Q-Controller System Operation Manual
- 7 -
86550-001-000 Rev B
guaranteed to be accessible.
Feeding the Q-Controller power from a rack main switch or from
a switch in a distribution box is adequate.
Enclosure
UL 508 Type 1, 2, 3, 4, 4X, 12 and 13
CSA Type 1, 2, 3, 4, 4X, 12 and 13
NEMA Type 1, 2, 3, 4, 4X, 12 and 13
IEC 60529, IP66
Flammability V-O per UL 94
UV rating (f1) per UL746C
Environmental
conditions
Location:
Indoor use only
Altitude:
Up to 2 000 m
Temperature:
5 °C to 50 °C
Relative Humidity:
80 % for temperatures up to 31 °C
decreasing linearly to 50 % at 40 °C.
Pollution Degree:
3, in accordance with IEC 664.
Installation Categories (Overvoltage Categories) II
Display & Keypad
7 inch LCD touchscreen display delivers 800 x 480 resolution and
offers a capacitive multi-touch TN panel for easily navigate
screen
Panel Indicators
15 Status LEDs
Power Status
USB TX/RX status
4 RS-485 port TX/RX Status for Sensor Network
1 RS-485 port TX/RX Status for Modbus
1 RS-485 port TX/RX Status for BACnet Module BAC-Box
On-Board Relays
4 pluggable Relays SPDT, Dry contacts
Resistive load:
10A at 250VAC
10A at 30VDC
Inductive load:
7.5A at 250VAC
5A at 30VDC
On-Board Switch
Inputs:
4 channel switch inputs
The switch can be Q-Switch or any ON-OFF switch