250-3692 (11/2000)  DVi32 Gas Insert

THERMOSTAT INSTALLATION

If desired, a thermostat may be installed to regulate the Quadra-Fire DVI-32. It is important to use a thermostat designed for
millivolt operation. Do not connect this appliance to a thermostat serving any other appliance.

Connect the thermostat wires to the outer two screw terminals on the gas control valve, located behind the left side fascia access
panel. Turn off the manual switch located behind the right side fascia access panel.

REMOTE CONTROL

A remote control or a wall switch may be wired to the thermostat terminals. Contact your Quadra-Fire dealer or service person
for details (see page 19 for part number).

BLOWER POWER CORD

The blower cord is located at the rear of the stove, and needs to be routed to a three-prong outlet with correct
polarity. Be sure that the stove is electrically grounded in accordance with local codes, with a current version of CSA
C22 (in Canada), or in the absence of local codes, with the National Electric Code ANSI/NFPA 70-1987.

OPTIONAL THERMOSTATS

Manual Thermostat
Part #812-2880
Anticipator Setting 1.2

Electronic Setback
Part #811-0520

RECOMMENDED MAXIMUM LEAD
LENGTH (TWO WIRE) WHEN USING
WALL THERMOSTAT/SWITCH

Wire Size

Maximum Length

16 gauge

65’ (19.8m)

18 gauge

40’ (12.2m)

20 gauge

25’ (7.6m)

22 gauge

18’ (5.5m)

WARNING

Do not cut the grounding terminal off under any circumstances.

Do not route the power cord under the body of the appliance due to high temperatures.

INSTALLATION PROCEDURES

The following procedures show some of the basic installation applications.  Remember that every installation is
different, and the installer should adjust to insure that the appliance is installed properly.

FRONT BRICK SHUTOFF PLATE ADJUSTMENT

The front brick shuttoff plate controls the secondary air supply to the burner tube. For NG stoves, it should be slid
all the way against the burner tube. For LP stoves, the front brick shutoff plate should be slid all the way to the front
of the stove.

GAS CONNECTIONS

Before hooking up the stove to the gas supply, be sure that the appliance you are installing is designed for the type
of gas being supplied to it. There is a serial number and listing label behind  the gas supply access door behind the
left side fascia that will indicate which type of gas it is designed to utilize. The gas valve also has a label telling the
type of fuel for which it is set up.

There is a 3/8” gas hookup located behind the left side fascia access panel, at the valve. We recommend connecting
the stove with an approved flex gas line, as shown below. If flex gas lines are not approved in your area, you can
connect a hard pipe to the gas hookup. Be sure to comply with all local codes.

FLEX LINE

GAS CONNECTION

FRONT

f i r e - p a r t s . c o m

Содержание DVI-32

Страница 1: ...epartment Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Improper installation adjustment alteration service or maintenance can cause injury or property damage Refer to this manual for correct installation and operational procedures For assistance or additional information consult a qualified installer service agency or the gas suppli...

Страница 2: ...rocedures 9 Front brick shutoff plate adjustment 9 Gas connections 9 Venting instructions 10 Installation precautions 10 Safety precautions 10 Venting parts list 11 Venting system maintenance 11 Planning your installation 12 Vertical terminations Using GS series pipe 12 Installing into an existing masonry or factory built metal chimney 15 Lighting instructions 17 First fire 18 Maintenance Cleaning...

Страница 3: ...N 1 149 This vented gas fireplace is not for use with air filters Install and use only in accordance with manufactaurer s installation and operating instructions Not for use with solid fuel Keep burner and control compartment clean See installation and operating instructions accom panying this appliance Due to high surface temperatures keep children clothing and furniture away ELECTRICAL SUPPLY 12...

Страница 4: ...le materials gasoline and other flammable vapors and liquids This appliance is hot during operation and should be located out of heavy traffic areas and away from furniture and draperies Clothing or other flammable material should not be placed on or near the appliance Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns or clothing ...

Страница 5: ... A REGULATOR UPSTREAM FROM THE APPLIANCE IF LINE PRESSURE IS GREATER THAN 1 2 PSIG OUTPUT SIDE TEST PRESSURE INPUT SIDE TEST PRESSURE PRESSURE TESTING If the gas supply piping system exceeds pressures of 1 2 PSIG during testing this appliance and its individual shutoff valve must be disconnected from the piping system If test pressure is less than or equal to 1 2 PSIG then this appliance must be i...

Страница 6: ...6 250 3692 11 2000 DVi32 Gas Insert DIMENSIONS 7 1 2 190mm 23 15 16 680mm 12 305mm 29 737mm 30 762mm 30 762mm 14 1 2 368mm 13 13 16 351mm 10 9 16 268mm 11 16 18mm fire parts com ...

Страница 7: ...000 over the 2000 level Exception As permitted by the authority having jurisdiction LISTINGS The Quadra Fire DVI 32 is listed to ANSI Z21 88a 1998 CSA 22 33a M98 and CAN1 2 17 M91NFPA 70 by OMNI Test Laboratories Inc Beaverton Oregon CLEARANCES TO COMBUSTIBLES Minimum clearances to combustible materials from stove body A Side wall to combustibles 9 229mm B Height of combustible above bottom of ins...

Страница 8: ...Place nuggets in a single layer across the burner tube Make sure that nuggets do not fall behind the tube If more than one layer of nuggets is placed across the burner tube flame impingement and tall sooty flames can result If the flames on one side are too high adjust the nuggets until the flame is the same height on both sides of the stove The log set is installed at the factory To remove log se...

Страница 9: ... 2m 20 gauge 25 7 6m 22 gauge 18 5 5m WARNING Do not cut the grounding terminal off under any circumstances Do not route the power cord under the body of the appliance due to high temperatures INSTALLATION PROCEDURES The following procedures show some of the basic installation applications Remember that every installation is different and the installer should adjust to insure that the appliance is...

Страница 10: ...ing system installation of any component part not approved by Aladdin Hearth Products or installation other than as instructed by these instructions Consult your local building codes before beginning this installation WARNING Always maintain the required clearances air space to nearby combustibles to avoid creating a fire hazard Do not fill air space with insulation Minimum clearance between vent ...

Страница 11: ... 12 12 roof itch 945 45 elbow two maximum 953 Storm collar 963 Ceiling firestop 988 Wall strap 991 High wind termination cap 2280 3 76mm chimney flex liner 923GCL Co linear to co axial adaptor VENTING SYSTEM MAINTENANCE Conduct an inspection of the venting system semiannually Recommended areas to inspect are as follows 1 Check areas of the venting system which are exposed to the elements for corro...

Страница 12: ...ero clearance chimney it is important to carefully measure the length of flex needed to reach from the appliance outlet to the termination cap If the flex length is too short a flex coupler will be needed to attach an additional length of flex liner to make up the difference If the flex length is too long the liner could sag below the appliance outlet which could result in a potential fire hazard ...

Страница 13: ...tep 4 Assemble the desired lengths of black pipe and elbows necessary to reach from the appliance up through the round support box Insure that all pipe and elbow connections are in their fully twist locked position Step 5 Cut a hole in the roof centered on the small drill hole placed in the roof in step 2 The hole should be of sufficient size to meet the minimum requirements for clearance to combu...

Страница 14: ...roofing nails Insure the roofing material overlaps the top edge of the flashing Figure 4 Verify that you have at least the minimum clearance to combustibles at the roofline Step 7 Continue to assemble pipe sections and seal with silicone until the height of the vent cap H Figure 5 meets the minimum building code requirements described in Table 1 Figure 5 and outlined in the current CANGA Bl49 Inst...

Страница 15: ...rope through the end of the flex puller and tie a knot at the end of the rope Attach the flex puller to the flex liner using four sheet metal screws Be sure to label one liner exhaust and other intake Carefully feed the liner down the chimney and out through the damper NOTE If additional lengths of flex liner are needed to span the chimney height use a flex coupler to connect the pieces of flex li...

Страница 16: ...ap SDV part 991 to the top adaptor see Figure 9 Do not use any other termination cap Step 9 Attach the flex lines to the appliance using hose clamps provided FIG 7 FIG 8 FIG 9 We strongly recommend the use of two flex liners to properly install the DVi 32 NOTE THE FOLLOWING INSTALLATION IS APPROVED FOR APPLICATIONS IN THE UNITED STATES ONLY IT IS NOT APPROVED FOR INSTALLATIONS IN CANADA The DVI 32...

Страница 17: ...the left hand side fascia access door to expose the gas control 5 Push in gas control knob slightly and turn clockwise to OFF NOTE Knob cannot be turned from PILOT to OFF unless knob is pushed in slightly Do not force 6 Wait five 5 minutes to clear out any gas Smell for gas including near the floor If you smell gas STOP Follow B of the safety information above If you don t smell gas go to the next...

Страница 18: ...an odor and steam coming from the insert This is normal it is the high temperature paint finishing the curing process Open the door and or windows in the home or structure for ventilation We recommend that you cycle the insert to heat for several minutes until it reaches the curing stage and then turn to off to cool for five minutes Then turn the insert back on and burn until the steam and or odor...

Страница 19: ...ing of the stove and it should be checked 4 Check the thermostat and thermopile connections at the valve and tighten or reconnect if needed 5 If the burner still will not ignite you may have a bad valve call your dealer or authorized service person Check the pilot and burner flames periodically When properly adjusted they should look like the flames in the illustration below Call your dealer or au...

Страница 20: ...ch as but not limited to blowers wiring thermodisc switches and gas valves are covered by Aladdin s one year warranty program Aladdin Hearth Products will not be responsible for any alteration to the unit which causes sooting that results in damage to the interior of the building in which this appliance is installed This warranty is void if the stove has been operated in atmospheres contaminated b...

Отзывы: