17
01/21
7082-153K
Figure 17.1
NOTE: Use metal plate around
exhaust vent pipe and seal all
edges with non-flammable
insulation such as fiberglass,
mineral wool or ceramic.
Do not use high temperature
caulking materials to seal any
edge
to
prevent
future
serviceability.
Outside Air
Termination
A. Full Reline with Outside Air - Horizontal
NOTE:
In Canada, where passage through a wall or
partition of combustible construction is desired, the
installation shall conform to
CAN/CSA-B365
NOTE:
•
Illustrations reflect typical installations and are FOR
DESIGN PURPOSES ONLY.
•
Illustrations/diagrams are not drawn to scale.
•
Actual installation may vary due to individual
design preference.
55
Venting Systems
Never draw outside combustion air from:
•
Wall, floor or ceiling cavity
•
Enclosed space such as an attic or garage
CAUTION
Fire Risk.
Inspection of Chimney:
• Masonry chimney must be in good condition.
• Meets minimum standard of
NFPA 211
• Factory-built chimney must be a minimum 6
inch (152mm)
UL103 HT
.
WARNING
NOTE:
Check clearances carefully for this type of
installation to ensure adequate room for outside air
venting.
B. Full Reline with Outside Air - Vertical
Figure 17.2
NOTE: Use metal plate
around exhaust vent pipe
and seal all edges with
non-flammable insulation
such as fiberglass, mineral
wool or ceramic.
Do not use high temperature
caulking materials to seal
any edge to prevent future
serviceability.
Outside Air
Termination at
Chimney Top
(Vertical)
12 in [305mm]
min. below
12 in [305mm]
min. below
NOTE:
In Canada this fireplace insert must be installed
with a continuous chimney liner extending from the
fireplace insert to the top of the chimney. The chimney
liner must conform to the Class 3 requirements of
CAN/
ULC-S635, Standard for Lining Systems for Existing
Masonry or Factory-Built Chimneys and Vents, or
CAN/ULC-S640, Standard for Lining Systems for New
Masonry Chimneys
.
NOTE:
In Canada only a full reline is allowed per
ULC
S628, ORD ULC C1482-M1990
.
Check building codes prior to installation.
•
Installation MUST comply with local, regional, state
and national codes and regulations.
•
Consult local building, fire officials or authorities
having jurisdiction about restrictions, installation
inspection, and permits.
CAUTION