then battery will black start to support inverter and after inverter turned on and set up
communication, then BMS is ready for work.
Caution:
When the breaker is tripped off because
of
over current or short circuit, must wait after
10min to turn on it again, otherwise may cause the breaker damage.
Warning:
If has failure during the self-check, must debug the failure then can start next step.
If the “STATUS” lamp shows orange from beginning, it means there has some failure in the
battery string, the Power Relays in BMS will open, must debug at first.
Note:
The LED lamp will be off in 20sec without any operation.
Caution:
During first time power on, the system will require to do fully charge progress for SOC
calibration purpose.
Caution:
it is suggested to fully charge the whole Battery Energy Storage System (BESS) first after
installation or after long time storage without charging. Depending on the soc level,
there will be a regularly (3 month) fully charge requesting during continuous operation
as well, it will be handled automatically by the communication between BESS and
external device.
.