Stat LLC User’s Manual Rev 

3.2, 04/10/18 

Page | 8 

3.4 T-Stat Settings 

The T-stat LLC comes preprogrammed from Quest and cannot be changed in the field.  The settings are 
as follows: 
 

Setpoint Name 

Value

 

Normal mode - Lead unit cooling on 

80 

Normal mode - Lag unit cooling on 

84 

Normal mode - All cooling off 

75 

Normal mode - Lead unit heating on 

45 

Normal mode - Lag unit heating on 

43 

Normal mode - All heating off 

50 

Comfort mode - Lead unit cooling on 

76 

Comfort mode - Lag unit cooling on 

80 

Comfort mode - All cooling off 

71 

Comfort mode - Lead unit heating on 

55 

Comfort mode - Lag heating on 

53 

Comfort mode - All heating off 

60 

Lead Switch time 

24 hours 

Comfort mode time 

1 hour 

Lead unit fan operation 

Automatic 

 

4.0 Care and Cleaning 

The T-Stat LLC should provide years of uninterrupted service.  Minimal preventive maintenance is 
required.  However; it is important to make sure that the T-Stat is kept free of dust.  A dusty T-Stat will 
not allow air to circulate properly around the built-in temperature sensor effecting proper operation of 
the unit.   

Ensure temperature 

probe in this air tunnel 
is free of dirt and dust.

 

Содержание 100 T-Stat LLC

Страница 1: ...NOTICE Copyright 2018 by Quest Controls Inc QUEST The material discussed in this publication is the proprietary property of QUEST QUEST retains all rights to reproduction and distribution of this pub...

Страница 2: ...0 Installation Wiring 4 2 1 Installing the mounting plate 5 2 2 Wiring 5 3 0 Front Panel Display Keypad Operation 7 3 1 Run Mode 7 3 2 Occupied Override 7 3 3 Lead Switch 7 3 4 T Stat Settings 8 4 0 C...

Страница 3: ...credentials for the work I am about to do 2 Do I know why I m doing this work 3 Have I identified and notified all key stakeholders who will be directly and possibly indirectly affected by this work...

Страница 4: ...lead change every 24 hours LCD display for current operating mode and shelter temperature readings Comfort mode to allow Occupied settings for a one hour timed duration Five button keypad for navigati...

Страница 5: ...be snug and depressing the clips through the slot openings may help in getting the cover off 4 Mount the Plate Dress the wires through the center window on the back plate and install mounting screws T...

Страница 6: ...C R C G Y1 W Supply Fan Cooling Heating Control Interface Located in HVAC system HVAC 2 HVAC 2 C R T Stat Lead Lag Controller Back plate mounts to standard electrical box HVAC Unit 2 24VAC R C G Y1 W...

Страница 7: ...ewed by pressing the up or down arrow keys This will cycle the display on the second line to show Occupied status and control mode of each HVAC unit 3 2 Occupied Override Press the center button until...

Страница 8: ...mode Lag unit cooling on 80 Comfort mode All cooling off 71 Comfort mode Lead unit heating on 55 Comfort mode Lag heating on 53 Comfort mode All heating off 60 Lead Switch time 24 hours Comfort mode t...

Страница 9: ...ot correct the problem reset system by removing the T Stat body from the mounting plate Then return the body to the mounting plate while depressing the up arrow center button and down arrow all at the...

Отзывы: