Quest Engineering HI-E Dry 100 Скачать руководство пользователя страница 6

quest

Asset Protection and IAQ Solutions

quest

1-800-533-7533 

6

www.QuestProtect.com

[email protected]

HI-E DRY 100 

Installation, Operation and Maintenance Instructions

  

quest

quest

2.3 Condensate Removal

The HI-E Dry 100 is equipped with a condensate pump to remove the water that is condensed during 
dehumidification. This allows the condensate to be disposed of at a distant location, or to be pumped to a 
level above the HI-E Dry 100. The condensate pump is mounted inside the HI-E Dry 100 as an integral part 
of the unit. If the condensate must be pumped more than 18 feet above the unit, a second pump must be 
added to relay the condensate.

2.4 Ducting

2.4A Optional Ducting
An inlet shroud with a 8” round collar and an 8” round exhaust collar are available from the factory that will 
allow round ducting to be attached to the inlet and/or outlet of the HI-E Dry 100.

2.4B Ducting for Dehumidification
Ducting the HI-E Dry 100 as mentioned in sections 2.1B-2.1E requires consideration of the following points.

Duct Sizing: For total duct lengths up to 25’, use a minimum 8” diameter round or equivalent rectangular. 
For longer lengths, use a minimum 10” diameter or equivalent. Grills or diffusers on the duct ends must not 
excessively restrict air flow.

Isolated Areas: Effective dehumidification may require that ducting be branched to isolated, stagnant areas. 
Use 6” diameter branch ducting to each of two or three areas; use 4” to each of four or more areas.

2.4C Ducting for Fresh Air
Fresh air can be brought into the structure continuously by connecting a duct from outside to the HI-E Dry 
100 inlet and by turning on the fan switch. Advantages of this form of ventilation include:

1.  Outside air is filtered before entering the building.
2.  Outside air will be dehumidified before entering if the HI-E Dry 100 is running.
3.  Drawing air from outside and blowing inside aids in pressurizing the structure. This helps prevent 

unfiltered and undehumidified air from entering elsewhere. It also reduces the potential for carcinogenic 
radon gas to enter.

4.  The need for an alternate ventilation device may be eliminated.

3. Operation

3.1 Humidity Control Adjustment

The humidity control device will run continuously until the relative humidity (RH) is reduced to the 
humidity control dial setting. Setting the humidity control to lower RH levels will NOT increase the unit’s 
dehumidification rate, it will simply run longer to reduce the area’s RH to the setting. The HI-E Dry 100  unit 
(and refrigerant based humidity control devices in general) will reduce a warm space’s RH to a lower level 
than that of a cool space. It is therefore pointless to set the humidity control to excessively low levels in cool 
rooms. Doing so will result in long periods of ineffective humidity control device run time.

A quality humidity meter is recommended to accurately monitor humidity levels. For a quote on a quality 
humidity meter, call the factory.

Содержание HI-E Dry 100

Страница 1: ...tProtect com sales QuestProtect com Read and Save These Instructions Specifications subject to change without notice TS 598 04 14 1 HI E Dry 100 Controlled by a dehumidistat with settings from 20 to 80 percent relative humidity and a positive on and off setting Contains a blower switch that permits continuous blower operation independent of dehumidification Portable and provided with four casters ...

Страница 2: ...idification 6 2 4C Ducting for Fresh Air 6 3 Operation 6 3 1 Humidity Control Adjustment 6 3 2 Fan Switch 7 3 3 Defrost Control Adjustment 7 4 Maintenance 7 4 1 Air Filter 7 5 Service 7 5 1 Warranty 7 5 2 Technical description 7 5 3 Troubleshooting 8 5 4 Refrigerant Charging 9 5 5 Blower Replacement 9 5 6 Compressor Capacitor Replacement 10 5 6A Checking Compressor Motor Circuits 10 5 6B Replacing...

Страница 3: ... Read the installation operation and maintenance instructions carefully before installing and using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your HI E Dry 100 humidity control device READ AND SAVE THESE INSTRUCTIONS It is designed to be installed INDOORS ONLY DO NOT use the HI E Dry 100 as a bench or table Avoid discharging the air directly at pe...

Страница 4: ...Weight 110 Lb 125 Lb Minimum Performance at Set Conditions Intake Air 70 60 80 60 Water removal day 86 Lbs 114 Lbs Pints KWH 6 0 6 3 2 Installation 2 1 Location The HI E Dry can be installed in a variety of locations to meet the owner s needs as listed below In all cases keep the following cautions in mind It is designed to be installed INDOORS ONLY If used near a pool or spa be certain there is N...

Страница 5: ... e g high door undercut louvered door or wall grill This eliminates the need to remote mount the humidity control There are several potential disadvantages to using this method First humid air is drawn into the room where the HI E Dry 100 is located Second to accurately sense humidity the blower in the HI E Dry 100 may need to run continuously to draw air from the humid room into the HI E Dry 100 ...

Страница 6: ...s Use 6 diameter branch ducting to each of two or three areas use 4 to each of four or more areas 2 4C Ducting for Fresh Air Fresh air can be brought into the structure continuously by connecting a duct from outside to the HI E Dry 100 inlet and by turning on the fan switch Advantages of this form of ventilation include 1 Outside air is filtered before entering the building 2 Outside air will be d...

Страница 7: ...ble DO NOT operate the unit without the filter or with a less effective filter as the heat exchange coils inside the unit could become clogged and require disassembly to clean 5 Service CAUTION Servicing the HI E Dry 100 with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death serious bodily injury and or property damage Only qualifi...

Страница 8: ...ously but compressor only runs sporadically with fan switch OFF 1 Unit is in defrost cycle Sec 3 3 5 10 2 Defrost thermostat defective or loose Sec 3 3 5 10 3 Loose connection in compressor circuit see Fig 4 4 Defective compressor overload Sec 5 6A 5 Defective compressor Sec 5 6 6 Defective relay Sec 5 8 7 Defective defrost timer Sec 5 10 No dehumidification Blower runs but compressor does not wit...

Страница 9: ...rge Sec 5 4 3 Dirty air filters or airflow restricted Sec 4 1 4 Defrost timer set incorrectly Sec 3 3 5 4 Refrigerant Charging If the refrigerant charge is lost due to service or a leak a new charge must be accurately weighed in If any of the old charge is left in the system it must be removed before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigera...

Страница 10: ...continuity indicates an open start winding the compressor must be replaced 5 Compressor terminals C and R No continuity indicates an open run winding the compressor must be replaced 6 Compressor terminal C and overload terminal 1 No continuity indicates a defective overload lead 7 Overload terminals 1 and 3 If there is no continuity the overload may be tripped wait 10 minutes and try again If ther...

Страница 11: ...cid have been pumped throughout the system Several changes of the liquid and suction filter driers will probably be necessary to cleanse the system 5 Correct the system fault that caused the burn out Consult the factory for advice 6 Install the replacement compressor with a new capacitor and an oversized liquid line filter In a running burn out install an oversized suction line filter drier betwee...

Страница 12: ...ugh the evaporator coil and melt the ice when the compressor is off When the air temperature and or humidity increase the evaporator temperature will rise and the thermostat will close to end the defrost cycle 5 10 Condensate Pump Condensate is automatically pumped when the water level in the pump s reservoir rises to close the float switch If the pump is unable to empty its reservoir due to a pum...

Страница 13: ...OTOR BRN WHT COMPRESSOR COMPRESSOR COMPRESSOR OVERLOAD PART NO REV 4033549 A RUN CAPACITOR RUN CAPACITOR YEL BRN TIMER TIMER SWITCH WHT WHT WHT PNK MOTOR WHT BLK BLK BLK BLK GRN 115VAC 60HZ 1PH CONDENSATE PUMP FLOAT SWITCH PUMP FLOAT SWITCH SAFETY SWITCH C NO 1 4 6 1 C S R 2 3 5 NC BLK ORG ORG ORG BLOWER SWITCH BLOWER SWITCH BLOWER MOTOR BLOWER MOTOR PUMP MOTOR TIMER MOTOR RELAY COIL PUMP SAFETY S...

Страница 14: ...9 1 Compressor Overload not shown 8 4033032 05 1 Compressor Run Capacitor 45 MFD 370V 9 4034097 1 Condensate Pump 10 4028226 1 Condenser Coil 11 4023495 1 Cord Wire Harness 12 4025741 1 Defrost Thermostat 4021648 1 Defrost Control Mounting Clip 13 4033925 02 1 Evaporator Coil 14 4029510 1 Filter Drier 15 4024916 1 Hose Drain 25 IDx33FT 16 4027172 1 Humidity Controller 17 4021495 1 Knob Humidity Co...

Страница 15: ...ctions 15 www QuestProtect com sales QuestProtect com quest Asset Protection and IAQ Solutions quest quest quest 8 Filter Installation Instructions To prevent damaging the foam filter place it grid side up on top of the pleated filter and slide them both into the filter slot ...

Страница 16: ...ranty card or other reasonable and reliable means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor s reasonable control Limitation and Exclusions If ...

Отзывы: