INSTALLATION AND OPERATION MANUAL SOLAR MODULES – Q.PRO L-G2 – HANWHA Q CELLS USA CORP.
INSTALLATION AND OPERATION MANUAL SOLAR MODULES – Q.PRO L-G2 – HANWHA Q CELLS USA CORP.
2 PLANNING
2.3 Mounting options
Specifications
MODULE TYPE
MOUNTING OPTION
CLAMPING RANGE
1
TEST LOAD ACC. IEC 61215 PUSH/PULL [PA]
Q.PRO L-G2
CL1 (4 point clamping on
long side)
0 - 9.84 (0 - 250)
2400/2400
9.88 - 19.69 (251 - 500)
5400/4000
IP1 (Slide-in / long mo-
dule side)
5400/2400
IP2 (Slide-in / short
module side)
2400/2400
FB1
5400/4000
1
Distance between outer edge of module and middle of the clamp.
DISTANCE BETWEEN MODULES
Ä
Maintain an interval of at least 0.39 in (10 mm) between two modules along the short side
Ä
Maintain an interval of at least 0.20 in (5 mm) between two modules along the long side
MOUNTING OPTIONS CL1
Ä
Ensure, that the subconstruction does not run below the junction box.
Ä
Ensure, that the connection cables of the junction box don‘t run between laminate and substructure.
MOUNTING OPTIONS FB1
Ä
Use M8 corrosion-proof screws and washers (min. diameter 0.63 in (16 mm)).
Ä
Ensure, that the connection cables of the junction box don‘t run between laminate and substructure.
•
The fastening points are located on the backside of the module frame.
Module Selection
For detailed key electrical data, please refer to the product data
sheet for the respective product.
Ä
Only connect modules of the same type and the same power
class.
Safety Factor
During normal operation, a module may generate a greater current
and / or higher voltage than that determined under standardized test
conditions. Please use a safety factor of 1.25 for the following:
•
Calculating the voltage measurement values (V
oc
) of components
•
Calculating the current measurement values (I
SC
) of conductors
•
Sizing of control systems connected to the outlets of the solar
modules
Ä
Please follow the valid national guidelines for the installation
of electrical systems (refer to section 690-8 of the NEC for an
additional multiplying factor of 125 percent [80 percent derating]
which may be applicable).
Series Connection
Connection of modules in series is only permitted up to the
maximum system voltage as listed in the applicable data sheet.
Ä
Take into account all possible operating situations and all relevant
technical norms and regulations when designing the system.
This will ensure that the maximum system voltage, including all
necessary safety margins, is not exceeded.
Ä
Take the voltage limit of the inverter into account when determining
the maximum number of modules in the string.
Parallel Connection
Modules may be damaged by the occurrence of reverse currents
(caused by module defects, ground leaks, or defective insulation).
Ä
Ensure that the maximum reverse current load capacity indicated
in the data sheet is observed.
In order to limit reverse currents that may occur, we recommend
using the following safety options:
1) Layout with a limited number of parallel connected strings :
Without undertaking further current blocking measures, a maximum
of two module strings may be operated in parallel on an inverter or
MPP tracker.
2) Layout with string fuses :
Place fuses for each string of modules at the plus and minus ends.
Observe the maximum permitted number of strings as indicated
in the specifications provided by the respective string fuse manu
-
facturer and the technical guidelines.
NOTE!
When installing different product versions, the lowest minimum
permitted reverse current load capacity applies.
Inverters
Inverters with or without transformers may be used.
2.4 Electrical layout