background image

Chapter 5  ALERT Library Management

Library Status

MC300 Prism Management Card User’s Guide

45

Table 10   Element 
Information Fields

Field

Description

Address

Displays the hexadecimal address of the element

Barcode

If a cartridge is present in the element and has a 

barcode, the barcode label displays. If a cartridge is 

present in the element and does not have a barcode, 

the message 

(Barcode?)

 appears. If no cartridge is 

present in the element, the field is blank.

Type

Displays the element being viewed

BUS ID

This field displays the BUS ID of the element being 

viewed. (For SCSI devices, the BUS ID is the unique 

target ID of the device. For Fibre Channel devices, 

the BUS ID is the unique Loop ID of the device or 

“Soft” to indicate soft addressing mode.)

Interface Type

This field displays the element connection type 

(whether SCSI or Fibre Channel)

Serial Number

Displays the serial number of the selected tape drive

Model

Displays the tape drive type, such as 

DLT8000

Revision

Displays the firmware revision number

Cleaning 
Needed

Displays 

Yes

 if the tape drive is in need of cleaning. 

This informational message permits you to schedule 
the drive cleaning. If the condition is allowed to 

persist, the drive eventually moves to the 

Cleaning 

Required

 state and the drive will not function until 

cleaning is performed.

Cleaning Tape 
Expired

Displays 

Yes

 if the cleaning cartridge has expired

Cleaning 
Required

Displays 

Yes

 if cleaning is required. The tape drive 

will not function until cleaning is performed.

Hardware Error

Displays 

Yes

 for a hardware error, default is 

No

Load Complete

If the tape load is complete, displays 

Yes

, default is 

No

Содержание MC300 Prism

Страница 1: ...MC300 Prism Management Card User s Guide 6311631 10 Ver 10 Rel 0...

Страница 2: ...orporation may revise this publication from time to time without notice COPYRIGHT STATEMENT Copyright 2003 by Quantum Corporation All rights reserved Your right to copy this manual is limited by copyr...

Страница 3: ...Management Console Web Pages 3 Using the Prism Management Console Interface 4 Home Page 5 First Time User Account Setup 6 Accessing Online Help 6 Accessing the Quantum Web Site 7 Chapter 2 PMC Server...

Страница 4: ...9 Shutting Down the PMC 20 Chapter 3 ALERT SNMP 21 SNMP Configuration 21 SNMP Community Management 24 Accessing Community Management 24 Viewing Existing Communities 25 Editing a Community 25 Deleting...

Страница 5: ...izing Statistics 52 Library Firmware Upload 53 Monitoring Configuration Page 54 Accessing Monitoring Configuration 54 Setting the Monitoring Interval 54 Generating a Weekly Status Report 55 Event Hist...

Страница 6: ...Contents vi MC300 Prism Management Card User s Guide Chapter 7 Getting Help 79 Appendix A Event Details Listing 81 Appendix B Battery Statements 113 Glossary 117 Index 121...

Страница 7: ...ent 13 Figure 5 Edit Users 14 Figure 6 Utilities 17 Figure 7 Shutdown Prism Management Card 20 Figure 8 SNMP Configuration 22 Figure 9 Community Management 24 Figure 10 Edit Community 26 Figure 11 Con...

Страница 8: ...vent History 57 Figure 23 Cabling for a Single FC420 in an ATL M1500 61 Figure 24 Cabling for a Single FC420 in an ATL M2500 61 Figure 25 Cabling for Three FC420s in an ATL M2500 62 Figure 26 Cabling...

Страница 9: ...32 Table 7 Message Configuration Fields 34 Table 8 E mail Configuration Fields 38 Table 9 Library Status Fields 40 Table 10 Element Information Fields 45 Table 11 Library Configuration Page Field Des...

Страница 10: ...Tables x MC300 Prism Management Card User s Guide Table 18 Failure Events Detail 101 Table 19 Failure Events Detail 112...

Страница 11: ...es library and a PMC Hereafter the libraries are referred to as ATL M1500 and ATL M2500 This document assumes that the reader has a moderate level of general computer knowledge and server systems admi...

Страница 12: ...se the ALERT Library Management Web pages Library Status Library Configuration Library Statistics Service Operations Monitoring Configuration and Event History Chapter 6 Fibre Channel Management expla...

Страница 13: ...scape Communicator 4 78 and 6 2 or later You can download this software from http www netscape com Microsoft Internet Explorer IE 5 5 or 6 0 You can download this software from http www microsoft com...

Страница 14: ...uick Reference Guide This guide provides step by step instructions for installation of the PMC for the ATL M Series libraries 6473010 ATL FC310 Quick Reference Guide This guide provides step by step i...

Страница 15: ...ineering Documents 15 Inverness Way East Englewood CO 80112 800 854 7179 or 303 397 2740 Contact Quantum company contacts are listed below Quantum Corporate Headquarters 0 To order documentation on th...

Страница 16: ...839 0988 Europe Middle East Africa International Code 44 0 1256 848748 Send faxes for the Customer Support Department to North South America 949 725 2176 Asia Pacific Rim International Code 61 7 3839...

Страница 17: ...existing and future functionality Included with the PMC is an easy to use yet powerful Web based interface known as the Prism Management Console It allows authorized staff to configure and manage all...

Страница 18: ...e PMC The Subnet Mask default is 255 255 255 0 If your subnet mask is different you need to set up an isolated network access the PMC and modify it from the Prism Management Console to add it into the...

Страница 19: ...tings 2 In the Address field of your browser type the IP address for the PMC When the correct IP address for the PMC has been entered the Internet browser displays the Prism Management Console Home pa...

Страница 20: ...nterface 1 The Prism Management Console interface see figure 1 is divided into three distinct sections The Banner frame displays the Quantum logo and software name Clicking the Quantum logo links you...

Страница 21: ...le Green The library is ready for normal operation Unable to communicate with library Red A communication problem exists between the PMC and the library Possible causes include a bad serial connection...

Страница 22: ...tton at the bottom of the current Web page A new Internet browser window opens and displays online help for the current Web page Note A default user name admin and password admin is assigned when you...

Страница 23: ...Prism Management Card User s Guide 7 Accessing the Quantum Web Site 1 To access the Quantum Web site 1 Click the Quantum link in the navigation frame of the Prism Home page see figure 1 The Web browse...

Страница 24: ...Chapter 1 Prism Management Console Using the Prism Management Console Interface 8 MC300 Prism Management Card User s Guide...

Страница 25: ...stname domain IP address subnet mask and gateway addresses Date and Time Configuration Page allows you to set or adjust the date and time User Management Page allows you to set up users that are permi...

Страница 26: ...diting Network Configuration 2 To access or change the basic configuration of the PMC 1 In the navigation frame under PMC Server Management click Network Configuration The Network Configuration page d...

Страница 27: ...me View or set the hostname for the PMC for example the DNS name The default value is PMC300 MAC address When entering a hostname no spaces are allowed Underscores are acceptable Domain View or set th...

Страница 28: ...the changes to the PMC Accessing Date and Time Configuration 2 To access the Date and Time Configuration page 1 In the navigation frame click Date and Time Configuration The management frame displays...

Страница 29: ...sing User Management 2 To access the User Management page 1 In the navigation frame click User Management 2 The management frame displays the User Management page see figure 4 Figure 4 User Management...

Страница 30: ...it The management frame displays the Edit Users page see figure 5 Figure 5 Edit Users 3 Under Add User add the new user account information A unique user name in the User Name field The desired passwo...

Страница 31: ...eting User Accounts 2 To delete a user account 1 Access the User Management page 2 Under Edit User click Edit The management frame displays the Edit Users page see figure 5 3 Under Delete User select...

Страница 32: ...e user in the selection of a Software Image file Once a Software Image file is selected the upload initiates by clicking on the Upload button The Activate New Software Image button causes the last upd...

Страница 33: ...uide 17 Figure 6 Utilities Uploading New Software Image 2 The Upload a New Software Image option is intended for the FSE to update the PMC operating software To upload a new software image 1 Access th...

Страница 34: ...age and rebooting the PMC see Rebooting the PMC and Library Activating a New Software Image 2 To move the uploaded software image from the temporary area replace the current software image and activat...

Страница 35: ...ormation the PMC and library must be rebooted To reboot the PMC and library To reboot the PMC and library 1 Access the Utilities Page 2 Under Shutdown Prism Management Card select Reboot and click OK...

Страница 36: ...ng follow this procedure whenever you must shutdown a library with a PMC installed 1 Shutdown the PMC first Select Shutdown from the Shutdown Prism Management Card pull down menu on bottom of the Util...

Страница 37: ...ories containing predefined traps SNMP Community Management allows you to set up the communities that have access to the ALERT SNMP option and define their read write privileges SNMP Configuration 3 T...

Страница 38: ...as required see table 4 Figure 8 SNMP Configuration 2 If necessary change the library name or location 3 If necessary enable the trap types to be reported Informational Traps Warning Traps Failure Tra...

Страница 39: ...plays a listing of the supported Informational traps Warning Traps If selected Warning level traps are enabled The Details button displays a listing of the supported Warning traps Failure Traps If sel...

Страница 40: ...o perform a set operation the SNMP management software must provide a community name with Read write privileges All SNMP requests must conform to the IP access rules Accessing Community Management 3 T...

Страница 41: ...onfigured communities and their properties including Community Name createname IP Address xxx xx x x Subnet Mask 255 255 255 0 Access read only Editing a Community 3 To edit a community 1 Access the C...

Страница 42: ...or blank spaces are allowed Enter an IP address in the IP Address field If the value in the Subnet Mask field ends in a zero the value in the IP address edit box must also end in a zero Enter a subne...

Страница 43: ...ommunity has been added 5 Click OK to return to the Edit Community page Deleting Communities 3 To delete communities 1 Access the Community Management page 2 Under Edit Communities click Edit The mana...

Страница 44: ...Chapter 3 ALERT SNMP SNMP Community Management 28 MC300 Prism Management Card User s Guide...

Страница 45: ...installed on the host computer Contact Configuration Page allows you to set up information about the company that owns the library and the primary and secondary contacts Message Configuration Page all...

Страница 46: ...orm contains information about the primary and secondary people who are to be contacted in case of library failure or other actions such as notification of firmware updates To view or edit the contact...

Страница 47: ...n 2 If desired insert or change the company information or the primary or secondary library administrators see table 5 Note The Support Contract field is initially set up by the FSE during installatio...

Страница 48: ...r the installed library Street Street address at which the library is installed City City for the above street address State State or territory for the above street address Postal Code Postal code or...

Страница 49: ...ure 12 allows you to Control who in the company is notified of various types of library errors failures and activity Select when to notify Quantum Customer Support Pager The pager telephone number for...

Страница 50: ...ation Fields Field Description Hardware Failure Errors or failures requiring onsite assistance or follow up such as Tape drive failure detection Library control card failure Configuration Changes Chan...

Страница 51: ...sage Configuration page 2 Click the down arrow if SelectRecipient is visible in the Delete Recipient field for the desired message type A list of existing e mail recipients for that message type is di...

Страница 52: ...tances of the desired message type 4 Click Apply A Results page indicates the e mail recipient has been added 5 Click OK to return to the Message Configuration page Deleting E mail Recipients 4 To del...

Страница 53: ...essages The information must be entered before any ALERT E mail options will work Viewing or Changing E mail Configuration 4 To view or edit the E mail Configuration page 1 In the navigation frame und...

Страница 54: ...n From E mail Account Prism_Management_Console is the default account The name entered here must be a valid address on the e mail server specified in the Outgoing E mail Server field Do not add the do...

Страница 55: ...s of the library It also allows you to move cartridges to various locations in the library or multiple library stack Library Configuration Page allows you to view and set the BUS ID configuration of t...

Страница 56: ...ame number is additional information see table 9 Table 9 Library Status Fields Note This page remains blank while the PMC queries the library for status The page will periodically go blank while the i...

Страница 57: ...sm Management Card User s Guide 41 Figure 14 Library Status Part 1 Hand Cartridge status in the hand Bin Cartridge status of the bins Bins appearing with a shaded area are designated as import export...

Страница 58: ...Chapter 5 ALERT Library Management Library Status 42 MC300 Prism Management Card User s Guide Figure 15 Library Status Part 2 Drive element status...

Страница 59: ...and figure 15 Also refer to the physical view of the library frames to determine the identification of the bins for the cartridge movement see Library Status To move an individual tape cartridge from...

Страница 60: ...us page Scroll down to the appropriate frame and level then select the desired tape drive in the Drive section of the graphic 2 In the Library Physical View section of the page click the number of the...

Страница 61: ...o indicate soft addressing mode Interface Type This field displays the element connection type whether SCSI or Fibre Channel Serial Number Displays the serial number of the selected tape drive Model D...

Страница 62: ...erface type and the BUS ID of the library and drives Figure 17 Library Configuration BUS ID Configuration OK to Operate Handle Displays status and whether the hand is available for operation Compressi...

Страница 63: ...e type can be selected The two choices are SCSI and Fibre Note The interface is obtained automatically for the current fitted devices and can be set for future drives BUS ID Indicates the BUS ID of th...

Страница 64: ...y Management click Library Statistics The management frame displays the Library Statistics page see figure 18 The Library Statistics page includes statistical information on each library frame and its...

Страница 65: ...Chapter 5 ALERT Library Management Library Statistics Page MC300 Prism Management Card User s Guide 49 Figure 18 Library Statistics Part 1...

Страница 66: ...Chapter 5 ALERT Library Management Library Statistics Page 50 MC300 Prism Management Card User s Guide Figure 19 Library Statistics Part 2...

Страница 67: ...Operations page allows you to perform various service and status tests and view the results Accessing Service Operations 5 To view the Service Operations page 1 In the navigation frame under ALERT Lib...

Страница 68: ...Axis Sensor Check Picker Axis Sensor Check Theta Axis Sensor 1 Check Theta Axis Sensor 2 Check Elevator Axis Sensor 2 Click Apply A Results page indicates the self test is complete 3 Click OK to retur...

Страница 69: ...n until the upload completes Verify the image file is valid otherwise you may render the library unusable after the upload Caution The entire process may take up to 45 minutes depending on the network...

Страница 70: ...ing Configuration 5 To view the Monitoring Configuration page 1 In the navigation frame under ALERT Library Management click Monitoring Configuration The management frame displays the Monitoring Confi...

Страница 71: ...ry Statistics function This report can be sent via e mail to the administrator To specify when to generate a weekly status report of the library 1 In the Weekly Status Report section of the page speci...

Страница 72: ...le through the Event History page see figure 22 The Event History page includes information by Title the specific trap code Description a brief description of the code including the Fault System Code...

Страница 73: ...Chapter 5 ALERT Library Management Event History Page MC300 Prism Management Card User s Guide 57 Figure 22 Event History...

Страница 74: ...Chapter 5 ALERT Library Management Event History Page 58 MC300 Prism Management Card User s Guide...

Страница 75: ...nd refresh the route maps related to the Fibre Channel bridges Bridge Status allows you to view the hardware and software status of the Fibre Channel bridges Bridge Administration allows you to config...

Страница 76: ...ver cable to connect the bottom Ethernet port on the PMC ETH 1 to the Ethernet port on the FC420 bridge see figure 23 and figure 24 Note These instructions call out specific Ethernet cables to be used...

Страница 77: ...for a Single FC420 in an ATL M1500 Figure 24 Cabling for a Single FC420 in an ATL M2500 MC300 PMC FC420 Cross over cable is not supplied other standard cabling not shown for clarity Ethernet cross ove...

Страница 78: ...switch using a CAT 5 Ethernet cable 2 Connect the Ethernet port of each FC420 bridge to an available port on the Ethernet hub switch using a CAT 5 Ethernet cable see figure 25 figure 26 and figure 27...

Страница 79: ...Management Card User s Guide 63 Figure 26 Cabling for Two or More FC420s in an ATL M1500 Stack FC420 one MC300 PMC 100Mbit second Ethernet hub switch per library Uplink port do not use Ethernet cables...

Страница 80: ...for each FC420 bridge If your hub switch does not have enough ports you can connect the uplink port of a second hub switch to one of the standard ports on the primary hub switch to provide more ports...

Страница 81: ...arated by a title that contains the bridge number Under each bridge title is the route map that denotes the Fibre Channel paths from the host to the FC420 bridge including port bus target and Logical...

Страница 82: ...ee table 12 Table 12 Route Status Descriptions Field Description LUN The LUN assigned to the Fibre Channel port Device The SCSI device type using the LUN available types are CHANGER TAPE and BRIDGE Bu...

Страница 83: ...ure 29 At the top of the Bridge Status page is a line of text that denotes the number of FC420 bridges that are installed and connected to the PMC Each bridge is separated by a title that contains the...

Страница 84: ...ter 6 Fibre Channel Management Bridge Status 68 MC300 Prism Management Card User s Guide Figure 29 Bridge Status The hardware and software status information within the table is defined below see tabl...

Страница 85: ...on levels for the NVRAM Command Line Interface and the Fibre Channel bridge firmware WWName Displays the World Wide Name WWN for the Fibre Channel port SCSI Busses n LVD Displays the number and type o...

Страница 86: ...fer rate at which the bridge will operate The options are 1 Gb per second 2 Gb per second or Auto negotiated takes effect after a reboot Set Fibre Channel Loop ID configures a hard addressing 0 125 or...

Страница 87: ...r all bridges A bridge takes approximately 30 seconds to reboot Upload New Bridge Firmware installs new bridge firmware to one bridge or all bridges It takes approximately 60 seconds to upload new bri...

Страница 88: ...Chapter 6 Fibre Channel Management Bridge Administration 72 MC300 Prism Management Card User s Guide Figure 31 Bridge Administration Part 2...

Страница 89: ...m the Mode pull down list The mode types include Loop Point to Point Loop to PTP PTP to Loop 4 Click Apply A Results page displays indicating the mode was configured Setting the Fibre Channel Data Rat...

Страница 90: ...t a bridge from the Bridge pull down list 3 Enter the desired Loop ID for the selected bridge 4 Click Apply A Results page appears indicating the loop ID was configured Route Maps 6 To configure a Rou...

Страница 91: ...A Results page displays indicating the Route Map was configured Route Bridge LUN 6 To select a bridge and a destination LUN 1 Select a bridge from the Bridge pull down list 2 Select a Fibre Channel LU...

Страница 92: ...Copy setting 1 Select a bridge from the Bridge pull down list 2 Select an action from the Action pull down list The choices are Enable or Disable 3 Click OK A Results page appears indicating the chang...

Страница 93: ...the Bridge Administration page In the Navigation frame under Fibre Channel Management click Bridge Administration 2 Select a specific bridge or All from the Bridge pull down list 3 Enter the name of t...

Страница 94: ...Chapter 6 Fibre Channel Management Bridge Administration 78 MC300 Prism Management Card User s Guide...

Страница 95: ...es provide extensive online help files defining actions and terms for all functions features and fields To access the Help page press of the following the Help link at the bottom of the navigation fra...

Страница 96: ...Chapter 7 Getting Help 80 MC300 Prism Management Card User s Guide Figure 32 Help...

Страница 97: ...ftware installed on the host computer This configuration allows you to set up information about SNMP and select categories containing predefined traps The predefined traps are listed in this appendix...

Страница 98: ...ne or drive removed 2415 No mail generated Move medium attempted to drive that is being autocleaned 2418 Soft Error Requested action cannot be performed because robot is in use 2629 Hardware Failure A...

Страница 99: ...or Cleaner cartridge fitted 400F No mail generated Move medium destination full 4010 No mail generated Move medium source empty 4011 Soft Error Parameters not saved Undefined 4012 Soft Error Illegal e...

Страница 100: ...rial port 4101 Configuration Change Time set via synchronization command 4102 Configuration Change Synchronize clock command issued 4103 No mail generated Library is rebooting 4104 Configuration Chang...

Страница 101: ...has been removed right magazine 440B No mail generated Magazine 3 has been removed left magazine 440C No mail generated Magazine 4 has been removed right magazine 440D No mail generated Magazine 5 has...

Страница 102: ...d Magazine 6 has been inserted right magazine 4419 No mail generated Magazine 7 has been inserted left magazine 441A No mail generated Magazine 8 has been inserted right magazine 441B No mail generate...

Страница 103: ...erated Magazine 9 absent at power up left magazine 4426 No mail generated Magazine 10 absent at power up right magazine 4427 No mail generated Library ready 4428 No mail generated Library not ready 44...

Страница 104: ...6 in this frame inserted 443E No mail generated Drive 1 in this frame absent at power on 443F No mail generated Drive 2 in this frame absent at power on 4440 No mail generated Drive 3 in this frame ab...

Страница 105: ...No mail generated Drive 3 in this frame has powered down 4455 No mail generated Drive 4 in this frame has powered down 4456 No mail generated Drive 5 in this frame has powered down 4457 No mail gener...

Страница 106: ...lly 4473 Soft Error Drive 2 in this frame has been cleaned successfully 4474 Soft Error Drive 3 in this frame has been cleaned successfully 4475 Soft Error Drive 4 in this frame has been cleaned succe...

Страница 107: ...5 in stack has been powered down disconnected 448B No mail generated Module at level 6 in stack has been powered down disconnected 448C No mail generated Module at level 7 in stack has been powered d...

Страница 108: ...fitted in stack 4498 No mail generated Level 6 fitted in stack 4499 No mail generated Level 7 fitted in stack 449A No mail generated Level 8 fitted in stack 449B No mail generated Level 9 fitted in st...

Страница 109: ...o mail generated Level 9 not fitted in stack 44A8 No mail generated Level 10 not fitted in stack 44A9 No mail generated Level 11 not fitted in stack 44AA No mail generated Level 12 not fitted in stack...

Страница 110: ...as become the stack master elevator controller 4901 Configuration Change This unit has changed from stack master to slave module 4902 Soft Error The stack master is no longer polling this unit Tape Al...

Страница 111: ...resent drive 1 in this frame 200B Hardware Failure Drive caddy not present drive 2 in this frame 200C Hardware Failure Drive caddy not present drive 3 in this frame 200D Hardware Failure Drive caddy n...

Страница 112: ...rame indicates drive busy 2038 Hardware Failure Response received from drive 5 in this frame indicates drive busy 2039 Hardware Failure Response received from drive 6 in this frame indicates drive bus...

Страница 113: ...1A Soft Error Stack contains modules configured for different media to stack master 241B Soft Error Fixed slot detected when library configured for 6 drive operation 241C Soft Error No fixed slot dete...

Страница 114: ...The cartridge is not fully in the elevator manual intervention required 263F Hardware Failure Manual intervention and power cycle are required 2640 Hardware Failure Detail is not known but manual inte...

Страница 115: ...vailable 26DD Hardware Failure Attempt to initialize Drive 6 in this frame before it has become available 4200 Soft Error NVR CRC invalid and contents probably corrupt Tape Alert Flag E mail Message E...

Страница 116: ...fault 34 Soft Error Firmware download failed 35 Soft Error Drive humidity limits exceeded 36 Soft Error Drive temperature limits exceeded 37 Soft Error Drive voltage limits exceeded 38 Soft Error Pre...

Страница 117: ...ree called on bad memory block 0009 Hardware Failure Realloc found corrupted memory block 0010 Hardware Failure Free found corrupted memory block trailer 0011 Hardware Failure Realloc found corrupted...

Страница 118: ...ow 1003 Hardware Failure FPGA DONE pin was detected as being low when it should have been high 2000 Hardware Failure DLT initialization failed 2001 Hardware Failure Drive timeout waiting for status dr...

Страница 119: ...t received from drive 5 in this frame 201F Soft Error Invalid packet received from drive 6 in this frame 2023 Hardware Failure Could not get a semaphore from OS 2024 Hardware Failure Response packet r...

Страница 120: ...Pending interrupt status not reset 2200 Hardware Failure UI task init failed 2201 Hardware Failure UI queue full 2202 Hardware Failure The UI is not in the correct state to perform the requested acti...

Страница 121: ...rget position 2607 Hardware Failure The Z axis failed to get to its target location 2608 Hardware Failure The X axis tacho counter failed to clear at power on 2609 Hardware Failure The Y axis tacho co...

Страница 122: ...ilure The hand action completed but was unable to engage 261D Hardware Failure The hand will not move in either direction 261E Hardware Failure The hand could not get the cartridge to its required pos...

Страница 123: ...iction is too high for normal operation 2633 Hardware Failure The Z axis did not travel the minimum distance when calibrating 2635 Hardware Failure The Z axis friction is too high for normal operation...

Страница 124: ...e Failure Drive 6 in this frame will not allow the hand to be operated as required 2690 Hardware Failure Drive 1 in this frame hand failed to close 2691 Hardware Failure Drive 2 in this frame hand fai...

Страница 125: ...Failure Drive 6 in this frame is indicating in flux not ready for commands 26A8 Hardware Failure Drive 1 in this frame is indicating its hand is closed and should be open 26A9 Hardware Failure Drive 2...

Страница 126: ...this frame has not responded to multiple requests to unload 26C2 Hardware Failure Drive 3 in this frame has not responded to multiple requests to unload 26C3 Hardware Failure Drive 4 in this frame has...

Страница 127: ...frame has failed to load the tape successfully 2700 Hardware Failure PCDIAG task init failed 2701 Soft Error Unknown or bad diagnostic message 2702 Soft Error Current diagnostic stack has terminated...

Страница 128: ...Hardware Failure Tape snapped or cut in the drive where media cannot be ejected 20 Soft Error The drive has a head clog or needs cleaning 22 Soft Error The cleaning tape has expired 30 Hardware Failur...

Страница 129: ...d Quantum service center There is a danger of explosion if the battery is incorrectly replaced Replace only with the same or equivalent type recommended by the manufacturer Attention Il y a danger d e...

Страница 130: ...T ss tuotteessa on litiumparisto Emolevyll oleva Dallas Semiconductor DS12B887 sis lt litiumpariston Litium saattaa olla luokiteltu vaaralliseksi aineeksi H vit t m paristo paikallisten lakien ja m r...

Страница 131: ...rmative vigenti Precauci n 2 Este producto contiene una bater a de litio El modelo Dallas Semiconductor DS12B887 de la placa base contiene una bater a de litio El litio puede ser considerado un materi...

Страница 132: ...Appendix B Battery Statements 116 MC300 Prism Management Card User s Guide...

Страница 133: ...e system administrator The community name is used as a selector by the agent to specify the access to local or remote management information and the context of the management information The names pub...

Страница 134: ...e Separate library modules connected through a common robot or elevator are considered frames Each individual frame will have a unique identifier FSE Field Service Engineer A representative of Quantum...

Страница 135: ...he operating system is reloaded restart The process of restarting a computer without reloading the operating system S SCSI Small Computer System Interface A parallel interface standard used by many sy...

Страница 136: ...ogram interrupt usually caused by some exceptional situation in the user program In most cases the user performs some action then returns control to the program U URL Uniform resource locator A server...

Страница 137: ...tivating software image 18 Adding community 25 e mail recipients 36 user account 14 Administration bridge 70 Administrator library contact 31 ALERT E mail 29 Library management 39 SNMP 21 81 B Banner...

Страница 138: ...g community 27 e mail recipient 36 user account 15 Displayed frames 4 E Editing e mail configuration 37 e mail recipients 35 users 14 E mail Prism ALERT 29 recipients adding 36 deleting 36 viewing 35...

Страница 139: ...5 Messages status 5 Monitoring configuration 54 Monitoring interval 54 N Network configuration 10 Number contract support 31 O On line Help accessing 6 Operations service 51 P Page community managemen...

Страница 140: ...nity 24 configuration 22 Software image activating 18 Status bridge Fibre Channel 67 70 library 5 Status library 43 Support contract number 31 T Tape SCSI device 66 Test E mail 38 U Upload library fir...

Отзывы: