Q-Controller System Operation Manual
- 25 -
86550-001-000 Rev B
5.3.2
Auto Scan & Config
Click the button [Auto Scan & Config] on the right corner of the screen, the Q-Controller
will automatically scan all online devices and generate a config file for all devices setup.
It will replace the existed config file in the Q-Controller, and not all information can be
generated, so we strongly recommend setting up each device individually and manually.
5.3.3
Cal 4-20mA Input for AI-Box
This feature is only for factory calibration.
Settings
Description
Drop list “CAL AI-
Box-0”
The Address of the being calibrated AI-Box. It supports AI-Box-0
to AI-Box-15. Each AI-Box can be calibrated individually on the
bus.
CAL 4mA
Each channel of the AI-Box can be calibrated individually.
Apply 4mA signal to Channel 1 to Channel 8 of the AI-Box, then
click the each channel button [4mA CAL CHx] to calibrate the
4mA signal, the AI-Box will sample the value and store it to the
AI-Box EEPROM. The value will be displayed on the right side of
“CHx 4mA A/D = XXXX”
CAL 20mA
Apply 20mA signal to Channel 1 to Channel 8 of the AI-Box, then
click the each channel button [20mA CAL CHx] to calibrate the
20mA signal, the AI-Box will sample the value and store it to the
AI-Box EEPROM. The value will be displayed on the right side of
“CHx 20mA A/D = XXXX”