background image

1-800-533-7533 

HI-E DRY 100 

Installation, Operation and Maintenance Instructions

  

11

www.QuestProtect.com

[email protected]

quest

Asset Protection and IAQ Solutions

quest

quest

quest

The following procedure is effective only if the system is monitored after replacing the compressor to insure 
that the clean up was complete.

1.  This procedure assumes that the previously listed compressor motor circuit tests revealed a shorted or 

open winding. If so, cautiously smell the refrigerant from the compressor service port for the acid odor of 
a burn out. 

WARNING: The gas could be toxic and highly acidic. If no acid odor is present, skip down to the section 
on changing a non-burn out compressor.
2.  Remove and properly dispose of the system charge. DO NOT vent the refrigerant or allow it to contact 

your eyes or skin.

3.  Remove the burned out compressor. Use rubber gloves if there is any possibility of coming in contact 

with the oil or sludge.

4.  To facilitate subsequent steps, determine the type of burn out that occurred. If the discharge line shows 

no evidence of sludge and the suction line is also clean or perhaps has some light carbon deposits, the 
burn out occurred while the compressor was not rotating. Contaminants are therefore largely confined to 
the compressor housing. A single installation of liquid and suction line filter/driers will probably clean up 
the system.

  If sludge is evident in the discharge line, it will likely be found in the suction line; this indicates the 

compressor burned out will running. Sludge and acid have been pumped throughout the system. Several 
changes of the liquid and suction filter/driers will probably be necessary to cleanse the system.

5.  Correct the system fault that caused the burn out. Consult the factory for advice.
6.  Install the replacement compressor with a new capacitor and an oversized liquid line filter.
  In a running burn out, install an oversized suction line filter/drier between the accumulator and 

compressor. Thoroughly flush the accumulator with refrigerant to remove all trapped sludge and to 
prevent the oil hole from becoming plugged. A standing burn out does not require a suction line filter/
drier.

7.  Evacuate the system with a good vacuum pump and accurate vacuum gauge. Leave the pump on the 

system for at least an hour.

8.  Operate the system for a short period of time, monitoring the suction pressure to determine that the 

suction filter is not becoming plugged. Replace the suction filter/drier if pressure drop occurs. If a severe 
running burn out has occurred, several filter/driers may have to be replaced to remove all of the acid and 
moisture.

NOTE: NEVER use the compressor to evacuate the system or any part of it.

5.6C Replacing a Compressor- Non-Burn Out
Remove the refrigerant from the system. Replace the compressor and liquid line filter/drier. Charge the 
system to 50 PSIG and check for leaks. Remove the charge and weigh in the refrigerant quantity listed on the 
nameplate. Operate the system to verify performance.

5.7 Relay

The contacts of the single pole, single throw relay complete the power circuit to the compressor. The 
contacts are closed when power is provided to the relay coil via the control circuit. The control circuit 
includes the humidity control, defrost thermostat and timer.

Содержание HI-E Dry 100

Страница 1: ...tProtect com sales QuestProtect com Read and Save These Instructions Specifications subject to change without notice TS 598 04 14 1 HI E Dry 100 Controlled by a dehumidistat with settings from 20 to 80 percent relative humidity and a positive on and off setting Contains a blower switch that permits continuous blower operation independent of dehumidification Portable and provided with four casters ...

Страница 2: ...idification 6 2 4C Ducting for Fresh Air 6 3 Operation 6 3 1 Humidity Control Adjustment 6 3 2 Fan Switch 7 3 3 Defrost Control Adjustment 7 4 Maintenance 7 4 1 Air Filter 7 5 Service 7 5 1 Warranty 7 5 2 Technical description 7 5 3 Troubleshooting 8 5 4 Refrigerant Charging 9 5 5 Blower Replacement 9 5 6 Compressor Capacitor Replacement 10 5 6A Checking Compressor Motor Circuits 10 5 6B Replacing...

Страница 3: ... Read the installation operation and maintenance instructions carefully before installing and using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your HI E Dry 100 humidity control device READ AND SAVE THESE INSTRUCTIONS It is designed to be installed INDOORS ONLY DO NOT use the HI E Dry 100 as a bench or table Avoid discharging the air directly at pe...

Страница 4: ...Weight 110 Lb 125 Lb Minimum Performance at Set Conditions Intake Air 70 60 80 60 Water removal day 86 Lbs 114 Lbs Pints KWH 6 0 6 3 2 Installation 2 1 Location The HI E Dry can be installed in a variety of locations to meet the owner s needs as listed below In all cases keep the following cautions in mind It is designed to be installed INDOORS ONLY If used near a pool or spa be certain there is N...

Страница 5: ... e g high door undercut louvered door or wall grill This eliminates the need to remote mount the humidity control There are several potential disadvantages to using this method First humid air is drawn into the room where the HI E Dry 100 is located Second to accurately sense humidity the blower in the HI E Dry 100 may need to run continuously to draw air from the humid room into the HI E Dry 100 ...

Страница 6: ...s Use 6 diameter branch ducting to each of two or three areas use 4 to each of four or more areas 2 4C Ducting for Fresh Air Fresh air can be brought into the structure continuously by connecting a duct from outside to the HI E Dry 100 inlet and by turning on the fan switch Advantages of this form of ventilation include 1 Outside air is filtered before entering the building 2 Outside air will be d...

Страница 7: ...ble DO NOT operate the unit without the filter or with a less effective filter as the heat exchange coils inside the unit could become clogged and require disassembly to clean 5 Service CAUTION Servicing the HI E Dry 100 with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death serious bodily injury and or property damage Only qualifi...

Страница 8: ...ously but compressor only runs sporadically with fan switch OFF 1 Unit is in defrost cycle Sec 3 3 5 10 2 Defrost thermostat defective or loose Sec 3 3 5 10 3 Loose connection in compressor circuit see Fig 4 4 Defective compressor overload Sec 5 6A 5 Defective compressor Sec 5 6 6 Defective relay Sec 5 8 7 Defective defrost timer Sec 5 10 No dehumidification Blower runs but compressor does not wit...

Страница 9: ...rge Sec 5 4 3 Dirty air filters or airflow restricted Sec 4 1 4 Defrost timer set incorrectly Sec 3 3 5 4 Refrigerant Charging If the refrigerant charge is lost due to service or a leak a new charge must be accurately weighed in If any of the old charge is left in the system it must be removed before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigera...

Страница 10: ...continuity indicates an open start winding the compressor must be replaced 5 Compressor terminals C and R No continuity indicates an open run winding the compressor must be replaced 6 Compressor terminal C and overload terminal 1 No continuity indicates a defective overload lead 7 Overload terminals 1 and 3 If there is no continuity the overload may be tripped wait 10 minutes and try again If ther...

Страница 11: ...cid have been pumped throughout the system Several changes of the liquid and suction filter driers will probably be necessary to cleanse the system 5 Correct the system fault that caused the burn out Consult the factory for advice 6 Install the replacement compressor with a new capacitor and an oversized liquid line filter In a running burn out install an oversized suction line filter drier betwee...

Страница 12: ...ugh the evaporator coil and melt the ice when the compressor is off When the air temperature and or humidity increase the evaporator temperature will rise and the thermostat will close to end the defrost cycle 5 10 Condensate Pump Condensate is automatically pumped when the water level in the pump s reservoir rises to close the float switch If the pump is unable to empty its reservoir due to a pum...

Страница 13: ...OTOR BRN WHT COMPRESSOR COMPRESSOR COMPRESSOR OVERLOAD PART NO REV 4033549 A RUN CAPACITOR RUN CAPACITOR YEL BRN TIMER TIMER SWITCH WHT WHT WHT PNK MOTOR WHT BLK BLK BLK BLK GRN 115VAC 60HZ 1PH CONDENSATE PUMP FLOAT SWITCH PUMP FLOAT SWITCH SAFETY SWITCH C NO 1 4 6 1 C S R 2 3 5 NC BLK ORG ORG ORG BLOWER SWITCH BLOWER SWITCH BLOWER MOTOR BLOWER MOTOR PUMP MOTOR TIMER MOTOR RELAY COIL PUMP SAFETY S...

Страница 14: ...9 1 Compressor Overload not shown 8 4033032 05 1 Compressor Run Capacitor 45 MFD 370V 9 4034097 1 Condensate Pump 10 4028226 1 Condenser Coil 11 4023495 1 Cord Wire Harness 12 4025741 1 Defrost Thermostat 4021648 1 Defrost Control Mounting Clip 13 4033925 02 1 Evaporator Coil 14 4029510 1 Filter Drier 15 4024916 1 Hose Drain 25 IDx33FT 16 4027172 1 Humidity Controller 17 4021495 1 Knob Humidity Co...

Страница 15: ...ctions 15 www QuestProtect com sales QuestProtect com quest Asset Protection and IAQ Solutions quest quest quest 8 Filter Installation Instructions To prevent damaging the foam filter place it grid side up on top of the pleated filter and slide them both into the filter slot ...

Страница 16: ...ranty card or other reasonable and reliable means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor s reasonable control Limitation and Exclusions If ...

Отзывы: