Q-Controller System Operation Manual
- 31 -
86550-001-000 Rev B
Off Concentration
: For each sensor or analog input assigned, set the concentration at or
below which the sensor or AI will return to Normal Status.
If On Concentration is less than Off Concentration:
On Concentration:
For each sensor or analog input assigned, set the concentration
below which the sensor or AI will return to Normal Status.
Off Concentration
: For each sensor or analog input assigned, set the concentration
above which the sensor or AI will be in Alarm Status and will be counted into Voting
Number.