*Available with 2 elements
Clearance Chart:
For safe and efficient operation, maintain at least the following
minimum clearances at all times (See Fig. 1):
Bottom of Heater to Finished Floor:
• Front Inlet Models: (max 250 watts per foot)
- May be installed on floor if under 250 watts per foot.
However, for best performance, install bottom of heater
approximately 3 inches (76 mm) off floor. For models 250
watts per foot or more, bottom of units must be mounted at
least 2” off floor.
• Bottom Inlet Models:
- 100-250 watts per foot – 2 inch (51 mm)
Top of Heater to Ceiling (all models):
- Minimum 36 inches (914 mm)
Top of Heater to Bottom of Drapes (See Example 2):
- Minimum 6 inches (152 mm)
IMPORTANT NOTE: Certain fabrics and vinyl materials (such
as vinyl blinds) may become damaged by the heated air from
the heater and should not be installed above the heater.
Front of Heater to Full Length Drapes (See Example 1):
- Minimum between bottom of drapes and floor – 2-1/2 inches
(64 mm)
- Minimum between top of drapes and ceiling – 1/2 inch (13
mm)
- Minimum between front of heater and nearest fold of drape –
2 inches (51 mm)
Top of Heater to Bottom of Window Sill:
- Minimum 12 inches (305 mm)
2
No. 12 AWG
No. 10 AWG
No. 8 AWG
5
4
2
7 Amps
9 Amps
12.0 Amps
5 Amps
7 Amps
10 Amps
4.5 Amps
6 Amps
-
Copper wire
size 90º C
Max. No.
wire installed
in wireway
Up to 2
conductors
3 to 4
conductors
4 to 5
conductors
Maximum Allowable Current
Table B. Sizing Field Installed Wiring
Catalog
Length
Watts
Total
Amperage
Number
"L"
per ft.
Watts
120V
208V
240V
277V
347V
600V
1125
125
250
--
--
--
--
--
--
1150
24”
150
300
--
1.4
1.3
--
--
--
1188
(610mm)
188
376
3.1
1.8
1.6
1.4
--
--
1250
250
500
--
2.4
2.1
1.8
--
--
2100
100
200
1.7
1
0.8
--
--
--
2125
28"
125
250
2.1
1.2
1
0.9
--
--
2150
(711mm)
150
300
2.5
1.4
1.3
1.1
--
--
2188
188
376
3.1
1.8
1.6
1.4
--
--
2250
250
500
4.2
2.4
2.1
1.8
1.4
--
3100
100
300
2.5
1.4
1.3
1.1
--
--
3125
3'
125
375
3.1
1.8
1.6
1.4
1.1
--
3150
(914mm)
150
450
3.8
2.2
1.9
1.6
1.3
--
3188
188
564
4.7
2.7
2.4
2
1.6
--
3250
250
750
6.3
3.6
3.1
2.7
2.2
--
4100
100
400
3.3
1.9
1.7
1.4
1.2
--
4125
4'
125
500
4.2
2.4
2.1
1.8
1.4
--
4150
(1219mm)
150
600
5
2.9
2.5
2.2
1.7
--
4188
188
752
6.3
3.6
3.1
2.7
2.2
1.3
4250
250
1000
8.3
4.8
4.2
3.6
2.9
1.7
5100
100
500
4.2
2.4
2.1
1.8
1.4
--
5125
5'
125
625
5.2
3
2.6
2.3
1.8
1
5150
(1524mm)
150
750
6.3
3.6
3.1
2.7
2.2
1.3
5188
188
940
7.8
4.5
3.9
3.4
2.7
1.6
5250
250
1250
10.4
6
5.2
4.5
3.6
2.1
6100
100
600
5
2.9
2.5
2.2
1.7
1
6125
6'
125
750
6.3
3.6
3.1
2.7
2.2
1.3
6150
(1829mm)
150
900
7.5
4.3
3.8
3.2
2.6
1.5
6188
188
1128
9.4
5.4
4.7
4.1
3.3
1.9
6250
250
1500
12.5
7.2
6.3
5.4
4.3
2.5
7100
100
700
5.8*
3.4
2.9
2.5
2
1.2
7125
7'
125
875
7.3*
4.2
3.6
3.2
2.5
1.5
7150
(2134mm)
150
1050
8.7
5
4.4
3.8
3
1.8
7188
188
1316
10.9*
6.3
5.5
4.8
3.8
2.2
7250
250
1750
14.5*
8.4
7.3
6.3
5
2.9
8100
100
800
6.7*
3.8
3.3
2.9
2.3
1.3
8125
8'
125
1000
8.3*
4.8
4.2
3.6
2.9
1.7
8150
(2438mm)
150
1200
10
5.8
5
4.3
3.5
2
8188
188
1504
12.5*
7.2
6.3
5.4
4.3
2.5
8250
250
2000
16.7*
9.6
8.3
7.2
5.8
3.3
9100
100
900
7.5*
4.3
3.8
3.2
2.6
1.5
9125
9'
125
1125
9.4*
5.4
4.7
4.1
3.2
1.9
9150
(2743mm)
150
1350
11.2*
6.5
5.6
4.9
3.9
2.3
9188
188
1692
14.1*
8.1
7.1
6.1
4.9
2.8
9250
250
2250
18.8*
10.8
9.4
8.1
6.5
3.8
10100
100
1000
8.3*
4.8
4.2
3.6
2.9
1.7
10125
10'
125
1250
10.4*
6
5.2
4.5
3.6
2.1
10150
(3048mm)
150
1500
12.5*
7.2
6.3
5.4
4.3
2.5
10188
188
1880
15.7*
9
7.8
6.8
5.4
3.1
10250
250
2500
--
12
10.4
9
7.2
4.2
Table A - DBSL Technical Data
CEILING
FLOOR
FLOOR
DRAPES
HEATER
W
A
L
L
W
A
L
L
CEILING
MIN. 1/2”
(13 mm)
MIN. 2”
(51 mm)
MIN. 2-1/2”
(64 mm)
MIN. 1/2”
(13 mm)
MIN. 6”
(152 mm)
HEATER
DRAPES
Fig. 1: Clearance for Drapery
Example 1
Example 2