PP6 

DEHUMIDIFIER 

OWNER’S MANUAL 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

www.eipl.co.uk 

 

Summary of Contents for Ebac PP6

Page 1: ...Page 1 of 12 Drawing TPC148 Issue 4 Date 24 11 16 PP6 DEHUMIDIFIER OWNER S MANUAL www eipl co uk ...

Page 2: ...s reheated With the addition of other radiated heat the air is discharged into the room at a higher temperature but lower relative humidity than when the air entered the unit Continuous circulation of the room air through the dehumidifier unit gradually reduces the relative humidity in the room The PP6 dehumidifier is a robust compact unit designed to control the humidity in the enclosed space in ...

Page 3: ...ng Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label MODEL PP6 HEIGHT 256mm WIDTH 300mm DEPTH 470mm WEIGHT 25 Kg AIRFLOW 7 M3 min POWER SUPPLY 230V 1 ph 50Hz POWER 350W max FINISH Epoxy coated Zintec steel REFRIGERANT TYPE QT...

Page 4: ...allation and operation the unit inlet and outlet must have a clearance of 0 5M from all adjacent surfaces and or structures WIRING Connect the power mains cable to a 5 or 13 Amp power supply As follows Brown Live Blue Neutral Green Yellow Earth ground DRAINAGE Connect a 12 5mm inside diameter hose to the condensate outlet pipe positioned centrally beneath the air inlet grille Secure the hose using...

Page 5: ...TION If the ambient temperature of the room in which the dehumidifier unit is conditioning falls below 15ºC ice will form on the evaporator coil as the air is passed over it after a time this build up of ice on the evaporator coil will effect the efficiency of the unit on its ability to maintain the required set conditions for the room The PP6 is therefore fitted with a defrost control device This...

Page 6: ...ve the build up of ice No attempt should be made to cut open any part of the refrigeration circuit due to high pressures and gas involved If the unit is switched off at the mains power supply for any reason the unit must be allowed to stand at rest for at least three minutes before restarting Failure to do so may cause the unit to blow the fuses owing to the compressor due to there being a refrige...

Page 7: ...ve 25 C the coil may be covered with droplets of water rather than frost Partial frosting accompanied by frosting of the thin capillary tubes indicates loss of refrigerant gas or low charge 4 Check all wiring connections 5 To check the operation of the defrost system switch the machine on and leave it running for approximately 45 minutes The machine will then enter Hot Gas defrost mode for approxi...

Page 8: ...the refrigerant compressor The charging stub should be crimped and rebrazed after servicing NEVER allow permanent service valves to be fitted to any part of the circuit Service valves may leak causing further loss of refrigerant gas 3 The refrigerant compressor fitted to the dehumidifier is a durable unit that should give many years of service Compressor failure can result from the machine losing ...

Page 9: ...e the fan motor 3 See Routine Maintenance Section 4 Check the wiring diagram to find fault and repair 5 Adjust humidistat as required or replace Little or no water extraction 1 Insufficient air flow 2 Compressor fault 3 Loss of refrigerant gas 1 Check all of the above 2 Contact the Factory Service Center 3 Contact the Factory Service Center Little or no defrost when required 1 Faulty Timer 2 Fault...

Page 10: ...over 3021518 Condenser Coil 3020740 Evaporator Coil 3014203 Filter Dryer 3020937 Fan Motor 3030194 Fan Blade 3040101 By pass Valve 3020811 P C B Timer 1601900 Solenoid Coil 3030422 Drain Tube 3014338 Worm Drive Clip 3086101 Clip Nut 3080501 Mains Cable 3031225 Control Humidistat 3031528 Stowage Plate 1012305 Fastener 3087401 Washer 3087403 Spare parts available online www EIPLDIRECT com ...

Page 11: ...rd This product contains fluorinated greenhouse gases covered by the Kyoto Protocol The refrigeration system is hermetically sealed The Global Warming Potential GWP of refrigerants used in products manufactured by Ebac Industrial Products Ltd is as follows R134a 1300 R407c 1610 For type and weight of refrigerant contained in this unit please refer to the product data label Due to the high pressure...

Page 12: ...www eipl co uk sales eipl co uk American Sales Office Ebac Industrial Products Inc 700 Thimble Shoals Blvd Suite 109 Newport News Virginia 23606 2575 USA Tel 01 757 873 6800 Fax 01 757 873 3632 www ebacusa com sales ebacusa com German Sales Office Ebac Industrial Products Ltd Gartenfelder Str 29 37 Gebäude 35 D 13599 Berlin Germany Tel 49 3043 557241 Fax 49 3043 557240 www eip ltd de sales eip ltd...