Copyright Pyroban Ltd. Issue 1 Page 17 of 32
Part number PM1083ENG
Location of Components
Select positions for Gascheka duo components with a low
risk of mechanical impact and where the operation of the
vehicle, driver’s view, access to doors or covers etc. is not
compromised.
Control Unit
(a) Remove the bracket from the Control Unit and
choose a position that is visible and within easy
reach of the driver. Consider also, easy cable
access to the rear of the unit.
(b) Mark hole positions using bracket as template; drill
holes. Fit the bracket to the vehicle and secure with
four M4 screws, spring washers, plain washers and
nuts supplied.
(c) Loosely mount the Control Unit & support bracket;
install the Gas Head Lead to the Control Unit and
secure Lead to the bracket.
(d) Fit the Control Unit Support Bracket 300814200
Gas Sensing Head
(a) Gas sensing heads contain sensitive
electronic components and may break if
subjected to impact or dropped.
(b) Mount Gas Sensing Heads on the vehicle so
as to be readily exposed to any flammable
atmosphere but protected from mechanical
damage and environmental contamination
(dirt, water spray etc.). For solvent
applications the head should be mounted
close to the ground (max 0.6m).
(c) Mount the Gas Sensing Head between 20
o
and 60
o
to the horizontal using the two
brackets and two M8 bolts supplied. Failure
to do this may cause the system to fail the
automated gas response test and
compromise response time.
Gas Head
Example of location
Bracket