4.3
Wiring
If the power ground terminal and the negative 4–20mA terminal in the controller are internally connected
(non-isolated 4–20mA input), it is unnecessary to connect the 4–20mA negative wire (green) to the 4–20mA
negative terminal in the controller. If a separate DC power supply other than that from the controller is used,
make sure that the output from the power supply is rated for 22–26 VDC @ 65 mA.
*
NOTE
*
The negative 24V power terminal (power ground) and the negative 4–20mA ter-
minal on the ST-590 sensor are internally connected.
Follow the wiring table below to connect the ST-590 sensor to a controller:
Table 2.
Wire Color
Designation
Red
24V +
Black
24V Power ground
White
4–20mA +
Green
*
4–20mA -
Blue
RS-485 A
Yellow
RS-485 B
Clear
Shield, earth ground
*
Internally connected to the power
ground
4.4
Connecting via Bluetooth
A Bluetooth adapter (P/N: MA-WB) can be used to connect a ST-590 sensor to a smart phone with the
uPyxis®
Mobile App or a computer with the
uPyxis®
Desktop App.
Figure 4.
Bluetooth connection to ST-590 sensor
ST-590 User Manual
| +1 (866) 203-8397
7