April 9, 2009
7051-158
Page 7
EDGE 60 Pellet Fireplace
8
Vent Information
A. Venting Termination Minimum Requirements
NOTICE:
Termination must exhaust above air inlet elevation.
• It is recommended that at least 60 inches (154mm) of
vertical pipe be installed when appliance is vented directly
through a wall. This will create a natural draft, which will
help prevent the possibility of smoke or odor venting into
the home during a power outage.
• It will also keep exhaust from causing a nuisance or hazard
by exposing people or shrubs to high temperatures.
• The safest and preferred venting method is to extend the
vent vertically through the roof or above the roof.
J or K
X
V
M
I
H
A
V
G
B
V
V
A
B
V
F V
C
B
B
E
L
V
D
V
Electrical
Service
V
N
V
N
V
N
N
V
Inside Corner
FIXED
CLOSED
OPEN
OPEN
FIXED
CLOSED
V
X
G
G
Termination Cap
Air Supply Inlet
Gas Meter
Restricted Area
O
P
Figure 37.1
A
1 in.
Above Finish Grade (the grade surface
must be a non-combustible material
B
1 in.
Open door or window: below or to the side
B
1 in.
Open door or window: above
C
6 in.
Permanently closed window: above, below
or to the side
D
18 in.
Vertical clearance to a ventilated soffit
located above the terminal within a hori
-
zontal distance of ft from the center-line
of the terminal
E
1 in.
Clearance to unventilated soffit
F
1 in.
Clearance to outside corner
G
1 in.
Clearance to inside corner
H
6 in.
Above gas meter/regulator measured from
horizontal center-line of regulator
I
6 in. USA
7 in. Canada
Clearance to service regulator vent outlet
J
1 in.
Clearance to non-mechanical air supply
inlet to the building or the combustion air
inlet to any other appliance
K
10 ft horizontal
ft vertical
Clearance to mechanical air supply
L
7 ft.
Above paved sidewalk, paved driveway
located on
public
property
M
1 in.
Under an open veranda, porch, deck or
balcony
N
See Note
below*
Electric service: above, below or to the
side (location must not obstruct or interfere
with access)
O
4 in.
Adjacent building, fences and protruding
parts of the structure
P
1 in.
Clearance above roof line for vertical
terminations
An Outside Air Kit is required on all installations.
Outside Air Kit must be ordered separately.
4 in.
Above grass, top of plants, wood or any other com
-
bustible
1 in.
Clearance from any forced air intake of other appli
-
ance
1 in.
Clearance horizontally from combustible wall
15 in.
Vented directly through a wall, minimum length of
horizontal pipe
1 in. horizontal
1 in. vertical
Minimum horizontal or vertical terminations must
protrude from wall
*NOTE:
Consult local building, fire officials or authorities having
jurisdiction. Local codes or regulations may require different
clearances.
NOTICE:
Do NOT Terminate Vent:
•
In any location that will allow flue gases or soot to enter
or stain the building.
•
In any location which could create a nuisance or hazard.
•
In any enclosed or semi-enclosed area such as a carport,
garage, attic, crawl space, under a sun deck or porch,
narrow walkway.
• Closely fenced area, or any location that can build up
a concentration of fumes such as a stairwell, covered
breezeway, etc.