Trouble-Shooting 

 

problem 

causes 

solutions 

the humidifier does not turn on  

1. no electrical power 
2. on/off switch of the humidifier in 
position 0 (open) 
3. control connectors improperly 
connected 
4. blown fuses 
5. transformer failure  

1. check the safety devices upstream from 
the humidifier and the presence of power 
2. close the switch on the panel: position I 
3. check that the connectors are properly 
inserted in the terminal block 
4. check the condition of fuses F1/F2/F3 
5. check that the voltage across the 
secondary winding of the transformer is 
24Vac  

the humidifier does not start 
operation 

1. remote ON/OFF contact open 
(relay/terminals AB - AB or 7I - 8I) 
2. the humidistat has not been 
connected correctly 
3. humidistat failure 
4. control signal not compatible 
with the type set 
5. value measured by the sensor/s 
higher than the corresponding set 
point  

1. close ON/OFF contacts (relay/terminals 
7I - 8I) 
2. check the external connection 
3. replace the humidistat 
4. set parameters A0, A2-A9 correctly 
5. check the values of the set point St and 
P7  

the humidifier fills with water 
without producing steam 

1. high steam back pressure 
2. fill valve strainer clogged 
3. mineral in the fill cup 
4. drain solenoid valve leaking  

1. check that the steam hose is not kinked 
or sagging, trapping condensate 
2. clean the fill valve strainer 
3. clean the fill cup 
4. check for 24Vac at the drain solenoid 
valve and/or drain solenoid replacement  

the thermal-magnetic overload 
switch is activated 

1. thermal-magnetic overload 
switch is under-rated 
2. over-current at the electrodes  

1. check that the thermal-magnetic 
overload switch is rated for a current of at 
least 1.5 times the rated current of the 
humidifier 
2. see description for alarm EH  

the humidifier wets the duct  

1. the distributor is not installed 
correctly (too near the top of the 
duct or the condensate return is 
blocked) 
2.system over-sized 
3.humidifier active when the fan in 
the duct is off  

1. check that the steam distributor is 
installed correctly 
2. decrease the steam production set on 
the control 
3. check the connection of the device (flow 
switch or differential pressure switch) 
slaving the humidifier to the ventilation in 
the duct (terminals 7I - 8I)  

the humidifier wets the floor 
below  

1. the humidifier drain is blocked 
2. the supply water or overflow 
circuit has leaks 
3. the condensate drain pipe does 
not bring the water back to the 
drain pan 
4. the steam hose is not properly 
fastened to the cylinder  

1. clean the drain assembly and pan 
2. check the entire water circuit 
3. check the correct position of the 
condensate drain hose in the drain pan 
4. check the fastening of the hose clamps 
on the steam outlet  

 

Содержание HU315 SERIES

Страница 1: ...1C9 Tel 514 630 4444 Fax 514 630 4454 website www quatro air com Simplified INSTALLATION MANUALand Detailed Installation manual are included in this package HU315 HUMIDIFIER SERIES Note HU315 has rep...

Страница 2: ...d blower distribution module fig 2 a 3 Plastic bag with plastic water adapter rubber seal clamps 8 Pin electrical connector mounting screws and anchors 4 Wall mounted sensor box located in the humidif...

Страница 3: ...e from the sensor to expose the terminal strip inside See figures 5 6 3 control wires not supplied need to be wired from the wall mounted sensor to the green connector terminals 4I 5I and 6I See figur...

Страница 4: ...there is a jumper installed across 7I and 8I as in figure 7 4 Connect Plumbing Water supply and drain connections are made according to the following diagram NOTE Drain line must be trapped under the...

Страница 5: ...pm Connection 1 1 2 nominal diameter Typical temperature 212 F Water supply The HU315 must be supplied with cold water not softened having the following characteristics Model HU315 Instant flow rate 0...

Страница 6: ...midify rooms or ducts using a distribution system The installation use and maintenance operations must be carried out according to the instructions contained in this manual and on the labels applied i...

Страница 7: ...rain 17 Accessing Changing Configuration Parameters 17 Notes about special parameters 21 STANDARD FACTORY SETTINGS 22 Seasonal Shut Down 23 Resetting the Hour Counter 23 Alarms 24 Trouble Shooting 28...

Страница 8: ...ebsite www quatro air com Description Of The Components HU315 33 lbs hr modulating steam humidifier 208 3 60 Model HU315 No Description 1 Steam generator cylinder 2 Water drain valve 3 Power contactor...

Страница 9: ...om of the steam cylinder 11 As the water fills the cylinder it will reach the electrodes 10 and current will begin to flow As the water continues to fill the cylinder the current will increase and thi...

Страница 10: ...The front cover is secured by a capture screw located underneath the QUATRO logo Twist the QUATRO logo to reveal the screw and use a phillips head screwdriver to remove it Then simply lift the front...

Страница 11: ...low rate 0 3 gpm Connection 1 4 O D Compression Temperature limits 34 to 104 F Pressure limits 15 to 116 psi Hardness limits 400 ppm CaCO3 Conductivity range 125 to 1250 S cm micromhos Water drain The...

Страница 12: ...following diagram NOTE Drain line must be trapped under the unit to prevent flash steam from condensing in the unit cabinet Physical location of the supply and drain connections are located as shown...

Страница 13: ...separate from any control wiring Per the table on the following page make sure that the unit has the proper number of turns through the TAM Torroid Amperage Monitor which is on the control board Also...

Страница 14: ...in the room In the case where the HU315 uses a direct discharge blower unit this is the only control needed Control wiring is made directly to the control board terminals 1 terminal block G dehumidif...

Страница 15: ...2 Do not connect power if the humidifier is damaged or even partially wet When installation is completed flush the supply pipe for around 30 minutes by piping water directly into the drain without se...

Страница 16: ...t be multiplied by 1000 8 LED to indicate dehumidify mode 9 LED to indicate alarm 10 LED to indicate humidifier is producing steam Flashing indicates lower than required production 11 LED to indicate...

Страница 17: ...seconds without pressing SEL or PRG will revert to the old value Activating Manual Drain In addition to the manual drain switch on the side of the humidifier pressing the and buttons simultaneously fo...

Страница 18: ...ut actual d4 0 0 to 19999 h Run time hours d5 0 to 1555 S cm Conductivity of the feed water d6 0 0 to 199 A Current Amperage d9 0 0 to 199 kg h Rated steam output 1 when accessing parameter A0 paramet...

Страница 19: ...C Room sensor minimum Accessible only in control mode A0 2 3 or 4 Used for scaling sensors A4 2 A3 to 255 100 RH C Room sensor maximum A5 10 0 to 10 0 0 RH C Room sensor offset A6 0 to 4 0 Type of out...

Страница 20: ...relay 64 enable periodic draining b2 0 to 120 0 s Shut down delay time b3 10 0 to 10 0 0 Current measurement gain b4 0 to 199 0 S cm Water conductivity 0 automatic measurement 0k2 2k0 b5 0 to 199 1k5...

Страница 21: ...ON OFF and room sensor 3 term with ON OFF and hi limit sensor Notes about special parameters b1 setting 2 Drain under power If parameter b1 includes setting 2 the humidifier will continue to produce s...

Страница 22: ...com STANDARD FACTORY SETTINGS HU315 Parameters H Controller Parameter HU315 STAND ALONE A0 2 A1 1 A2 0 A3 0 A4 100 A5 0 A6 N A A7 N A A8 N A A9 N A b1 2 b2 0 b3 0 0 b4 0 b5 15 b6 20 b7 75 b8 100 b9 10...

Страница 23: ...witch on the side of the humidifier and disconnect power from the humidifier Shut off the water to the humidifier In the event of malfunction of the drain valve the cylinder can be emptied manually by...

Страница 24: ...ted from the main power check the internal electrical connections Shut down N A Active N A EC High supply water conductivity 1 Check limit set for b6 2 Turn the machine off and clean the water conduct...

Страница 25: ...ve Manual Ed Drain malfunction Check the drain circuits and the correct operation of the drain valve Shut down Manual Active Manual Ec High water conductivity pre alarm Check the conductivity of the s...

Страница 26: ...obe and the setting of parameter A0 see chap 7 Shut down Manual Active Auto E4 Hi limit sensor not connected Check the connection of the probe parameter A6 for the outlet probe and the setting of para...

Страница 27: ...the manual drain sequence Sequence ends on its own Idr Complete draining for extended inactivity The unit is emptying the cylinder after an extended period of non use Sequence ends on its own Dr Comp...

Страница 28: ...mineral in the fill cup 4 drain solenoid valve leaking 1 check that the steam hose is not kinked or sagging trapping condensate 2 clean the fill valve strainer 3 clean the fill cup 4 check for 24Vac...

Страница 29: ...al drains to control the minerals 2 If you are using a softener check the salt being used If it contains any additives discontinue use flush all lines and convert to pure salt or unsoftened water 3 Ch...

Страница 30: ...that there are no significant water leaks and the general condition of the cylinder Check that during operation there is no arcing between the electrodes Every three months or no more than 1000 operat...

Страница 31: ...y drain the cylinder by pressing and holding the manual drain switch or by pressing the and buttons simultaneously for 2 seconds to force a manual drain This procedure can be stopped at any time by ag...

Страница 32: ...s Re start the humidifier and perform a number of supply and drain cycles from 2 to 4 then check for any water leaks Replacement Parts Three Phase Humidifiers HU315 Part s Water Parts Fill Cup Conduct...

Страница 33: ...Installation Operating Maintenance Manual 33 10 25 2004...

Страница 34: ...t humidifier replacement parts warranty is 60 days from date of Invoice Warranty replacement parts are warranted for remainder of original unit warranty or 60 days whichever is longer so long as the p...

Отзывы: