Connect the cables to inverter
The
power cables’ current capacity
is
120A(peak)
. If the battery string
’
s current over this limit,
must configure 2 pairs of external power cables to reach
240A
.
If nominal current of battery system is higher than 100A, it is suggested to use 2 pairs of cables.
(5)
There shall be a manual disconnecting device (breaker, etc.) between battery system and
inverter.
B. Power On
Double check all the power cable and communication cable, check the ADD switch.
(1)
Switch the breaker between battery system and inverter.
(2)
Switch power on
Switch on all the battery modules:
(3)
The one connects to inverter is the
Master Battery
Module, others are slaves (1 master battery
configure with maximum 19 slave batteries).
(4)
Press the Start Button (
SW
) of
master battery
to power on, all the battery LED light will be on
after master battery starts.