Quantum DX-Series System Unpacking and Installation Instructions
Document 6513502-06 A01
October 2006
36
Installing the DX-Series System
b
Connect strapping port
Out
on the fifth AC power sequencer to
strapping port
In
on the sixth AC power sequencer.
c
Connect strapping port
Out
on the sixth AC power sequencer to
strapping port
In
on the seventh AC power sequencer.
d
Connect strapping
Out
on the seventh AC power sequencer to
strapping port
In
on the eight AC power sequencer.
Figure 33 DX100 Power
Cabling (Controller, Ethernet
and Fibre Channel Switch)
Note:
Odd and even numbered AC power sequencers should be on
separate circuits for redundancy.
Note:
The storage arrays MUST be connected to the exact outlets
specified to allow the software discovery to function correctly.
Note:
Connect AC inputs to an external AC power source on a
dedicated circuit. Ensure that the AC inputs are secured to the
power sequencers with cable retention clamps.
J8
J7
J6
J5
J4
J3
J2
J1
AC input
Ethernet switch
Controller
Fibre Channel
in
out
First AC power sequencer
J8
J7
J6
J5
J4
J3
J2
J1
AC input
in
out
Second AC power sequencer
Primary AC
power source (separate circuit)
CAT5
cable
CAT5
cable
Switch
Secondary AC
power source (separate circuit)