QUATRO
HU315
18
QUATRO
-------------------------------------------------------------------------------------
”We Make Clean Air”
30 Hymus Boulevard, Montreal, Quebec, H9R 1C9 Tel.: (514) 630-4444 Fax: (514) 630-4454 website: www.quatro-air.com
Code Range Default Unit
Description
P3 to 60
60
°C
temperature alarm set point
P3 (1) 0 to P2
0
%RH, °C
Low humidity/temp. alarm set
point
P4
0 to 100
1
min Alarm delay (0*= 30 s)
P5
2 to 100
10
%RH Dehumidification dead zone
accessible only with the dehumidification
function enabled
P6 1.0 to 19.9
5
%RH Dehumidification differential
(b1 odd number) in humidity control
mode (A0 = 2 or 3)
P7 (1) St to 100
100
%RH Hi-limit set point
Accessible only with hi-limit control
(A0=3)
P8 2.0 to 19.9
5
%RH Hi-limit differential
P9
0 to 100
100
%RH Hi-limit alarm set point
Code Range
Default
Unit
Description
d1 (2) 0.0 to 199
read
only
%RH, °C,
%
Signal from external controller
or sensor
Not accessible in on/off mode (A0=0)
d2 0.0 to 199
%RH
Signal from hi-limit or
temperature sensor
Accessible only with hi-limit control
(A0=3)
d3 0.0 to 199
kg/h
Steam output (actual)
d4
0.0 to
19999
h
Run time hours
d5
0 to 1555
µS/cm Conductivity of the feed water
d6 0.0 to 199
A
Current (Amperage)
d9 0.0 to 199
kg/h
Rated steam output
(1): when accessing parameter A0, parameters P2, P3, P7 and St are automatically reset to the corresponding
default value.
(2): in proportional operation (A0=1), d1 displays the % of the control signal
To display the Level 3 Configuration Parameters:
•
Press and hold the PRG and SEL buttons simultaneously for 5 seconds until 00 is displayed;
•
Press the
and
buttons to enter the password value of 77;
•
Press the SEL button and A0 should display;
•
Press the
and
buttons to scroll through the configuration parameters;
•
Press the SEL button to display the value of any parameter (the unit of measure will display first for 1
second);
•
Press the
and
buttons to change the value;
•
Press SEL when the change is complete and then continue scrolling through the parameters;
•
To leave the programming mode, press PRG at any time. NOTE: after more than 5 seconds without a
button press, the display will begin to blink. 60 seconds after a button press, the controller will erase all
changes and return to operating mode with the previous parameters.