Installation Manual 

3. Product Installation 

18 

 

www.qtech.ru 

 

 

The related network cables have already been deployed at the installation location.  

3.3

 

Cabinet Installation 

Precautions 

When you install the cabinet, pay attention to the following requirements: 

 

All  expansion  bolts  for  fastening  the  cabinet  base  to  the  ground  should  be  installed  and 
tightened in sequence from bottom up (large plain washer, spring washer, and nut), and the 
installation holes on the base and the expansion bolts should be well aligned. 

 

After the cabinet is installed, it should be stable and still. 

 

After the cabinet is installed, it should be vertical to the ground. 

 

When  multiple  cabinets  are  placed  side  by  side  in  the  room,  they  should  be  aligned  in  a 
straight line, with an error less than 5 mm. 

 

The front/back doors of the cabinet should be properly installed. You can open and close 
them smoothly. The locks should work normally, and all keys should be complete. 

 

There  should  be  no  unnecessary  and  informal  labels  inside  the  cabinet  and  on  various 
boards. 

 

Blank panels should be installed completely. 

 

Fastening screws of various devices in the cabinet of the same model should be ready and 
tightened. 

 

Various boards of the equipment should be installed securely, and the fastening screws on 
the panel should be tightened. 

 

All  wiring  inlets  at  the  top  and  bottom  of  the  cabinet  should  be  installed  with  rodent-
resistant nets with seams no more than 1.5 cm in diameter, to prevent rodents and other 
small animals from entering the cabinet. 

 

Antistatic wrist straps should be provided in the cabinet. 

Installation Steps 

1.

 

Plan the available space before installing the cabinet. You must reserve sufficient space for 
front and back doors for maintenance. 

2.

 

Mount and fasten the cabinet at the designed location as planned. 

3.

 

Install the appropriate chute and cables. 

4.

 

Install the tray and wiring layer on the rack according to the configuration of one rack with 
one cabinet installed or one rack with multiple cabinets installed.  

3.4

 

Mounting into the Cabinet 

Precautions 

Before mounting QSW-6900-56LF into the cabinet, first verify that the front and back brackets 
of the cabinet are at the right locations. If the bracket is too far forward, the front panel of the 
equipment may be too close to the front door, so that the front door cannot be closed when the 
equipment is connected with network cables and pigtail fibers. Usually, you should reserve space 
of  at  least  10mm  between  the  front  panel  of  the  equipment  and  that  of  the  cabinet  after 
installation. Before mounting into a cabinet, you need to make sure the following conditions are 
met: 

Содержание QSW-6900-56LF Series

Страница 1: ...Installation Manual 0 Preface 1 www qtech ru QSW 6900 56LF Series Switches Hardware Installation and Reference Guide QSW 6900 56LF...

Страница 2: ...this document in any form or by any means without the prior written consent of QTECH is prohibited Exemption Statement This document is provided as is The contents of this document are subject to cha...

Страница 3: ...umed that the users of this switch are already familiar with the related terms and concepts of Ethernet Obtaining Technical Assistance QTECH Website https www qtech ru Technical Support Website https...

Страница 4: ...l 100G QSFP28 Ethernet Port 10G SFP Ethernet Port 10GBase T Ethernet Port Extension Module Slot Redundant Fan Redundant Power Supply QSW 6900 56LF 8 48 N A N A 3 1 1 1 An SFP port supports 10GBase R a...

Страница 5: ...rent range 3 6A Power Consumption Less than 300 W Optical Module The supported modules update at any time contact QTECH for details SFP Port Supported QSFP28 Port Supported FC Port Unsupported 10GBASE...

Страница 6: ...6900 56LF includes the chassis the power supply system and the heat dissipation system The power supply system Provides two power supply slots which support 1 1 power supply redundancy It is recommend...

Страница 7: ...to the switch status indicator of the switch back panel The label is movable and can be withdrawn from the device Users can mark the information such as asset name category code and registration date...

Страница 8: ...perform program downloading SFP port There are 48 10G SFP ports which support optical modules and DAC copper cables 1000BASE X compatible QSFP28 port There are 8 100G QSFP28 ports which support optic...

Страница 9: ...hes support 1 1 power supply redundancy To improve the stability and reliability of the entire system it is recommended to configure 1 1 power supply redundancy When the two power supply modules work...

Страница 10: ...in the front and at the back of the chassis at least 20 cm for ventilation It requires at least three fan modules to work normally Filler panels need to be installed in the unoccupied fan module slots...

Страница 11: ...power supply handle or the fan handle for these parts are not designed for bearing the entire weight of the device It will cause damage to the device or to your body if you hold these parts when remo...

Страница 12: ...are used Use an anti static shielding bag to properly store the board Do not let any clothes touch a circuit board An antistatic wrist strap can only prevent human static electricity from damaging the...

Страница 13: ...sulation or even leak electricity And sometimes the materials may suffer from mechanical performance change and metallic parts may get rusted On the other hand in an environment with low relative humi...

Страница 14: ...ng Requirements A good grounding system is the basis for the stable and reliable operation of the QSW 6900 56LF It is the key to prevent lightning stroke and resist interference Please carefully check...

Страница 15: ...of the propagation path When the energy often RF energy from a component arrives at a sensitive component via the space the energy is known as radiated interference The interference source can be eith...

Страница 16: ...ti static gloves stripping pliers crimping pliers crystal head crimping pliers wire cutters Fiber optic cleaning Tools Air laid paper fiber end microscope Meter Multimeter errormeter optic power meter...

Страница 17: ...power supply and wiring before installation Verify the following requirements before installation The installation location provides sufficient space for heat dissipation The installation location me...

Страница 18: ...should be installed securely and the fastening screws on the panel should be tightened All wiring inlets at the top and bottom of the cabinet should be installed with rodent resistant nets with seams...

Страница 19: ...m the plastic package Install the brackets at the side panels of the switch and fix the brackets with four M4 8FMO countersink screws at each side Figure 3 1 Installing Mounting Brackets Mounting the...

Страница 20: ...ts provided are only applicable for cabinets with depth of 800mm 1200mm Mounting the Switch to a Workbench In some cases users do not have the 19 inch standard cabinet The common solution is to place...

Страница 21: ...with a screwdriver to fix the fan module in the switch chassis Figure 3 4 Installing a Fan Module Insert the fan module smoothly Pay attention to the direction of the fan panel to avoid wrong inserti...

Страница 22: ...the package and confirm the input mode and the input parameters of the power module match the requirements Remove the power filler panel and take the plane printed with power information as the top p...

Страница 23: ...the location where the power module is removed to ensure the normal ventilation and dissipation and avoid the dust in the chassis Installing Power Cord Retainer Power cord retainer includes a strap a...

Страница 24: ...e 4 Plug the power cord into the connector Pass the power cord through the strap and adjust the ring by pressing buckle B until the power cord is fastened Figure 3 9 Installing Power Cord Retainer Rem...

Страница 25: ...used Do not use bare wire The grounding resistance for combined grounding should be less than 1 To guarantee the security of the person and the device the QSW 6900 56LF must be well grounded The groun...

Страница 26: ...ir with the RJ45 port into the appropriate interface according to the identification on the panel of the line card Distinguish the crossover cable and straight through cable 3 10 Binding the Cables Pr...

Страница 27: ...the Cables Verify that the fibers and twisted pairs match the ports Verify that the cables have been bound properly Verify that the cabling specification and connecting method are correct Verify that...

Страница 28: ...able to the serial port of the PC 2 Connect one end of the console cable RJ45 to the console port of the switch Setting Terminal Parameters Step One Start the PC and run the terminal simulation progra...

Страница 29: ...igure 4 3 In the column of Connect Using field select the serial port you want to use Figure 4 3 After the serial port is selected please click OK The Serial Port Parameter Setting window is displayed...

Страница 30: ...rrectly connected Check if the power supply voltage complies with the requirement of the switch Check if the console cable is correctly connected the terminal can be a PC used for configuration is alr...

Страница 31: ...indicator of the host or the extension module is red or flashing it indicates a failure in which case you need to find out the cause and turn off the power when necessary When the RWR1 PWR2 indicator...

Страница 32: ...ium Battery The built in lithium batteries can support the real time clock of the QSW 6900 56LF series switches without external power supply Please contact the technical support representatives of QT...

Страница 33: ...ch in the cabinet Check the power connection Check the installation of the power supply module Check the plug in units of each module Check the installation and fastening of the modules Check the indi...

Страница 34: ...fan tray does not work Fault Description After the system starts the fans in the fan module do not work or the Status indicator is OFF Troubleshooting Check if the connection between the fan module a...

Страница 35: ...The system runs normally After the fiber interface is inserted into the optical module and the optical fiber is properly connected the link cannot be set up Troubleshooting 1 Check whether the receiv...

Страница 36: ...C 11801 Ed2 1 TIA 568 C 2 Class E ISO IEC TR24750 TSB 155 Max Transmissio n Distance 100 m 100 m 100 m 37 m to 55 m Cabling System Bandwidth 600 MHz 500 MHz 250 MHz Description Meet the minimum perfor...

Страница 37: ...rd and uses up to 100m of 100 ohm CAT5 CAT5E or twisted pairs with higher standard The 1000BASE T port uses four pairs of wires for transmission all of which must be connected Figure A 1 shows the con...

Страница 38: ...ection of the twisted pairs of the 100BASE TX 10BASE T Fiber Connection For the fiber ports select single mode or multiple mode fibers for connection according to the fiber module connected The connec...

Страница 39: ...igure B 1 Schematic Diagram for the Power Arrester The power arrester is not provided and the user should purchase it to address the practical requirement Precautions for installation Make sure that t...

Страница 40: ...r for the double sided adhesive tape and paste the Ethernet port arrester to the switch framework The paste location for the Ethernet port arrester should be as close to the grounding terminal of the...

Страница 41: ...n to the following conditions during the actual installation to avoid influencing the performance of the Ethernet port arrester Reversed direction of the arrester installation You shall connect the ex...

Страница 42: ...er seven times greater than their respective diameters After cabling is fixed the bend radius of a common coaxial cable should be over seven times greater than its diameter The bend radius of this typ...

Страница 43: ...hould maintain a distance not less than 30 mm The binding rack and cabling slot inside and outside the cabinet should be smooth without sharp corners The metal hole traversed by cables should have a s...

Страница 44: ...will not affect device running or cause device damage or cable damage during commissioning 220V and 48V power cords cannot be bundled on the guide rails of moving parts The power cables connecting mov...

Страница 45: ...n and cable Do not use self tapping screws to fasten terminals Power cables of the same type and in the same cabling direction should be bundled up into cable bunches with cables in cable bunches clea...

Страница 46: ...Recommendations in Installation 46 www qtech ru For wiring terminal blocks such as air switches of the cold pressing terminal type the metal part of the cold pressing terminal should not be exposed o...

Страница 47: ...s windstorm and heavy rain as well as away from dust If the dust is unavoidable keep the door and window away from the pollution source The machine room should be away from the residential area Otherw...

Отзывы: