Values (size is 1-byte dec):
•
default value 1
•
0 - disable
•
1 - enable
Parameter no. 74
–
Motor moving up/down time
This parameter defines the time, required by the Shutter motor, to completely open or
completely close the attached shutters.
Values (size is 2-byte dec):
•
default value 0
•
0
–
moving time disabled (working with limit switches)
•
1 - 32767 = 0.1 seconds
–
3276.7 seconds
After the set time passes, the motor stops (relay goes to the off state).
NOTE: It is important that the reference position, for setting the moving time, is always when the
Shutter is at its lowest position!
Set parameter 74 to 0 and move the Shutter (using the up/down push-buttons or the main
gateway (hub) UI) to the lowest desired position. When the Shutter reaches this position, set the
parameter 74 to the duration, required by the Shutter, to completely open or completely close
the attached shutters. At this point the Shutter can be moved up (open), but can't be moved
down, because this position is already set as its lowest position.
To change the defined lowest position of the Shutter below the one, which is already defined
(manual recalibration), the parameter 74 must be set to 0 and the procedure, which is described
above, should be repeated.
Содержание Flush Shutter
Страница 3: ...EN 3 18 Warning 64 19 Regulations 64 ...
Страница 12: ...EN 12 Remotely control projector screen Remotely control retractable awnings Remotely control windows ...
Страница 19: ...EN 19 4 Package Contents Flush Shutter Device Installation Manual ...
Страница 21: ...EN 21 ...
Страница 25: ...EN 25 After Qubino installation ...
Страница 31: ...EN 31 Step 2 Switch of the power supply Step 3 Connect the temperature sensor as shown below ...
Страница 32: ...EN 32 Step 4 Place the temperature sensor in the switch box Step 5 Turn the fuse on ...
Страница 33: ...EN 33 Step 6 Re include the device to your network ...
Страница 34: ...EN 34 Step 7 Start using the temperature sensor in connection with your device ...