Rev 1. 1 05/08/19
- 44 -
TELSEC
©
MP2 User Guide
Figure 57 - Using additional qualifiers
9.4.1.7
Alarm Delay and Delay Units
Use the Alarm Delay field and the Delay Units drop down to create a delay time for the alarm condition.
The alarm condition must be true for this time period for the alarm to be generated. An alarm will not
be generated if the conditions become false before the delay time elapses. The maximum delay time is
25 hours
9.4.1.8
Clear Delay and Delay Units
Use the Clear Delay field and the Delay Units drop down to create a delay time for the clear condition. A
clear alarm will be generated once the alarm condition is no longer true for the defined delay time. The
maximum delay time is 24 hours.
9.4.1.9
Nag Interval
The nag interval is used to resend the alarm if the alarm is still active. A value of 0 means the alarm will
be sent once per occurrence. A value in minutes greater than 0 will create an interval timer where the
alarm will be resent every time the time has been elapsed. The maximum nag interval is 1440 minutes.