background image

15

April 23, 2019

7021-801B

CASTILE FREESTANDING

C. Negative Pressure

NOTE

: The appliance exhaust outlet is designed to 

accommodate 3 inch venting. Use of 4 inch 

venting requires the use of a 3-to-4 inch exhaust 

vent increaser in addition to any other venting 

components needed, sold separately.

Negative pressure results from the imbalance of air 

available for the appliance to operate properly. It can be 

strongest in lower levels of the house.

Causes include:

• 

Exhaust fans (kitchen, bath, etc.)

•  Range hoods

•  Combustion air requirements for furnaces, water 

appliances and other combustion appliances

•  Clothes dryers

• 

Location of return-air vents to furnace or air 

conditioning

•  Imbalances of the HVAC air handling system

•  Upper level air leaks such as: 

 

-

Recessed lighting

 

-

Attic hatch

 

-

Duct leaks

To minimize the effects of negative air pressure:

•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

•  Ensure adequate outdoor air for all combustion 

appliances and exhaust equipment

•  Ensure furnace and air conditioning return vents are 

not located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

• 

Recessed lighting should be a “sealed can” design

•  Attic hatches weather stripped or sealed

•  Attic mounted duct work and air handler joints and 

seams taped or sealed

E. Chimney and Exhaust Connection 

1.  Chimney & Connector:

 Use 3 or 4 inch (76-102mm) 

diameter type “L” or “PL” venting system. It can be 

vented vertically or horizontally.

D. Draft

Draft is the pressure difference needed to vent an 

appliance successfully. When an appliance is drafting 

successfully, all combustion byproducts are exiting the 

home through the chimney.

Install through the warm airspace enclosed by the building 

envelope. This helps to produce more draft, especially 

during lighting and die-down of the fire.

Considerations for successful draft include:

• 

Preventing negative pressure

• 

Location of appliance and chimney

NOTE: 

All pipe must be welded seam pipe whenever 

possible. Seal pipe joints with high temperature 

silicone (500°F [260°C] minimum rated only).

WARNING

USE ONLY RECOMMENDED VENTING 

COMPONENTS; OTHERWISE MAKESHIFT PARTS MAY 

RESULT IN PROPERTY DAMAGE, PERSONAL INJURY, 

OR DEATH. 

NOTICE:

 Hearth & Home Technologies assumes no 

responsibility for the improper performance of 

the chimney system caused by:

•  Inadequate draft due to environmental conditions

•  Down drafts

•  Tight sealing construction of the structure

•  Mechanical exhausting devices

2.  Mobile Home:

 Approved for all Listed pellet vent. If 

using the 3 inch (76mm) vertical Top Vent Adapter Kit 

or the 3 to 6 inch (76-152mm) Top Vent Offset Adapter, 

use Listed double wall flue connector. A Quadra-Fire 

Outside Air Kit must be used with manufactured home 

installations.

3.  Residential:

 The 3 inch (76mm) vertical Top Vent 

Adapter Kit and the 3 to 6 inch (76 to 152mm) Top Vent 

Offset Adapter are tested to use 24 gauge single wall 

flue connector or Listed double wall flue connector to 

Class A Listed metal chimneys, or masonry chimneys 

meeting International Residential Code standards for 

solid fuel appliances.

4. 

Install vent at clearances specified by the vent 

manufacturer.

5. 

Secure exhaust venting system to the appliance with 

at least 3 screws. Also secure all connector pipe joints 

with at least 3 screws through each joint.

6.  DO NOT INSTALL A FLUE DAMPER IN THE 

EXHAUST VENTING SYSTEM OF THIS Appliance.

7. 

DO NOT CONNECT THIS Appliance TO A CHIMNEY 

FLUE SERVING ANOTHER APPLIANCE.

WARNING

Risk of Asphyxiation!

 

Negative pressure can cause spillage of combustion 

fumes and soot.

Содержание CASTILE-MBK-C

Страница 1: ...not followed exactly a fire could result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other applia...

Страница 2: ...mostat Wall Control Location 6 C Tools And Supplies Needed 6 D Inspect Appliance and Components 6 E Install Checklist 7 3 Dimensions and Clearances 8 A Appliance Dimensions 8 B Clearances to Combustib...

Страница 3: ...proper operation It is against federal regulations to operate this pellet appliance in a manner inconsistent with operating instructions in this manual Emissions Report Number 0061PM077E EPA Certific...

Страница 4: ...on of such fuels can expose you to chemicals including carbon black which is known to the State of California to cause cancer and carbon monoxide which is known to the State of California to cause bir...

Страница 5: ...ior to installation Installation MUST comply with local regional state and national codes and regulations Consult insurance carrier local building inspector fire officials or authorities having jurisd...

Страница 6: ...lation to ensure maximum safety and benefit Follow pipe manufacturer instructions for installation and air clearance requirements C Tools And Supplies Needed Tools and building supplies normally requi...

Страница 7: ...tion and copying this checklist for your file That this checklist remain visible at all times on the appliance until the installation is complete Electrical 120 VAC unswitched power provided to the ap...

Страница 8: ...ure 8 1 Top View Figure 8 2 Top View with TPVNT 2 and 812 3570 Figure 8 4 Top view with TPVNT 2 and 811 0720 11 7 8 in 302mm 11 7 8 in 302mm 5 3 4 in 146mm 3 1 2 in 89mm 5 in 127mm 11 7 8 in 297mm 3 i...

Страница 9: ...de View Figure 9 4 Side View with TPVNT 2 and 811 0720 28 1 2 in 724mm 24 in 610mm 23 5 8 in 600mm 15 1 2 in 394mm 9 1 2 in 241mm 28 5 8 in 727mm 27 in 686mm 24 1 2 in 622mm 22 7 8 in 581mm 22 7 8 in...

Страница 10: ...vidual design preference C C A B D E F G G H H Horizontal Through the Wall Inches Millimeters A Back Wall to Appliance 2 51 B Side Wall to Appliance 6 152 Corner Installation Inches Millimeters C Wall...

Страница 11: ...de of pipe shaded area to the wall thimble 152MM USA INSTALLATIONS A non combustible floor protection is recommended extending beneath the flue pipe when installed with horizontal venting or under the...

Страница 12: ...ight 43 1092 n a n a B Width 38 965 n a n a C Depth n a n a 36 914 D To Side Wall 6 152 n a n a All minimums listed are to a combustible surface NOTE Illustrations reflect typical installations and ar...

Страница 13: ...nd protruding parts of the structure P 12 in Clearance above roof line for vertical terminations All minimum clearances are listed with an Outside Air Kit OAK installed unless otherwise noted in table...

Страница 14: ...t of the demands of the pellet appliance but consideration must be given to the total house demand House demand may consume the air needed for the appliance It may be necessary to add additional venti...

Страница 15: ...through the chimney Install through the warm airspace enclosed by the building envelope This helps to produce more draft especially during lighting and die down of the fire Considerations for successf...

Страница 16: ...until you reach your altitude above sea level 3 If you fall below the diagonal line 3 or 4 inch 76 to 102mm pipe may be used 4 If it is anywhere above the diagonal line a 4 inch 102mm diameter pipe i...

Страница 17: ...ed for mobile home installations Must use 3 or 4 inch 76 102mm L or PL Listed pellet venting or Listed double wall pipe and a Quadra Fire Outside Air Kit in mobile homes NOTE In Canada where passage t...

Страница 18: ...ean out Cover 24 in 610mm Minimum Ceiling Support 6 in 152mm Flue Connector 6 in 152mm Class A Chimney Connector Adapter 3 in to 6 in 76 152mm Top Vent Kit B Vertical into Existing Class A Chimney We...

Страница 19: ...ace Concrete Cap 1 in 25mm clearance with firestop 6 in 152mm minimum Non combustible Hearth Pad Airtight clean out door Sheathing 2 in 51mm minimum Flashing 1 in 25mm clearance 1 in 25mm clearance wi...

Страница 20: ...h slots in convection blower mount and ash box Figure 20 2 Push up and slide forward CAUTION Never draw outside combustion air from Wall floor or ceiling cavity Enclosed space such as an attic or gara...

Страница 21: ...exhaust outlet Do not put silicone inside of pipe Figure 21 1 2 Slide the adapter onto the rear exhaust outlet and adjust the assembly to the appropriate position 3 Install the vent pipe into the ada...

Страница 22: ...t for drywall or a 7 32 drill bit for plaster drill holes 3 Using a hammer tap in wall anchors 4 Route the wires through the opening in the base plate and hold the base against the wall while aligning...

Страница 23: ...E Due to the abrasive nature of a pellet appliance fire the logs are not covered under warranty Any placement variation other than shown here can cause excessive heat and shall void the appliance warr...

Страница 24: ...24 PART NUMBER 811 0872 Spark Arestor Cap Roof Flashing Storm Collar Joist Shield Firestop Double Wall Connector Pipe Figure 24 1 CAUTION THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEI...

Страница 25: ...25 April 23 2019 7021 801B CASTILE FREESTANDING 8 Reference Materials A Service and Maintenance Log Date of Service Performed By Description of Service...

Страница 26: ...26 April 23 2019 7021 801B CASTILE FREESTANDING Date of Service Performed By Description of Service...

Страница 27: ...7050 144 Log Right Rear 7050 143 Collar Offset Top Vent 812 3570 Damper 3 Inch Tall Vertical Installs Only PEL DAMP3 Y Damper 4 Inch Tall Vertical Installs Only PEL DAMP4 Outside Air Kit Rear 811 0872...

Страница 28: ...purchased installed _________________________________________________________________________ Serial Number ____________________________________ Location on appliance ___________________________ Deal...

Отзывы: