T-

Stat LLC User’s Manual Rev 

3.2, 04/10/18 

Page | 5 

2.1 Installing the mounting plate 

1.

 

Plan the Location

 

The T-Stat should be mounted away from external sources of heat or cold 

(doors, HVAC supply grill, exhaust from equipment, radio heads, etc.) and provide a good 

representation of the shelter’s 

temperature. 

2.

 

Prepare the Area 

- The mounting screw holes will line up on a standard duplex outlet box or can 

be flush mounted to the wall.  When flush mounting, ensure clearance for the wires to exit 
through the center window on the back plate.  Install outlet box or screw anchors and run 
thermostat wires. 

3.

 

Remove the cover

 - The cover of the T-Stat is held on by four clips, two on the top and two on 

the bottom.  Remove the cover carefully, the cover may be snug and depressing the clips 
through the slot openings may help in getting the cover off. 

4.

 

Mount the Plate

 - Dress the wires through the center window on the back plate and install 

mounting screws.  Tighten screws to ensure the plate is mounted securely, but do not over 
tighten and warp the back plate. 

2.2 Wiring 

1.

 

Terminate the Wire Connections 

 Cut off excess wire, dress wire flush to the back panel and 

strip 1/4” of insulation to expose conductor.  Insert and tighten using the 

Wire Terminations 

diagram.  Label all point to point connections at both ends of the cable. 

2.

 

Connection Descriptions

Terminal 

Description 

 wire color 

HVAC 1 - R 

24VAC power - red 

HVAC 1 - C 

24VAC common - black 

HVAC 1 - G 

Fan Control 

 green 

HVAC 1 - Y 

Call for Cool - yellow 

HVAC 1 - W 

Call for Heat - white 

HVAC 2 - R 

24VAC power - red 

HVAC 2 - C 

24VAC common - black 

HVAC 2 - G 

Fan Control 

 green 

HVAC 2 - Y 

Call for Cool - yellow 

HVAC 2 - W 

Call for Heat - white 

Figure 2 - Connection Descriptions 

Содержание 100 T-Stat LLC

Страница 1: ...NOTICE Copyright 2018 by Quest Controls Inc QUEST The material discussed in this publication is the proprietary property of QUEST QUEST retains all rights to reproduction and distribution of this pub...

Страница 2: ...0 Installation Wiring 4 2 1 Installing the mounting plate 5 2 2 Wiring 5 3 0 Front Panel Display Keypad Operation 7 3 1 Run Mode 7 3 2 Occupied Override 7 3 3 Lead Switch 7 3 4 T Stat Settings 8 4 0 C...

Страница 3: ...credentials for the work I am about to do 2 Do I know why I m doing this work 3 Have I identified and notified all key stakeholders who will be directly and possibly indirectly affected by this work...

Страница 4: ...lead change every 24 hours LCD display for current operating mode and shelter temperature readings Comfort mode to allow Occupied settings for a one hour timed duration Five button keypad for navigati...

Страница 5: ...be snug and depressing the clips through the slot openings may help in getting the cover off 4 Mount the Plate Dress the wires through the center window on the back plate and install mounting screws T...

Страница 6: ...C R C G Y1 W Supply Fan Cooling Heating Control Interface Located in HVAC system HVAC 2 HVAC 2 C R T Stat Lead Lag Controller Back plate mounts to standard electrical box HVAC Unit 2 24VAC R C G Y1 W...

Страница 7: ...ewed by pressing the up or down arrow keys This will cycle the display on the second line to show Occupied status and control mode of each HVAC unit 3 2 Occupied Override Press the center button until...

Страница 8: ...mode Lag unit cooling on 80 Comfort mode All cooling off 71 Comfort mode Lead unit heating on 55 Comfort mode Lag heating on 53 Comfort mode All heating off 60 Lead Switch time 24 hours Comfort mode t...

Страница 9: ...ot correct the problem reset system by removing the T Stat body from the mounting plate Then return the body to the mounting plate while depressing the up arrow center button and down arrow all at the...

Отзывы: