 16 

 

 

 

 

                       7080-163D 

 

 

 

       August 3, 2018

MT. VERNON E2-C

R. Thermostat Controls

TEMPERATURE (HEAT / OFF) SWITCH:

Set this switch to HEAT to control your appliance. The off 

position will disable the appliance.

SET (MULTI- FUNCTION) SLIDE SWITCH:

This provides easy access to common settings, and should 

always remain in RUN unless items are being adjusted.

NOTE:

 When thermostat is set to “Manual” non-

programmable mode, all positions of the SET slide 

switch will act like RUN.

UP / DOWN BUTTONS:

The UP and DOWN buttons are used to control the set 

temperature, or adjust any other on-screen items. An items 

flashing, is the item currently being adjusted.

HOLD BUTTON:

This button activates and deactivates the manual 

Temperature HOLD feature, which maintains a fixed set 

temperature indefinitely without following a program routine.

COPY BUTTON:

This is used to copy temperature program items from one 

day to the next. Also used to to access the menu setup.

NEXT BUTTON:

This is used when setting items such as software options, 

and temperature programs when they are flashing on the 

screen. Pressing the NEXT button will cycle through which 

item is flashing.

Figure  16.1

S. Thermostat Setup Options

Setup options for how the thermostat will function are 

performed using a menu on the display screen.

TO ACCESS THE SETUP MENU:

Move the TEMPERATURE switch into the OFF position, 

and then hold down the COPY button for approximately 5 

seconds until the screen changes. The menu will always 

start with item #01, and is advanced to each following item 

by a single press of the NEXT button. The options for each 

item are changed using the UP or DOWN buttons.

ITEM #01 (CLK = CLOCK FORMAT):

•  12Hr, default: This displays the clock times using 

standard AM and PM values. 

•  24Hr: This displays the clock times using the military-

time format (example 22:00 hours, without using AM or 

PM).

ITEM #02 (TMP = TEMPERATURE SCALE):

•  F, default: Shows all temperature values in Fahrenheit.

•  C: Shows all temperature values Celsius.

ITEM #03 (PROGRAMMING STYLE):

•  7 Day, default: This style uses a separate program 

routine for each of the 7 days in the week.

•  5/2 Day: This style uses a weekday program routine for 

Monday, Tuesday, Wednesday, Thursday, Friday, and 

a separate weekend program routine for Saturday and 

Sunday.

•  Manual Non-Programmable: In this setting, there are 

no program routines for the thermostat to follow and 

the temperature control will be set only by the UP and 

DOWN buttons on the front panel.

ITEM #04 (PERD = EVENT OR PERIOD QUANTITY):

•  4P, default: Thermostat uses four Events per day 

(called MORN, DAY, EVE, and NITE).

•  2P: The thermostat uses two Events per day (called 

DAY and NITE).

NOTE: 

Event or Period Quantity feature is not accessible 

during Manual Non-Programmable mode.

ITEM #07 (DLAY = DELAY TIME): 

•  5, default: Thermostat waits 5 minutes before turning 

the system back on after it was last run. This internal 

delay prevents the appliance from turning on too 

quickly after shutting down. The 5 minute setting is fine 

for most applications. 

•  2: Same operation as above but reduced to 2 minutes 

between state changes. 

NOTE: 

There is no delay available when the thermostat is 

manually turned up and down.

f i r e - p a r t s . c o m

Содержание MT. VERNON E2 Series

Страница 1: ...sdiction about restrictions installation inspection and permits WARNING Please read this entire manual before use of this pellet fuel burning room heater Failure to follow these instructions could res...

Страница 2: ...urther instruction refer to owner s manual Keep viewing doors tightly closed during operation Keep viewing and ash removal doors tightly closed during operation Conforme la norme ASTM E1509 12 Std Cer...

Страница 3: ...F Filling the Hopper 11 G User Dial Control 11 H Normal Startup Sequence 11 I Fire Characteristics 11 J Fire pot Purge 12 K Ignition Cycles 12 L Restarting the Appliance 12 M Shutdown 12 N Clear Space...

Страница 4: ...mponents and glass X X X Factory installed blowers X Molded refractory panels X Ignition Modules X Firepots burnpots mechanical feeders auger assemblies X Vent Free burners Vent Free ceramic fiber log...

Страница 5: ...warranty call Travel and shipping charges for parts are not covered by this warranty Limited Catalyst Warranty o For wood burning products containing a catalyst the catalyst will be warranted for a si...

Страница 6: ...or weather damage which is the result of but not limited LIMITATIONS OF LIABILITY have other rights which vary from state to state EXCEPT TO THE EXTENT PROVIDED BY LAW HHT MAKES NO EXPRESS WARRANTIES...

Страница 7: ...it or after the unit has alarmed out due to an empty hopper Priming while under normal operating conditions will cause the fire pot to overfill HEAT SETTING HEAT SETTING O F F HI LO HEAT SETTING HEAT...

Страница 8: ...particulate emission standards at 0 74 G HR EPA CFR subpart AAA using ASTM E2779 10 ASTM 2515 11 Method Pellet Appliance sections CSA B415 1 10 Emissions Report Number 0061PS094E EPA Certification 98...

Страница 9: ...sleeping room it is recommended that 3ft of vertical be installed prior to horizontally exiting the room and a smoke CO alarm be installed in the bedroom The size of the room must be at least 50ft pe...

Страница 10: ...r to contend with small fires In the event of a hopper fire Evacuate the house immediately Notify fire department B Non Combustible Materials Material which will not ignite and burn composed of any co...

Страница 11: ...IMPORTANT DETAIL THE TIP OF THE THERMOCOUPLE MUST BE IN CONTACT WITH THE INSIDE END OF THE THERMOCOUPLE COVER OR MISSED IGNITIONS CAN OCCUR F Filling the Hopper Open the hopper lid by lifting the han...

Страница 12: ...The smoke will stop once the fire starts 2 The convection blower will automatically turn on after your appliance has been burning for approximately 10 minutes This blower transfers heat from your app...

Страница 13: ...ns approved by the regulatory authority having jurisdiction Figure 13 1 Trim adjustment is the small dial located below the main dial control The function of the trim adjustment is to allow for variat...

Страница 14: ...14 7080 163D August 3 2018 MT VERNON E2 C P Your Pellet Appliance s General Operating Parts Ash Dump Lever Baffle Latch Firepot Baffle Dial Control Hopper Switch fire parts com...

Страница 15: ...51 528 Amber Blinks Continuously Appliance is in the shutdown sequence During shut down the blowers will shut off when the exhaust temperature has cooled Red 1X Empty Hopper Alarm This alarm is cause...

Страница 16: ...em 01 and is advanced to each following item by a single press of the NEXT button The options for each item are changed using the UP or DOWN buttons ITEM 01 CLK CLOCK FORMAT 12Hr default This displays...

Страница 17: ...e temporarily changed set temperature will return to the programmed value stored in memory when start time of the next upcoming scheduled event is reached MORN DAY EVE OR NITE While the temporary chan...

Страница 18: ...house this feature can be used to synchronize this thermostat to the others Change the temperature calibration 1 Move TEMPERATURE switch to OFF 2 Move SET switch to RUN 3 Press and hold both UP and DO...

Страница 19: ...back half by using the tabs on the top edge of the thermostat housing Figure 19 1 Figure 19 1 Figure 19 2 Full battery icon Figure 19 3 Low battery icon When installing new batteries it is recommende...

Страница 20: ...wers is from the impellers becoming dirty over time See maintenance and service section for maintaining and servicing What is the metal object with the bend in it that came inside the plastic bag It i...

Страница 21: ...his pellet heater has a manufacturer set minimum low burn rate that must not be altered It is against federal regulations to alter this setting or otherwise operate this pellet heater in a manner inco...

Страница 22: ...ash Ash Disposal Ashes should be placed in a steel container with a tight fitting lid The container of ashes should be moved outdoors immediately and placed on a non combustible floor or on the ground...

Страница 23: ...affle also Inspect the drop tube and remove any residue build up in the drop tube Figure 23 3 c Assemble the crevice tool from the micro cleaning kit to attach to a Shop Vac Figure 23 4 d Use the crev...

Страница 24: ...ket between the glass and firebox should be inspected periodically to make sure there is a good seal If the gasket is frayed or damaged replace with a new one WARNING Risk of fire Do NOT store fuel Cl...

Страница 25: ...e a high temperature paint made specifically for heating appliances d Cleaning the flue at the end of the burn season will prevent corrosives to build up and damage the flue D Soot or Creosote Fire Aw...

Страница 26: ...e top of the latch up to lock latch into place G Glass Replacement 1 Swing open the face and remove the door from the appliance by lifting the door off of the hinge pins and lay on a flat surface face...

Страница 27: ...als to the new blower 10 Reposition and Re secure the back panel NOTE Make sure wires are connected prior to restarting the appliance Failure to do so will result in the side mounted safety thermal sn...

Страница 28: ...eck hopper switch wires for integrity Safety snap disc is tripped 3 Check to make sure convection blower wires are connected and reset snap disc located on RH side of appliance Clean inspect convectio...

Страница 29: ...probe to exhaust blower housing keeping its wire away from hot surfaces Control board is defective Replace control board Convection Blower fails to shut off Wire short between blower and ground Contro...

Страница 30: ...over the fire pot and or excessive flame Dirty Appliance Clean unit including the fire pot exhaust path and venting system Feed Motor locked on Follow corrective action for feed motor not turning off...

Страница 31: ...end to control board Failed component Replace exhaust probe securing it to exhaust blower housing keeping wire away from hot surfaces 4 Red Flashes Missed Ignition Hopper empty Fill the hopper Feed m...

Страница 32: ...designed to pull the exhaust from the appliance and push it out through the venting system 2 Control Board The control board is located on the right side of appliance It controls the functioning of t...

Страница 33: ...August 3 2018 7080 163D 33 MT VERNON E2 C Date of Service Performed By Description of Service B Service and Maintenance Log fire parts com...

Страница 34: ...34 7080 163D August 3 2018 MT VERNON E2 C C Exploded Drawings fire parts com...

Страница 35: ...August 3 2018 7080 163D 35 MT VERNON E2 C D Parts List fire parts com...

Страница 36: ...36 7080 163D August 3 2018 MT VERNON E2 C fire parts com...

Страница 37: ...August 3 2018 7080 163D 37 MT VERNON E2 C fire parts com...

Страница 38: ...38 7080 163D August 3 2018 MT VERNON E2 C fire parts com...

Страница 39: ...August 3 2018 7080 163D 39 MT VERNON E2 C fire parts com...

Страница 40: ...ed installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Dealership p...

Отзывы: