again. If there is still no continuity, it is defective and must be replaced.

8.  Compressor terminal C and compressor case: Continuity indicates a grounded motor; the compressor 

must be replaced.

9.  Disconnect the wires from the capacitor. Set the ohmmeter to the Rx1 scale; the capacitor is shorted and 

must be replaced if continuity exists across its terminals. If there is no needle movement with the meter 
set on the Rx100000 scale, the capacitor is open and must be replaced.

10. Reconnect the wires to the compressor and capacitor; plug in and turn on the unit. If the compressor 

fails to start, replace the run capacitor.

11. If the unit still does not start, adding a hard-start kit will provide greater starting torque. If this does not 

work, the compressor has an internal mechanical defect and must be replaced.

5.6B Replacing a Burned Out Compressor
The refrigerant and oil mixture in a compressor is chemically very stable under normal operating conditions. 
However, when an electrical short occurs in the compressor motor, the resulting high temperature arc causes 
a portion of the refrigerant oil mixture to break down into carbonaceous sludge, a very corrosive acid, and 
water. These contaminants must be carefully removed otherwise even small residues will attack replacement 
compressor motors and cause failures.

Содержание HI-E Dry 100

Страница 1: ...tProtect com sales QuestProtect com Read and Save These Instructions Specifications subject to change without notice TS 598 04 14 1 HI E Dry 100 Controlled by a dehumidistat with settings from 20 to 80 percent relative humidity and a positive on and off setting Contains a blower switch that permits continuous blower operation independent of dehumidification Portable and provided with four casters ...

Страница 2: ...idification 6 2 4C Ducting for Fresh Air 6 3 Operation 6 3 1 Humidity Control Adjustment 6 3 2 Fan Switch 7 3 3 Defrost Control Adjustment 7 4 Maintenance 7 4 1 Air Filter 7 5 Service 7 5 1 Warranty 7 5 2 Technical description 7 5 3 Troubleshooting 8 5 4 Refrigerant Charging 9 5 5 Blower Replacement 9 5 6 Compressor Capacitor Replacement 10 5 6A Checking Compressor Motor Circuits 10 5 6B Replacing...

Страница 3: ... Read the installation operation and maintenance instructions carefully before installing and using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your HI E Dry 100 humidity control device READ AND SAVE THESE INSTRUCTIONS It is designed to be installed INDOORS ONLY DO NOT use the HI E Dry 100 as a bench or table Avoid discharging the air directly at pe...

Страница 4: ...Weight 110 Lb 125 Lb Minimum Performance at Set Conditions Intake Air 70 60 80 60 Water removal day 86 Lbs 114 Lbs Pints KWH 6 0 6 3 2 Installation 2 1 Location The HI E Dry can be installed in a variety of locations to meet the owner s needs as listed below In all cases keep the following cautions in mind It is designed to be installed INDOORS ONLY If used near a pool or spa be certain there is N...

Страница 5: ... e g high door undercut louvered door or wall grill This eliminates the need to remote mount the humidity control There are several potential disadvantages to using this method First humid air is drawn into the room where the HI E Dry 100 is located Second to accurately sense humidity the blower in the HI E Dry 100 may need to run continuously to draw air from the humid room into the HI E Dry 100 ...

Страница 6: ...s Use 6 diameter branch ducting to each of two or three areas use 4 to each of four or more areas 2 4C Ducting for Fresh Air Fresh air can be brought into the structure continuously by connecting a duct from outside to the HI E Dry 100 inlet and by turning on the fan switch Advantages of this form of ventilation include 1 Outside air is filtered before entering the building 2 Outside air will be d...

Страница 7: ...ble DO NOT operate the unit without the filter or with a less effective filter as the heat exchange coils inside the unit could become clogged and require disassembly to clean 5 Service CAUTION Servicing the HI E Dry 100 with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death serious bodily injury and or property damage Only qualifi...

Страница 8: ...ously but compressor only runs sporadically with fan switch OFF 1 Unit is in defrost cycle Sec 3 3 5 10 2 Defrost thermostat defective or loose Sec 3 3 5 10 3 Loose connection in compressor circuit see Fig 4 4 Defective compressor overload Sec 5 6A 5 Defective compressor Sec 5 6 6 Defective relay Sec 5 8 7 Defective defrost timer Sec 5 10 No dehumidification Blower runs but compressor does not wit...

Страница 9: ...rge Sec 5 4 3 Dirty air filters or airflow restricted Sec 4 1 4 Defrost timer set incorrectly Sec 3 3 5 4 Refrigerant Charging If the refrigerant charge is lost due to service or a leak a new charge must be accurately weighed in If any of the old charge is left in the system it must be removed before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigera...

Страница 10: ...continuity indicates an open start winding the compressor must be replaced 5 Compressor terminals C and R No continuity indicates an open run winding the compressor must be replaced 6 Compressor terminal C and overload terminal 1 No continuity indicates a defective overload lead 7 Overload terminals 1 and 3 If there is no continuity the overload may be tripped wait 10 minutes and try again If ther...

Страница 11: ...cid have been pumped throughout the system Several changes of the liquid and suction filter driers will probably be necessary to cleanse the system 5 Correct the system fault that caused the burn out Consult the factory for advice 6 Install the replacement compressor with a new capacitor and an oversized liquid line filter In a running burn out install an oversized suction line filter drier betwee...

Страница 12: ...ugh the evaporator coil and melt the ice when the compressor is off When the air temperature and or humidity increase the evaporator temperature will rise and the thermostat will close to end the defrost cycle 5 10 Condensate Pump Condensate is automatically pumped when the water level in the pump s reservoir rises to close the float switch If the pump is unable to empty its reservoir due to a pum...

Страница 13: ...OTOR BRN WHT COMPRESSOR COMPRESSOR COMPRESSOR OVERLOAD PART NO REV 4033549 A RUN CAPACITOR RUN CAPACITOR YEL BRN TIMER TIMER SWITCH WHT WHT WHT PNK MOTOR WHT BLK BLK BLK BLK GRN 115VAC 60HZ 1PH CONDENSATE PUMP FLOAT SWITCH PUMP FLOAT SWITCH SAFETY SWITCH C NO 1 4 6 1 C S R 2 3 5 NC BLK ORG ORG ORG BLOWER SWITCH BLOWER SWITCH BLOWER MOTOR BLOWER MOTOR PUMP MOTOR TIMER MOTOR RELAY COIL PUMP SAFETY S...

Страница 14: ...9 1 Compressor Overload not shown 8 4033032 05 1 Compressor Run Capacitor 45 MFD 370V 9 4034097 1 Condensate Pump 10 4028226 1 Condenser Coil 11 4023495 1 Cord Wire Harness 12 4025741 1 Defrost Thermostat 4021648 1 Defrost Control Mounting Clip 13 4033925 02 1 Evaporator Coil 14 4029510 1 Filter Drier 15 4024916 1 Hose Drain 25 IDx33FT 16 4027172 1 Humidity Controller 17 4021495 1 Knob Humidity Co...

Страница 15: ...ctions 15 www QuestProtect com sales QuestProtect com quest Asset Protection and IAQ Solutions quest quest quest 8 Filter Installation Instructions To prevent damaging the foam filter place it grid side up on top of the pleated filter and slide them both into the filter slot ...

Страница 16: ...ranty card or other reasonable and reliable means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor s reasonable control Limitation and Exclusions If ...

Отзывы: