Page 6
7038-201D
October 12, 2015
5700 Step Top ACC Wood Burner
OPERATING INSTRUCTIONS
Air Controls
1. Start-Up Air Control
The Start-Up Air Control has two primary functions. The
fi
rst function is to activate the Automatic Combustion Control
system (ACC). This function is performed by sliding the con-
trol all the way back until it stops at the “HI” indicator on the
label and then pulling forward to the front of the stove until
it stops. This activates the ACC system and opens the front
air channel and allows air to enter the front of the stove for
approximately 25 minutes. The front air channel gradually
shuts down until it is completely closed at the end of the 25
minutes. The
fi
re is now controlled by the air supplied by the
Burn Rate Air Control. This function should be performed
each time you reload the stove.
Figure 6.1.
2. Burn Rate Air Control
This air supply enters at the upper front of the
fi
rebox, near
the top of the glass door. This preheated air supplies the
necessary fresh oxygen to mix with the unburned gases,
helping to create second, third and fourth combustions. This
air is regulated by the Burn Rate Air Control. There are four
settings High, Medium-High, Medium-Low and Low. When
the control is raised all the way up it is on the High setting and
when pushed all the down it is on the Low setting.
Figure 6.1.
HIGH
MED
LOW
Burn Rate
Air Control
Start-Up
Air Control
Figure 6.1
Burn Rates
1. Starting a Fire and Reloading
Open both controls fully by raising the Burn Rate Air Control
all the way up until it stops and slide the Start-Up Air Control
back until it stops. After loading the stove with wood and
starting the
fi
re, set both controls to the desired setting by
following the burn rate instructions below.
2. High Burn Rate - Maximum Heat
Raise the Burn Rate Air Control all the way up until it stops
(top marker) to a fully open position. Slide the Start-Up Air
Control all the way back until it stops (HI marker) and leave it
there. This setting over-rides the timer system (ACC) so you
must monitor the
fi
re closely while in this setting.
3. Medium-High Burn Rate
Raise the Burn Rate Air Control all the way up until it stops
(top marker) to a fully open position. Slide the Start-Up Air
Control all the way back until it stops (HI marker) and then pull
forward until it stops. This activates the timer system (ACC).
4. Medium-Low Burn Rate
Raise the Burn Rate Air Control up to the bottom of the middle
marker and stop. Slide the Start-Up Air Control all the way
back until it stops (HI marker) and then pull forward until it
stops. This activates the timer system (ACC).
5. Low Burn Rate
Leave the Burn Rate Air Control at the bottom marker. Slide
the Start-Up Air Control all the way back until it stops (HI
marker) and then pull forward until it stops. This activates
the timer system (ACC).
High (Open)
Low (Closed)
Start-Up Air
Control
Burn Rate
Air Control
Front Air Channel
Operated by Timer
Rear Air Channel
Operates independently
from Timer
Timer
Timer Manual
Shut-off
HIGH
LOW
Shown with Side
Shield Removed