F. Equivalent Feet of Pipe

The table below can help you calculate the equivalent feet 

of pipe which is a method used to determine pellet vent 

size 

(Figure 16.1)

.

Figure 16.2

3 in. or 4 in. (76mm or 

102mm)  Diameter   Pipe 

3 in. or 4 in. (76mm or 

102mm)  Diameter   Pipe 

Equivalent Pipe 

Length In Feet

Equivalent Pipe 

Length In Feet

ALTITUDE IN THOUSANDS OF FEET

ALTITUDE IN THOUSANDS OF FEET

0

20

30

   

1        2       3       4       5       6        7       8        9     10

4 in. (102mm) Diameter Pipe Only

4 in. (102mm) Diameter Pipe Only

10

Example 1

Example 1

Example 2

Example 2

Example 1

: If the equivalent length of pipe is 23 feet (7m) 

with altitude of 8,000 feet (2438m) you must use 

4 inch (102mm) diameter type “L” or “PL” vent.

Example 2

: If the equivalent length of pipe is 12 feet (3.7m) 

with altitude of 6,000 feet (1829m) you may use 

3 or 4 inch (76 to 102mm) diameter type “L” or 

“PL” vent.

G. Pipe Selection Chart

The chart will help you in determining proper venting 

size according to the equivalent feet of pipe calculated 

previously and the altitude above sea level of this 

installation 

(Figure 16.2)

.

1. 

Locate the calculated equivalent feet of pipe on the 

vertical left side of the chart.

2.  Move to the right horizontally on the chart until you 

reach your altitude above sea level.

3. 

If you fall below the diagonal line, 3 or 4 inch (76 to 

102mm) pipe may be used.  

4.  If it is anywhere above the diagonal line, a 4 inch 

(102mm) diameter pipe is required.

Example of 3 Elbow-Rear Vent Termination Calculation

Vent surfaces get HOT, can cause burns 

if touched. Non-combustible shielding or 

guards may be required.

WARNING

2 ft. 

2 ft. 

3 ft. 

2 ft. 

Pellet 

Venting 

Component

# of 

Elbows

Feet 

of 

Pipe

Multiplied 

By

Equivalent 

Feet

Components

Equivalent 

Feet

90° Elbow or 

Tee

3

X

5

15

45° Elbow

X

3

Horizontal 

Pipe

7

X

1

7

Vertical Pipe

2

X

0.5

1

Total Equivalent Feet

23

NOTE:

 This is a generic example and is not intended to represent any specific 

fuel type.

Figure 16.1

NOTICE:

• 

A 90° elbow is 5 times as restrictive to the flow of 

exhaust gases under positive pressure as 1 foot 

(305mm) of horizontal pipe.

•  A foot of horizontal pipe is twice as restrictive as a 

foot of vertical pipe.

Risk of Injury or Property Damage.

•  Improper installation, adjustment, alteration, 

service or maintenance can cause injury or 

property damage.

• 

Refer to the owner’s information manual 

provided with this appliance.

• 

For assistance or additional information 

consult a qualified installer, service agency 

or your dealer.

WARNING

Risk of Fire!

• 

Only LISTED venting components may be 

used.

• 

NO OTHER vent components may be 

used.

•  Substitute or damaged vent components 

may impair safe operation.

WARNING

Содержание CASTILE-MBK-C

Страница 1: ...not followed exactly a fire could result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other applia...

Страница 2: ...mostat Wall Control Location 6 C Tools And Supplies Needed 6 D Inspect Appliance and Components 6 E Install Checklist 7 3 Dimensions and Clearances 8 A Appliance Dimensions 8 B Clearances to Combustib...

Страница 3: ...proper operation It is against federal regulations to operate this pellet appliance in a manner inconsistent with operating instructions in this manual Emissions Report Number 0061PM077E EPA Certific...

Страница 4: ...on of such fuels can expose you to chemicals including carbon black which is known to the State of California to cause cancer and carbon monoxide which is known to the State of California to cause bir...

Страница 5: ...ior to installation Installation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisd...

Страница 6: ...lation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements C Tools And Supplies Needed Tools and building supplies normally requi...

Страница 7: ...tion and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the ap...

Страница 8: ...ure 8 1 Top View Figure 8 2 Top View with TPVNT 2 and 812 3570 Figure 8 4 Top view with TPVNT 2 and 811 0720 11 7 8 in 302mm 11 7 8 in 302mm 5 3 4 in 146mm 3 1 2 in 89mm 5 in 127mm 11 7 8 in 297mm 3 i...

Страница 9: ...de View Figure 9 4 Side View with TPVNT 2 and 811 0720 28 1 2 in 724mm 24 in 610mm 23 5 8 in 600mm 15 1 2 in 394mm 9 1 2 in 241mm 28 5 8 in 727mm 27 in 686mm 24 1 2 in 622mm 22 7 8 in 581mm 22 7 8 in...

Страница 10: ...vidual design preference C C A B D E F G G H H Horizontal Through the Wall Inches Millimeters A Back Wall to Appliance 2 51 B Side Wall to Appliance 6 152 Corner Installation Inches Millimeters C Wall...

Страница 11: ...de of pipe shaded area to the wall thimble 152MM USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when installed with horizontal venting or under the...

Страница 12: ...ight 43 1092 n a n a B Width 38 965 n a n a C Depth n a n a 36 914 D To Side Wall 6 152 n a n a All minimums listed are to a combustible surface NOTE Illustrations reflect typical installations and ar...

Страница 13: ...nd protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table...

Страница 14: ...t of the demands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appliance It may be necessary to add additional venti...

Страница 15: ...through the chimney Install through the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Considerations for successf...

Страница 16: ...until you reach your altitude above sea level 3 If you fall below the diagonal line 3 or 4 inch 76 to 102mm pipe may be used 4 If it is anywhere above the diagonal line a 4 inch 102mm diameter pipe i...

Страница 17: ...ed for mobile home installations Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage t...

Страница 18: ...ean out Cover 24 in 610mm Minimum Ceiling Support 6 in 152mm Flue Connector 6 in 152mm Class A Chimney Connector Adapter 3 in to 6 in 76 152mm Top Vent Kit B Vertical into Existing Class A Chimney We...

Страница 19: ...ace Concrete Cap 1 in 25mm clearance with firestop 6 in 152mm minimum Non combustible Hearth Pad Airtight clean out door Sheathing 2 in 51mm minimum Flashing 1 in 25mm clearance 1 in 25mm clearance wi...

Страница 20: ...h slots in convection blower mount and ash box Figure 20 2 Push up and slide forward CAUTION Never draw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or gara...

Страница 21: ...exhaust outlet Do not put silicone inside of pipe Figure 21 1 2 Slide the adapter onto the rear exhaust outlet and adjust the assembly to the appropriate position 3 Install the vent pipe into the ada...

Страница 22: ...t for drywall or a 7 32 drill bit for plaster drill holes 3 Using a hammer tap in wall anchors 4 Route the wires through the opening in the base plate and hold the base against the wall while aligning...

Страница 23: ...E Due to the abrasive nature of a pellet appliance fire the logs are not covered under warranty Any placement variation other than shown here can cause excessive heat and shall void the appliance warr...

Страница 24: ...24 PART NUMBER 811 0872 Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 CAUTION THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEI...

Страница 25: ...25 April 23 2019 7021 801B CASTILE FREESTANDING 8 Reference Materials A Service and Maintenance Log Date of Service Performed By Description of Service...

Страница 26: ...26 April 23 2019 7021 801B CASTILE FREESTANDING Date of Service Performed By Description of Service...

Страница 27: ...7050 144 Log Right Rear 7050 143 Collar Offset Top Vent 812 3570 Damper 3 Inch Tall Vertical Installs Only PEL DAMP3 Y Damper 4 Inch Tall Vertical Installs Only PEL DAMP4 Outside Air Kit Rear 811 0872...

Страница 28: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Отзывы: