background image

19

INSTALLATION AND OPERATION MANUAL SOLAR MODULES – Q.PRO L-G2 – HANWHA Q CELLS USA CORP.

18

INSTALLATION AND OPERATION MANUAL SOLAR MODULES – Q.PRO L-G2 – HANWHA Q CELLS USA CORP.

5       GROUNDING

Functional grounding

• 

When using an installation tilt of < 5° a functional grounding at 
the negative generator conncetion must be implemented.

 

Ä

Ensure that the difference of potential between the negative 
generator connection and the PE(N) of every MPP tracker of the 
respective inverters is 0 V.

 

Ä

Follow the directions of the inverter manufacturer.

 

Ä

Only use inverters which include lincensed grounding kits. 

Protective Grounding

In order to prevent electrical shock or fire, the frame of the module 

as well as any non-current-carrying metal parts of the system must 
be grounded. While this section provides some information about 
grounding the Q CELLS frames and modules, reference should be 

made  to  local  statutes  and  regulations  for  specific  requirements 

on grounding. The U.S. National Electrical Code addresses these 
issues in Article 250. 

Proper grounding is achieved by bonding all exposed non-current-
carrying metal equipment to the appropriately sized equipment 
grounding conductor (EGC) or racking system that can be used for 
integrated grounding. 

Q CELLS frames are protected from corrosion with an anodized 
coating, which has to be penetrated in order to ensure proper 
bonding. The different methods listed below are suggested 
methods for an appropriate bond between the frame and the EGC 
or racking system (that will have to be properly grounded). The 
method appropriate for any individual installation will depend on 
multiple factors.

Option A: Use of a grounding lug

A listed grounding lug can be bonded to the frame using the 
grounding holes pre-drilled in the frame. These holes are marked 

• 

Dimensions shown are in inches.

0.177” (+0.008/-0)

±0.08

0.79”

0.47”

±0.08

PV Laminate

Backing Nut (Stainless Steel)

Toothed Lock Washer (Stainless Steel
or tin-plated metal)

Grounding Lug (Stainless Steel)

Equipment 

Grounding 

Conductor

Aluminum 

Frame

Screw (Stainless Steel)

with a ground symbol, as shown below on the frame section drawing: 

To  install  the  grounding  lug,  follow  the  specified  instructions  of 

the manufacturer. The grounding lug should be made of stainless 
steel or tin plated metals such as aluminum to avoid corrosion. The 
grounding lug should be attached to the frame grounding hole using 
a stainless steel screw, toothed lock washer or KEPS nut (in order 
to penetrate the anodized layer) and backing nut. Care should be 
taken to avoid the use of grounding hardware of dissimilar metals, 
which may lead to corrosion

Option B: Integrated grounding methods

The Q CELLS modules can be bonded with the racking 

system  using  UL1703  or  UL2703  certified  integrated 

grounding methods. The racking system will then have to be 
grounded so that the overall system is properly grounded. 
The listed racking system and grounding device should be 
installed in accordance with the manufacturers’ instructions. 
An example of such integrated grounding method is the use 
of a WEEB clip or Schletter plate between the module and the 
racking system, when mounting the module. The WEEB washers 
are generally compatible with Q CELLS modules, however each 

combination  module  /  racking  system  requires  a  specific  WEEB 

washer size. Note that WEEB clips are intended for single use only; 
they must not be reused after removal or loosening. Refer to Wiley’s 

installation instructions for the specific use of WEEB washers.

An example of such integrated grounding method is the use of a 
washer recognized as meeting UL2703 requirements between the 
module and the racking system, when mounting the module. For 
example, WEEB washers are generally compatible with Q CELLS 
modules, however each combination module / racking system 

requires  a  specific  WEEB  washer  size.  Note  that  WEEB  washers 

are intended for single use only; they must not be reused after 
removal or loosening. Refer to Wiley’s installation instructions for 

the specific use of WEEB washers.

FAULTS AND DEFECTS

DANGER!  
Risk of fatal injury due to electric shock!

 

Ä

Do not attempt to fix any problems yourself (e.g., glass 

cracks, damaged cables).

 

Ä

Please contact an installer or Q CELLS Technical Customer 
Service Department.

 

Ä

Do not disconnect modules yourself.

 

Ä

Please commission a trade specialist.

 

Ä

Dispose of modules in accordance with the local disposal  
regulations.

7 DISPOSAL

Содержание Q.PRO L-G2

Страница 1: ...Valid for North America Q PRO L G2 INSTALLATION AND OPERATION MANUAL ...

Страница 2: ...Risk of fatal injury Attention Risk of serious injury or damage to property Note Risk of damage to product Units Where both metric and U S units for example inches are shown metric units are definitive References to Data Sheet or Module Data Sheet refer to the Module Data Sheet applicable to the module being used Safety Regulations The solar module operator is responsible for compliance with all a...

Страница 3: ...ing the formal requirements for solar power systems Ä Ä Please be sure to contact the relevant local authorities and energy providers regarding regulations and permit requirements prior to installation of the solar power system Your financial success depends on the fulfillment of these requirements Other applicable documents This installation manual is only valid in combination with the following ...

Страница 4: ... expansion and contraction due to temperature fluctuations Ä Ä Ensure that no mechanical stresses e g caused by vibrations twisting or expansion are generated on the module Ä Ä Ensure that the clamps and the mounting frame are compatible Clamp System Requirements Use customary clamps that comply with the requirements Clamp width 1 50in 38 mm Clamp height compliant with a 1 57in 40 mm frame height ...

Страница 5: ...omponents Calculating the current measurement values ISC of conductors Sizing of control systems connected to the outlets of the solar modules Ä Ä Please follow the valid national guidelines for the installation of electrical systems refer to section 690 8 of the NEC for an additional multiplying factor of 125 percent 80 percent derating which may be applicable Series Connection Connection of modu...

Страница 6: ...cool and dry rooms The packaging is not weatherproof DANGER Risk of fatal injury due to electric shock Ä Ä Do not install damaged modules Ä Ä Inform your vendor of any damages immediately 3 1 Safety and transport 3 INSTALLATION NOTE Module damage may occur Ä Ä Do not drop modules NOTE Module damage may occur Ä Ä Only make modifications to the module which have been confirmed in writing by Q CELLS ...

Страница 7: ...nly use dry insulated tools Ä Ä Do not carry out the installation alone Only install undamaged modules and components Ä Ä Do not drill any other holes e g do not drill any additional holes 3 2 Preparation of installation 3 INSTALLATION Ä Ä Maintain an interval of at least 0 39 in 10 mm between two modules along the short side and 0 20 in 5 mm along the long side 0 39 in 10mm 0 2 0 i n 5 m m Option...

Страница 8: ...ior to separation Ä Ä Be sure to observe the specified time intervals after switching off the inverter High voltage components need time to discharge DANGER Risk of fatal injury due to electric shock Ä Ä Never open the junction box Ä Ä Change of bypass diodes is only allowed by qualified and trained personnel in disconnected and covered state DANGER Risk of fatal injury due to electric shock Ä Ä N...

Страница 9: ...hat all electrical components are in a proper dry and safe condition A module with min 47 24 in 1 200 mm long cable in portrait orientation can be wired as a 2nd next neighbor 2nd next neighbor Wiring without a return cable Standard wiring with a return cable Inverter Inverter 1 2 4 3 Connection of modules 4 ELECTRICAL CONNECTION Ä Ä Ensure that all necessary safety and functional tests have been ...

Страница 10: ...ame section drawing To install the grounding lug follow the specified instructions of the manufacturer The grounding lug should be made of stainless steel or tin plated metals such as aluminum to avoid corrosion The grounding lug should be attached to the frame grounding hole using a stainless steel screw toothed lock washer or KEPS nut in order to penetrate the anodized layer and backing nut Care...

Страница 11: ... access the installation area alone or without taking adequate security precautions Ä Ä Please commission a trade specialist Clean the modules as follows NOTE Module surface damage may occur Ä Ä Remove snow and ice without force e g with a very soft broom Ä Ä Do not scratch off dirt Ä Ä Rinse dirt off with lukewarm water dust leaves etc Ä Ä Use a soft cellulose cloth kitchen roll or sponge to care...

Страница 12: ...ORP 300 Spectrum Center Drive Suite 1250 Irvine CA 92618 USA TEL 1 848 748 59 96 EMAIL q cells usa q cells com WEB www q cells us Subject to change without notice Hanwha Q CELLS GmbH Installation manual Q PRO L G2_2015 06_Rev02_NA ...

Отзывы: