T-
Stat LLC User’s Manual Rev
3.2, 04/10/18
Page | 8
3.4 T-Stat Settings
The T-stat LLC comes preprogrammed from Quest and cannot be changed in the field. The settings are
as follows:
Setpoint Name
Value
Normal mode - Lead unit cooling on
80
Normal mode - Lag unit cooling on
84
Normal mode - All cooling off
75
Normal mode - Lead unit heating on
45
Normal mode - Lag unit heating on
43
Normal mode - All heating off
50
Comfort mode - Lead unit cooling on
76
Comfort mode - Lag unit cooling on
80
Comfort mode - All cooling off
71
Comfort mode - Lead unit heating on
55
Comfort mode - Lag heating on
53
Comfort mode - All heating off
60
Lead Switch time
24 hours
Comfort mode time
1 hour
Lead unit fan operation
Automatic
4.0 Care and Cleaning
The T-Stat LLC should provide years of uninterrupted service. Minimal preventive maintenance is
required. However; it is important to make sure that the T-Stat is kept free of dust. A dusty T-Stat will
not allow air to circulate properly around the built-in temperature sensor effecting proper operation of
the unit.
Ensure temperature
probe in this air tunnel
is free of dirt and dust.