Installation, Operating & Maintenance Manual 

 

10/25/2004 

                   

                        

                   

Figure 3 

 

 

 

              

 

                                           
 

3) 

Control Wiring from wall mounted sensor

 

 

a.  Humidity sensor (see figure 4) must be mounted to the wall  (with dimple on left hand 

side and holes on right hand side) using the mounting screws provided in the sensor 
box.  

 
 
b.  Remove the cover plate from the sensor to expose the terminal strip inside.  
     (See figures 5&6) 

3 control wires (not supplied) need to be wired from the wall mounted sensor to the   
green connector  terminals 4I, 5I, and 6I (See figure 7) as follows:  
 
On the sensor from left to right, wire as follows (see figure 5 & 6) 
 
 

 position    # 1   should be wired to ………..……..  terminal  4I 

 

 

 position    # 2 ………………………………………  not wired 

 

 

 position    # 3 ………………………………………  not wired 

 

 

 position    #4  should be wired to .………………   terminal  6I 

 

 

 position    #5   should be wired to ………………   terminal  5I 

 
 
 

 

        

                     

 

        Figure 4 

 

 

 

 

 

                 Figure 5 

 
 

a) 

dimplea 

 
b)position #1 

 
b)position #5 

Содержание HU315 SERIES

Страница 1: ...1C9 Tel 514 630 4444 Fax 514 630 4454 website www quatro air com Simplified INSTALLATION MANUALand Detailed Installation manual are included in this package HU315 HUMIDIFIER SERIES Note HU315 has rep...

Страница 2: ...d blower distribution module fig 2 a 3 Plastic bag with plastic water adapter rubber seal clamps 8 Pin electrical connector mounting screws and anchors 4 Wall mounted sensor box located in the humidif...

Страница 3: ...e from the sensor to expose the terminal strip inside See figures 5 6 3 control wires not supplied need to be wired from the wall mounted sensor to the green connector terminals 4I 5I and 6I See figur...

Страница 4: ...there is a jumper installed across 7I and 8I as in figure 7 4 Connect Plumbing Water supply and drain connections are made according to the following diagram NOTE Drain line must be trapped under the...

Страница 5: ...pm Connection 1 1 2 nominal diameter Typical temperature 212 F Water supply The HU315 must be supplied with cold water not softened having the following characteristics Model HU315 Instant flow rate 0...

Страница 6: ...midify rooms or ducts using a distribution system The installation use and maintenance operations must be carried out according to the instructions contained in this manual and on the labels applied i...

Страница 7: ...rain 17 Accessing Changing Configuration Parameters 17 Notes about special parameters 21 STANDARD FACTORY SETTINGS 22 Seasonal Shut Down 23 Resetting the Hour Counter 23 Alarms 24 Trouble Shooting 28...

Страница 8: ...ebsite www quatro air com Description Of The Components HU315 33 lbs hr modulating steam humidifier 208 3 60 Model HU315 No Description 1 Steam generator cylinder 2 Water drain valve 3 Power contactor...

Страница 9: ...om of the steam cylinder 11 As the water fills the cylinder it will reach the electrodes 10 and current will begin to flow As the water continues to fill the cylinder the current will increase and thi...

Страница 10: ...The front cover is secured by a capture screw located underneath the QUATRO logo Twist the QUATRO logo to reveal the screw and use a phillips head screwdriver to remove it Then simply lift the front...

Страница 11: ...low rate 0 3 gpm Connection 1 4 O D Compression Temperature limits 34 to 104 F Pressure limits 15 to 116 psi Hardness limits 400 ppm CaCO3 Conductivity range 125 to 1250 S cm micromhos Water drain The...

Страница 12: ...following diagram NOTE Drain line must be trapped under the unit to prevent flash steam from condensing in the unit cabinet Physical location of the supply and drain connections are located as shown...

Страница 13: ...separate from any control wiring Per the table on the following page make sure that the unit has the proper number of turns through the TAM Torroid Amperage Monitor which is on the control board Also...

Страница 14: ...in the room In the case where the HU315 uses a direct discharge blower unit this is the only control needed Control wiring is made directly to the control board terminals 1 terminal block G dehumidif...

Страница 15: ...2 Do not connect power if the humidifier is damaged or even partially wet When installation is completed flush the supply pipe for around 30 minutes by piping water directly into the drain without se...

Страница 16: ...t be multiplied by 1000 8 LED to indicate dehumidify mode 9 LED to indicate alarm 10 LED to indicate humidifier is producing steam Flashing indicates lower than required production 11 LED to indicate...

Страница 17: ...seconds without pressing SEL or PRG will revert to the old value Activating Manual Drain In addition to the manual drain switch on the side of the humidifier pressing the and buttons simultaneously fo...

Страница 18: ...ut actual d4 0 0 to 19999 h Run time hours d5 0 to 1555 S cm Conductivity of the feed water d6 0 0 to 199 A Current Amperage d9 0 0 to 199 kg h Rated steam output 1 when accessing parameter A0 paramet...

Страница 19: ...C Room sensor minimum Accessible only in control mode A0 2 3 or 4 Used for scaling sensors A4 2 A3 to 255 100 RH C Room sensor maximum A5 10 0 to 10 0 0 RH C Room sensor offset A6 0 to 4 0 Type of out...

Страница 20: ...relay 64 enable periodic draining b2 0 to 120 0 s Shut down delay time b3 10 0 to 10 0 0 Current measurement gain b4 0 to 199 0 S cm Water conductivity 0 automatic measurement 0k2 2k0 b5 0 to 199 1k5...

Страница 21: ...ON OFF and room sensor 3 term with ON OFF and hi limit sensor Notes about special parameters b1 setting 2 Drain under power If parameter b1 includes setting 2 the humidifier will continue to produce s...

Страница 22: ...com STANDARD FACTORY SETTINGS HU315 Parameters H Controller Parameter HU315 STAND ALONE A0 2 A1 1 A2 0 A3 0 A4 100 A5 0 A6 N A A7 N A A8 N A A9 N A b1 2 b2 0 b3 0 0 b4 0 b5 15 b6 20 b7 75 b8 100 b9 10...

Страница 23: ...witch on the side of the humidifier and disconnect power from the humidifier Shut off the water to the humidifier In the event of malfunction of the drain valve the cylinder can be emptied manually by...

Страница 24: ...ted from the main power check the internal electrical connections Shut down N A Active N A EC High supply water conductivity 1 Check limit set for b6 2 Turn the machine off and clean the water conduct...

Страница 25: ...ve Manual Ed Drain malfunction Check the drain circuits and the correct operation of the drain valve Shut down Manual Active Manual Ec High water conductivity pre alarm Check the conductivity of the s...

Страница 26: ...obe and the setting of parameter A0 see chap 7 Shut down Manual Active Auto E4 Hi limit sensor not connected Check the connection of the probe parameter A6 for the outlet probe and the setting of para...

Страница 27: ...the manual drain sequence Sequence ends on its own Idr Complete draining for extended inactivity The unit is emptying the cylinder after an extended period of non use Sequence ends on its own Dr Comp...

Страница 28: ...mineral in the fill cup 4 drain solenoid valve leaking 1 check that the steam hose is not kinked or sagging trapping condensate 2 clean the fill valve strainer 3 clean the fill cup 4 check for 24Vac...

Страница 29: ...al drains to control the minerals 2 If you are using a softener check the salt being used If it contains any additives discontinue use flush all lines and convert to pure salt or unsoftened water 3 Ch...

Страница 30: ...that there are no significant water leaks and the general condition of the cylinder Check that during operation there is no arcing between the electrodes Every three months or no more than 1000 operat...

Страница 31: ...y drain the cylinder by pressing and holding the manual drain switch or by pressing the and buttons simultaneously for 2 seconds to force a manual drain This procedure can be stopped at any time by ag...

Страница 32: ...s Re start the humidifier and perform a number of supply and drain cycles from 2 to 4 then check for any water leaks Replacement Parts Three Phase Humidifiers HU315 Part s Water Parts Fill Cup Conduct...

Страница 33: ...Installation Operating Maintenance Manual 33 10 25 2004...

Страница 34: ...t humidifier replacement parts warranty is 60 days from date of Invoice Warranty replacement parts are warranted for remainder of original unit warranty or 60 days whichever is longer so long as the p...

Отзывы: