Isle Royale Wood Stove

R

February 4, 2005

250-5763B

Spark Arestor Cap

Roof Flashing

Storm Collar

Joist Shield/Firestop

Listed Chimney 

Connector

Floor Protector

Outside Air Kit Connector

Outside Air Floor Vent

1

.  An outside air inlet must be provided for combustion and must remain 

clear of leaves, debris, ice and/or snow. It must be unrestricted while 

stove is in use to prevent room air starvation which can cause smoke 

spillage and an inability to maintain a fire.  Smoke spillage can also 

set off smoke alarms.

2.  Stove must be secured to the mobile home structure.  Use 1/4 inch 

(6mm) lag bolts with the appropriate length for your installation to secure 

stove through pad and into floor.

3.  Stove  must  be  grounded  with  #8  solid  copper  grounding  wire 

or  equivalent  and  terminated  at  each  end  with  N.E.C.  approved 

grounding device.

4.  Stove  must  be  installed  with  an  approved  UL103  HT  ventilated 

chimney connector, UL103 HT chimney, and terminal cap with spark 

arrestor. Never use a single wall connector (stove pipe) in a mobile 

home installation.  Use only double-wall connector pipe, Dura-Vent 

DVL, Selkirk metalbestos DS, Security DL double wall connector or 

any listed double wall pipe connector.

5. 

Refer to page 6t

 of this manual or the Serial Number label on the 

back of the stove for clearances to combustibles.

6.  Floor  protections  requirements  on 

page  7

  must  be  followed 

precisely.

7.  In Canada, this appliance must be connected to a 6 inch (152mm) 

factory-built chimney conforming to CAN/ULC-629M, STANDARD 

FOR FACTORY BUILT CHIMNEYS. Floor protection referenced on 

page 7 

must be followed.

8.  Use  silicone  to  create  an  effective  vapor  barrier  at  the  location 

where the chimney or other component penetrates to the exterior 

of the structure.

9.  Follow the chimney and chimney connector manufacturer’s instructions 

when installing the flue system for use in a mobile home.

NOTE:

    Offsets  from  the  vertical,  not  exceeding  45°,  are  allowed  per 

Section  905(a)  of  the  Uniform  Mechanical  Code  (UMC).  Offsets 

greater  than  45°  are  considered  horizontal  and  are  also  allowed, 

providing  the  horizontal  run  does  not  exceed  75%  of  the  vertical 

height  of  the  vent.  Construction,  clearance  and  termination  must 

be  in  compliance  with  the  UMC Table  9C. This  installation  also 

complies with NFPA 211.

MOBILE HOME INSTALLATION

WARNING: NEVER DRAW COMBUSTION AIR 

FROM A WALL, FLOOR OR CEILING CAVITY 

OR FROM ANY ENCLOSED SPACE SUCH AS 

AN ATTIC OR GARAGE.

CAUTION:  THE  STRUCTURAL  INTEGRITY 

OF  THE  MOBILE  HOME  FLOOR,  WALL AND 

CEILING/ROOF  MUST  BE  MAINTAINED.  (i.e., 

DO NOT CUT THROUGH FLOOR JOIST, WALL 

STUD, CEILING TRUSS, ETC.)

WARNING: DO NOT INSTALL

 IN SLEEPING ROOM.

You must use a Quadra-Fire Outside Air Kit Part 831-1780 for installation in a mobile home.

NOTE:

 Top sections of chimney must be removable to allow maximum clearance of 13.5 ft. (411cm) from ground level for 

transportation purposes.

10.  Burn wood only.  Other types of fuels may generate poisonous gases (e.g., carbon monoxide).
11  If unit burns poorly while exhaust blower is on in home, (i.e. kitchen range hood) increase combustion air.

Содержание Isle Royale

Страница 1: ...YOUR WARRANTY 4 Cool ashes should be disposed of carefully using a metal container 5 Do not burn wet or green wood Store wood in a dry location 6 DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS SUCH AS GASOLI...

Страница 2: ...DE L INSTALLATION LE CONTACT PEUT CAUSER DES BR LURES LA PEAU GARDEZ LES MEUBLES ET LES MAT RIAUX COMBUSTIBLES LOIN DE L ESPACE D SIGN DE L APPAREIL VOIR L TIQUETTE ET LES INSTRUCTIONS ESPACES LIBRES...

Страница 3: ...Plated Surfaces 22 Brick replacement 23 Door gasket 23 Exploded view 24 Accessories Service Part 25 Service Maintenance Log 26 Warranty 27 Contact Information 28 TABLE OF CONTENTS PRE USE CHECK LIST...

Страница 4: ...ove to the chimney see page 10 It must be 6 inch 152mm minimum diameter 24 MSG black or blued steel or an approved air insulated double wall venting pipe THIMBLE A manufactured or site constructed dev...

Страница 5: ...x inch 6 152mm diameter listed double wall air insulated connector pipe with listed factory built UL103 HT Class A chimney or a masonry chimney Mobile Home must be equipped with a spark arrestor and t...

Страница 6: ...FIREPLACE OR THROUGH THE WALL Six inch 6 152mm diameter listed double wall air insulated connector pipe with UL 103HT listed factory built Class A chimney or a masonry chimney Mobile Home must be equi...

Страница 7: ...DA 203mm 8 203mm 8 203mm 8 457mm 18 1251mm 49 1 4 Minimum 1137mm 44 3 4 Minimum 16 from glass std legs 8 USA Fuel loading door 36 3 4 Minimum 39 1 4 Minimum 18 from glass hearth legs WHEN LOCATING YOU...

Страница 8: ...f temperature difference from one side of the material to the other The LOWER the k factor means less heat is being conducted through the non combustible material to the combustible material beneath i...

Страница 9: ...t the other two and thus change the amount of draft in the entire system A source of air oxygen is necessary in order for combustion to take place The combustion air enters the rebox below the ash cat...

Страница 10: ...ire Protection Association NFPA Standard 211 It must have at least a 5 8 inch 16mm re clay liner or a listed chimney liner system See Figure 10B Make sure there are no cracks loose mortar or other sig...

Страница 11: ...nd combustible wall and 2 the 1 inch 25mm air space around the chimney connector as it passes through the chimney section to the chimney The location of the opening through the wall to the chimney mus...

Страница 12: ...inst the chimney Install the trim collar on the outside of the opening Check to ensure there is a 1 inch 25mm air space between the connector and the chimney section During installation ensure that a...

Страница 13: ...should t tightly and be sealed with high temperature furnace cement unless the kit s instructions state otherwise Figure 13 The tight tting installation aids the proper draw of the chimney Figure 13A...

Страница 14: ...purchase but they demonstrate the basic components necessary for a proper and safe installation The chimney must be the required height above the roof or other obstruction for safety and for proper d...

Страница 15: ...cted to a 6 inch 152mm factory built chimney conforming to CAN ULC 629M STANDARD FOR FACTORY BUILT CHIMNEYS Floor protection referenced on page 7 must be followed 8 Use silicone to create an effective...

Страница 16: ...ion of the outside air kit rst NOTE If using Hearth Legs you can install an Outside Air Kit or Blower but not both 1 Remove 3 Phillips head screws from rear of unit 2 Using the Phillips head screws at...

Страница 17: ...d and not allowed to go out This will ensure the cleanest possible re If you are adjusting your stove for a low burn rate you should close down the air to the point where you can still maintain some a...

Страница 18: ...ate settings and will vary with type of wood or chimney draft Due to altitude and other environmental circumstances this operation infor mation is a guideline only Similar burn rates may be obtained u...

Страница 19: ...s 3 inches 76mm or 4 inches 102mm in diameter Be careful not to smother the re Stack the pieces of wood carefully near enough to keep each other hot but far enough away from each other to allow adequa...

Страница 20: ...e blower off until your stove is hot and a good coalbed is established The blower may be turned on approximately 30 minutes after a good coalbed is established 2 High burn setting The blower may be le...

Страница 21: ...steps to ensure that the accumulation of ash and creosote falls directly into the rebox for removal MAINTENANCE ASH REMOVAL DISPOSAL The stove is equipped with an ash removal system We recommend empt...

Страница 22: ...ss This air ow washes the glass helping to keep smoke from adher ing to its surface When operated at a low burn rate less air will be owing over the glass and the smokey relatively cool condition of a...

Страница 23: ...is available from your dealer MAINTENANCE Ensure that the rebricks are correctly positioned as referenced by diagram below and that the rebox does not contain any broken brick prior to operating the u...

Страница 24: ...sembly 13 Griddle Handle 23 Rear Shield 4 Brick Assembly 14 Hopper Lid Stop 24 Side Tertiary Channel Right 5 Door Assembly 15 Manifold Tube 4 25 Side Left 6 Face Assembly 16 Primary Air Channel 26 Sid...

Страница 25: ...Tube Set 4 832 3360 Accessories Serial No Part No Blower 831 1701 Brackets with Mitten Rod Gold WSB2G 2 844 7980 Brackets with Mitten Rod Black WSB2 2 844 7970 Firescreen USA installations only 834 3...

Страница 26: ...R Page 26 February 4 2005 Isle Royale Wood Stove 250 5763B Date of Service Performed By Description of Service Service and Maintenance Log...

Страница 27: ...ears for optional accessories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items...

Страница 28: ...0481 6237588 6296474 6374822 6413079 6439226 6484712 6543698 6550687 6601579 6672860 6688302B2 6715724B2 6729551 6736133 6748940 6748942 D320652 D445174 D462436 Canada 1297749 2195264 2225408 or other...

Отзывы: