EN
.
Parameter no. 85 – Power consumption max delay time
Define the maximum time before the power consumption of the motor, after one of the relays
is switched ON, is read from the device. If there is no power consumption during the set time
(motor not connected, damaged or requires longer time to start, motor at the end position),
the relay will switch OFF. This time is defined by entering it manually.
Values (data type is 1 byte dec):
•
default value 30 = 3s
•
0 = time is set automatically
•
3 - 50 = 0.3seconds - 5seconds (100ms resolution)